4
WinterWarm Fireplace Insert or System
2000941
Section I Operation
Your WinterWarm’s Controls
and What They Do
Three controls regulate the performance of your
WinterWarm: A primary air control supplies oxygen for
the fire, a damper directs air flow within the fireplace,
and a variable-speed fan control, or rheostat, regulates
the warm air flow into the room. (Fig. 2)
Primary Air Control
A single air control regulates the amount of heat the fire
will produce and how long it will burn.
The primary air control is located above the upper left
corner of the door. It is the top-most of the two brass-
capped controls located there (the brass knob on the
bottom regulates the fan), and is the primary source of
air for starting, maintaining, and reviving the fire.
Generally, more air entering the stove makes the fire
burn hotter and faster, while less air prolongs the burn.
The WinterWarm’s air supply is open to the maximum
when the control lever is moved to the left, and closed
when moved to the far right. It may be set anywhere
between the two extremes, however, depending on the
amount of heat desired.
To complement the manual setting of the air control, the
WinterWarm has an internal automatic thermostat that
ensures an even delivery of heat at the manual setting
you select.
The Damper
The damper directs air flow within the fireplace.
The damper is operated by moving the lever located
above the upper right corner of the door. It has two
positions: Open, to start or revive the fire (Fig. 3); and
closed (Fig. 4), for normal operation. The damper is
open when the lever is to the far left, and closed when
to the far right. There are no intermediate settings for
damper position.
When the damper is closed, the front door automati-
cally locks to prevent the door being inadvertently
opened when the fireplace is in its catalytic mode. This
could cause smoke to spill into the room.
To open the damper, lift up on the lever and move it to
the far left. The lock will disengage, allowing you to
open the front door.
To close the damper, move the lever to the right,
continuing past the resistance to lock the damper in
position. (The door handle must be positioned verti-
cally before the lock mechanism will engage.)
Primary Air Control (Top Lever)
Fan Speed Control
(Rheostat) (Bottom
Lever)
Damper Control
Door Handle
Optional Outside
Air Control
FP1070
Fig. 2 All WinterWarm controls are located conveniently on
the front.
Damper Closed
Catalytic
Combustor
FP1072
Fig. 4 Damper is closed: Smoke is channelled through the
catalytic combustor where much of it can be burned.
Damper
Open
FP1071
Fig. 3 The damper is open; Smoke is vented directly to the
chimney.