8
20306746
WDV See-thru Gas Fireplace
PRE-INSTALLATION INFORMATION
MANTEL CLEARANCES
NOTE: The combustible area above the facing must
not protrude more than
3
⁄
4
" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
6”
5”
3”
4
¹⁄₂
”
45°
1”
3
¹⁄₂
”
FP2423
mantel leg
1
¹⁄₂
”
2
¹⁄₂
”
FP2746
Side of Fire-
place Opening
Figure 5 -
Mantel clearances
Top View
CLEARANCES TO COMBUSTIBLES
Follow these instructions carefully to
ensure safe installation. Failure to follow
instructions exactly can create a fire
hazard.
The appliance cannot be installed on a
carpet, tile or other combustible material
other than wood flooring. If installed on
carpet or vinyl flooring, the appliance
shall be installed on a metal, wood or
noncombustible material panel extending
full width and depth of the appliance.
W
ARNING
54” (1372 mm)
Minimum
Ceiling
12” (305 mm)
Max. Depth
2
1
/
2
” (64 mm)
Max Depth
6” (152 mm)
Min. From
Opening
12” (305 mm) Min.
From Opening
6”
(152 mm)
Min.
FP2421
mantel clearances
5
³⁄₄
” (146 mm)
Min. to Combustibles
Figure 4 -
Ceiling and Sidewall Clearances for
Both Sides of Fireplace
FP2421
9"
(229 mm)
12"
(305 mm)
6"
(152 mm)
12" (305 mm)
6" (152 mm)
2
¹⁄₂
"
(64 mm)
FP2745
mantel clearances
Wall
Stud
Insulation
Board
Standoff
Top of Fireplace
Opening
FP2745
Side View