background image

20306746

11

WDV See-thru Gas Fireplace

VENT INSTALLATION 

INSTALLATION PLANNING 

There are two basic types of direct-vent installation:

•  

Horizontal Termination

•  

Vertical Termination

It is important to select the proper length of vent pipe for 

the type of termination you choose. It is also important to 

note the wall thickness. 

HORIZONTAL TERMINATION

Select  the  amount  of  vertical  rise  desired. All  horizontal 

run of venting must have 

1

4

" (6 mm) rise for every 12" (305 

mm) of run towards the termination below 7

1

2

 feet (2.3 m) of 

vertical rise from the floor of the fireplace. With 7

1

2

 feet (2.3 

m) or more vertical rise from the floor of the fireplace, the 

horizontal run may run level. NEVER run vent piping down. 
Horizontal venting which incorporates the twist lock pipe 

must be installed on a level plane without an inclining or 

declining slope.

You may use up to three 90° elbows in this vent configura

-

tion. Refer to Vertical/Horizontal Termination Configurations 

on 

Page 15

.

FOR VERTICAL TERMINATION

Measure the distance from the fireplace floor to the ceil

-

ing. Add the ceiling thickness, the vertical rise in an attic 

or second story, and allow for sufficient vent height above 

the roof line. 

NOTICE

When  installing  in  a  chase,  you  should 

insulate the chase as you would the outside 

walls of your home. This is especially 

important  in  cold  climates.  Insulation 

should  be  considered  a  combustible 

material. Maintain proper clearances to all 

combustible materials. 

Treatment of firestops and construction of 

the chase may vary from building type to 

building  type.  These  instructions  are  not 

substitutes  for  the  requirements  of  local 

building  codes. You  must  follow  all  local 

building codes. 

NOTICE

Never run the vent pipe level down. This 

may cause excessive temperatures which 

could cause a fire. 

W

ARNING

Always  maintain  minimum  clearances  around 

vent systems. The minimum clearances to 

combustibles  for  horizontal  and  vertical  vent 

pipe are 1" (25 mm) at the top, sides and bottom 

of  the  vent  system.  Do  not  pack  the  open  air 

spaces with insulation or other materials. This 

could cause high temperatures and may present 

a fire hazard.

 

W

ARNING

NOTE:

 You may use two 45° elbows in place of a 90° elbow. 

You must follow rise to run ratios when using 45° elbows. 

The appliance is approved for use with three 90° elbows 

maximum or a combination of  90° and 45° elbows up to 

a maximum of 270°.

 

For two-story applications, firestops are required at each 

floor level. If an offset is needed in the attic, additional pipe 

and elbows will be required.
You may use a chase with a vent termination with exposed 

pipe on the exterior of the house.
Refer to 

Installing A Vent System in an Outside Chase

 

below. If pipe is enclosed in chase, it is not exposed. 
It is very important that the venting system maintain its bal-

ance between the combustion air intake and the flue gas 

exhaust. Certain limitations apply to vent configurations 

and must be strictly followed.

INSTALLING A VENT SYSTEM IN AN 

OUTSIDE CHASE

A chase is a vertical boxlike structure built to enclose 

venting that runs along the outside of a building. A chase 

is required for such venting. 

Содержание WDVST500NTSCSB

Страница 1: ...maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier Thisappliancemaybeinstall...

Страница 2: ...13 Vertical Sidewall Installation 14 Vertical Horizontal Termination Configurations 15 Below Grade Installation 16 Vertical Through the Roof Applications Installation 17 Installation for Vertical Ter...

Страница 3: ...properly seated and sealed If this unit is not properly installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early...

Страница 4: ...tested by CSA and found to comply with the established standards for VENTED GAS FIREPLACES in the USA and Canada as follows LISTED VENTED GAS FIREPLACES WDVST500 TESTED TO ANSI Z21 50 2014 CSA 2 22 2...

Страница 5: ...ny damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have been received You should have the following Fireplac...

Страница 6: ...to do so will cause fire and damage to property 1 2 or 5 8 25 654 mm Min Rough Opening Width 51 1314 mm 40 1016 mm 361 8 918 mm 177 8 454 mm 299 16 751 mm 375 8 956 mm 711 16 195 mm 1 38 mm 13 349 mm...

Страница 7: ...this manual for allowable venting configurations These units can be installed in a bedroom Refer to the National Fuel Gas Code ANSI Z233 1 NFPA 54 cur rent edition the Uniform Mechanical Code current...

