WinterWarm Fireplace Insert or System
2000941
The listed chimneys and their manufacturers are:
American Metal Products
Ameri-Tec Model HS
Condensation
Engineering Corp.
Model HS
GSW Building Product Co.
Model SC
Metal Fab, Inc.
Model TG
Security Chimneys Ltd.
Model ASHT
Selkirk Metalbestos
Model SSII
Simpson Dura-Vent
Model SDP
In the United States, do not use any other chimney
system with the WinterWarm Fireplace System.
In Canada, the WinterWarm Fireplace System is listed
for use with any 200mm diameter prefabricated chim-
ney tested and listed to the High Temperature (650
°
C)
Chimney Standard, ULC S-629.
Guidelines for an Outside Air Supply
Outside air may be introduced to the WinterWarm at
either of two available ports: at the lower left corner of
the back of the cabinet (as viewed from the front), or at
the lower left corner of the left side panel.
An outside air duct must be 3" (75mm) in diameter,
must be no longer than 20' (6m), and must not have
more than three elbows. No part of the outside air duct
(including the outside air inlet) may be higher than the
89"
(2260mm)
Chimney Cap
Storm Collar
Roof Support Package
Flashing
Firestops
Wall Band
Offset
Firestop
Chimney Section
Anchor Plate
Front
Cabinet
FP1094
Fig. 30 Typical chimney components used in the installation
of a WinterWarm Fireplace System.
cut-out panel on the WinterWarm shroud, and it should
terminate at an outside air source. It may not terminate
in a garage or basement, nor near another fuel-fed
appliance. The air inlet must be covered by a wire
mesh screen (not included) with openings not larger
than 1/4" x 1/4" (6 x 6mm) to prevent rodents from
entering from the outside. The optional duct kit in-
cludes a valve to close off incoming air when the
WinterWarm is not in use.
Hearth Requirements
Unless the Fireplace System Cabinet will be installed
on a completely noncombustible surface such as
unpainted concrete over earth, a floor protector must be
used in the installation for protection against radiated
heat as well as protection against spilled coals and
embers.
Floor protectors must extend at least 8" (203mm) from
the side of the door opening, making a total width of 40"
(1016mm). In addition, the floor protector must extend
from the front door opening a minimum of 16" (410mm) in
the United States and 18"(460mm) in Canada. (Fig. 31)
A
B
B
C
Flue
Collar
Glass
Door
United States
Canada
A. 16“ (406mm)
18” (457mm)
B. 8” (203mm)
8” (203mm)
C. 40” (1016mm)
40” (1016mm)
FP1085
NOTE: Measuring form the door opening of the insert to the
fireplace opening adds 3
¹⁄₂
” (90mm) to the total depth of the
hearth protector.
Fig. 31 A floor protector must satisfy these requirements.
The approved construction of a floor protector calls for
24 gauge galvanized sheet metal covered with a listed
floor protector material that is at least 7/16" (11mm)
thick (such as Wonderboard® or Durock®). The floor
protector may be covered with a noncombustible
decorative material if desired.