PARAMETER
DESCRIPTION
Physical
RJ-45 Pin-Out
Defines the serial port pinout as Auto, Cyclades or Cisco. Default: Auto.
Status
Defines the status of the serial port as either enabled or disabled. Default: Disabled.
Speed
Defines the speed as 1200, 2400, 4800, 9600, 19200, 38400, 57600,115200 or 230400. Default: 9600.
Parity
Defines the parity as either Even, Odd or None. Default: None.
Data Bits
Defines the data bits as either 5, 6, 7 or 8. Default: 8.
Stop Bits
Defines the stop bits as either 1 or 2. Default: 1.
Flow Control
Defines the flow control as none, hardware, software, RxON software or TxON software. Default: None.
Power
UPS Type
Defines the type or vendor of the UPS connected to the serial port. Default: Liebert GXT4.
PDU Type
Defines the type or vendor of the PDU connected to the serial port. Default: Auto.
•
Auto - the vendor is detected.
•
Avocent-Cyclades - Avocent-Cyclades PM PDU family.
•
Vertiv - Vertiv PDUs
•
SPC - SPC power control device family.
•
ServerTech/Server Tech PRO2 - Server Tech family.
•
Raritan - Raritan PX G2 PDU family.
•
APC - APC rPDU2 family.
•
Eaton - Eaton ePDU G3 PDUs.
•
Geist - Geist PDU family.
Enable Speed Auto Detection
When enabled, detects the speed of the port. Default: Disabled.
Polling Rate
The interval in seconds to update information from the PDU. Default: 20.
For Avocent/Cyclades PDUs
Power Cycle Interval
The interval in seconds between Off and On actions for the power cycle command. Default: 15.
Syslog
When enabled, the PDU will send syslog messages to the appliance. Default: Enabled.
Buzzer
Enables or disables the PDU’s buzzer. Default: Enabled.
SW Overcurrent Protection
When enabled, the software’s overcurrent protection is on. Default: Disabled.
Table 3.13 Power Parameters
To copy/clone the configuration of one port to other ports:
1.
Select
Ports - Serial Ports
.
2.
Click the checkbox for the serial port you want to clone.
3.
Click the
Clone
button.
4. Enter the serial port(s) to be configured in the Copy Configuration To field and click
Save
.
NOTE: If the selected port is configured as a CAS Profile, the following parameters will not be copied: Port Name, TCP
Port Alias, IPv4 Port Alias, IPv6 Port Alias and Power (merged outlets).
To reset one or more serial ports to their factory configuration:
1.
Select
Ports - Serial Ports.
Vertiv™ | Avocent® ACS800/8000 Advanced Console Server Installer/User Guide
40
Содержание Avocent ACS800
Страница 1: ...Avocent ACS800 8000 Advanced Console Server Installer User Guide ...
Страница 40: ...8 Click Save Vertiv Avocent ACS800 8000 Advanced Console Server Installer User Guide 36 ...
Страница 83: ...Vertiv Avocent ACS800 8000 Advanced Console Server Installer User Guide 79 This page intentionally left blank ...
Страница 98: ...Vertiv Avocent ACS800 8000 Advanced Console Server Installer User Guide 94 This page intentionally left blank ...
Страница 99: ...Vertiv Avocent ACS800 8000 Advanced Console Server Installer User Guide ...