VL-12CT96/7 Analog & Digital I/O Card
4-11
Analog Output Data Representation
The VL-12CT96/7 converts 12-bit, two’s complement digital words into ±5V, ±10V, or 4-20 ma output
signals. The output is divided into 4096 steps. The code 0000H produces an analog output of 0 Volts
(ground). Positive digital values produce positive analog output voltages, and negative digital values
(i.e., -1 = FFFFH) produce negative analog output voltages.
The formulas for calculating analog or two’s complement digital values are given by:
Analog
Digital =
————
Analog = Step
×
Digital
Step
Where:
Analog
= Applied voltage
Digital
= A/D Conversion Data
Step
= 0.00244140625
(±5V Range)
0.0048828125
(±10V Range)
0.0000244140625
(±50 mV Range)
0.000048828125
(±100 mV Range)
±5V Output
±10V Output
4-20 ma Output
Output Data
Voltage
Voltage
Current
(Hex)
(Dec)
Comment
+4.9976
+9.9951
20.0000
07FF
2047
Maximum positive voltage
+2.5000
+5.0000
12.0000
0400
1024
Positive half scale
+1.2500
+2.5000
8.0000
0200
512
Positive quarter scale
+0.00244
+0.00488
4.0078
0001
1
Positive 1 LSB
0.0000
0.0000
4.0000
0000
0
Zero (ground output)
-0.00244
-0.00488
Not
allowed
FFFF
-1
Negative 1 LSB
-1.2500
-2.5000
Not
allowed
FE00
-512
Negative quarter scale
-2.5000
-5.0000
Not
allowed
FC00
-1024
Negative half scale
-5.0000
-10.0000
Not
allowed
F800
-2048
Maximum negative voltage
Figure 4-16. Two’s Complement Data Format
Registers — Analog Output Registers
Содержание VL-12CT96
Страница 2: ...ii VL 12CT96 7 Analog Digital I O Card ...
Страница 26: ...2 20 VL 12CT96 7 Analog Digital I O Card ...
Страница 32: ...3 6 VL 12CT96 7 Analog Digital I O Card ...
Страница 62: ...7 4 VL 12CT96 7 Analog Digital I O Card ...
Страница 65: ...VL 12CT96 7 Analog Digital I O Card 8 3 VL 12CT96 7 Parts Placement Reference ...