To add a network PDU:
1.
Select
Power Management – Network PDUs.
2.
Click
Add
.
3.
Enter the IP address of the network PDU.
4. Select the PDU type.
5.
Enter the interval to poll the PDU for the status of the outlets.
6. Enter the community name that has write permission in the PDU.
Network UPS
Liebert GXT4 UPS devices with installed Liebert Intellislot Unity Cards, connected to the network with SNMP (read/write)
enabled, may be monitored and controlled. The console server enables authorized users to monitor battery information,
system input and output information, and to control output receptacles.
NOTE: SNMP needs to be enabled and have one community with write permission enabled in the UPS.
By selecting the Network UPS node, an administrator can add new network UPS devices or edit the configuration of current
ones.
3.3.13 Sensors
Internal
The console server has sensors that monitor the internal temperature. You can specify an operating range for the console
server that fits its environment. There are two internal temperature sensors that can generate event notifications: the CPU
temperature sensor and the Board temperature sensor.
CAUTION: Do not use values that exceed the maximum and minimum temperatures.
Appendices
on page 69.
To configure the temperature sensors:
1.
Click
Sensors - Appliance - Internal
to open the Internal page displaying both the CPU and Board temperature
sensors.
2.
In the Maximum Temperature field for either the CPU or Board temperature sensor, enter the temperature in
degrees Celsius that, if exceeded, will generate an event notification.
3.
In the Maximum Temperature Threshold field for either the CPU or Board temperature sensor, enter the
temperature threshold in degrees Celsius below the maximum temperature.
NOTE: The Maximum Temperature Threshold field will define a region around the maximum temperature. When the
temperature exceeds the Maximum Temperature plus Threshold, an event notification will be generated. When the
temperature falls below the Maximum Temperature minus Threshold, an even notification that the console server has
returned to normal operating temperature will be generated. This is also true for setting the minimum temperature
threshold.
4. In the Minimum Temperature field, enter the temperature in degrees Celsius that, if the console server’s
temperature falls below, will generate an event notification.
5.
In the Minimum Temperature Threshold field, enter the temperature threshold in degrees Celsius above the
minimum temperature.
6. Click
Save
.
3 Accessing the Console System via the Web UI
65
Содержание Avocent ACS800
Страница 1: ...Avocent ACS800 8000 Advanced Console Server Installer User Guide ...
Страница 40: ...8 Click Save Vertiv Avocent ACS800 8000 Advanced Console Server Installer User Guide 36 ...
Страница 83: ...Vertiv Avocent ACS800 8000 Advanced Console Server Installer User Guide 79 This page intentionally left blank ...
Страница 98: ...Vertiv Avocent ACS800 8000 Advanced Console Server Installer User Guide 94 This page intentionally left blank ...
Страница 99: ...Vertiv Avocent ACS800 8000 Advanced Console Server Installer User Guide ...