Страница 8: ...a fire hazard The appliance cannot be installed on a carpet tile or other combustible material other than wood flooring If installed on carpet or vinyl flooring the appliance shall be installed on a m...

Страница 9: ...als i e brick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black painted face of the appliance It is permissible to bring combustible wall board to the to...

Страница 10: ...m 1 25 mm 1 25 mm Figure 7 Combustible Clearances for Vent Pipe 12 305 mm Vertical Rise Required Before Horizontal Run FP2748 VENT INSTALLATION Read all instructions completely and thoroughly before a...

Страница 11: ...Treatment of firestops and construction of the chase may vary from building type to building type These instructions are not substitutes for the requirements of local building codes You must follow al...

Страница 12: ...r appliances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clearance to permanently...

Страница 13: ...place Vertical Dimension From the Floor of Unit to the Center of the Horizontal Vent Pipe Dimensions in Feet 50 1270 mm From Floor to Center Outside Corner Inside Corner Termination Clearances Termina...

Страница 14: ...re the vertical height X required from the base of the flue collars to the center of the wall opening Figure 12 Step 4 Using appropriate length of pipe section s attach to fire place with three 3 scre...

Страница 15: ...ree 3 Figure 14 A minimum of 12 305 mm is required before a 90 elbow If a 90 elbow is fitted directly after 12 305 mm vertical section mounted to the top of the fireplace the maximum horizontal vent r...

Страница 16: ...ee the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 12 1 Establish vent hole through the wall 2 Remove soil to a depth of approximately 16 below base of snorkel Install d...

Страница 17: ...Screws Wall Screws Snorkel WARNING Do not back fill around snorkel A clearance of at least 4 must be maintained between the snorkel and the soil Up to two 45 elbows may be used within the horizontal r...

Страница 18: ...of the flue exit Mark the center point where the vent will penetrate the ceiling Drill a small locating hole a this point Drop a plumb line from the inside of the roof to the ceiling locating hole in...

Страница 19: ...ials 6 Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements NOTE You must increase vent height for steep roof pitches Nearby trees adjoining roof...

Страница 20: ...extend the inner flexible vent 4 Slide the inner vent onto the adapter collar for a minimum 13 4 overlap 5 Locate the clamp at approximately 3 4 from the flex end and tighten 6 Secure the clamped inn...

Страница 21: ...o be installed at inter vals prescribed by the flexible vent manufacturer and in such a way as to maintain concentric inner and outer vent spacing D Attaching flexible venting to vertical termination...

Страница 22: ...fittings approved for gas connections The gas control inlet is 3 8 NPT The gas control is equipped with a captured screw type pressure test point therefore it is not necessary to provide a 1 8 test po...

Страница 23: ...xcess sealant from going into pipe Excess seal ant in pipe could result in clogged burner system valves We recommend that you install a sediment trap drip leg in supply line as shown in Figure 32 Loca...

Страница 24: ...e extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from junction box to lower control area at bottom of fireplace Unplug the 12 cable from the com mand center...

Страница 25: ...HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Connector Control Board to Solenoid Gas In Gas Out Pilot Gas Tubing...

Страница 26: ...connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the main electrical power supply or performing service BLOTB...

Страница 27: ...3 Tilt glass away from unit Lift glass frame up and away from unit FP2432 open cam levers Cam Levers FP2433 lift glass FP2431 remove glass 1 Front Access Door Spring Hinge Pin Figure 37 Remove Glass...

Страница 28: ...Figure 58 4 Replace glass frame and access door in reverse order of removal Figure 39 Stone Placement FP2434 stone placement Firebox Perimeter Burner Surface Rear Vent Example of Stone Placement FP24...

Страница 29: ...NSTALLATION INSTRUCTIONS 1 Remove screen from packaging 2 Align the four tabs on the sides of the screen frame two top two bottom Figure 40 with the correspond ing slots on the firebox Figure 41 3 Sli...

Страница 30: ...phone Follow the gas supplier s instruc tions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not...

Страница 31: ...gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will...

Страница 32: ...out X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blower Modulation X Three Brightness Settings for Lights X Three...

Страница 33: ...ds when the master switch Shutoff on the main burner is off RF Remote Receiver Push the RF receiver On Off button on the control board RF OFF On Off Beep once for ON and beep twice for OFF Learn Remot...

Страница 34: ...al reset Self Diagnostics Chart The Command Center has a self diagnostic LED en abling you to troubleshoot problems and potentially avoid a service call Please refer to the charts below for indicator...

Страница 35: ...r an extended period of time Never leave anything on top of the surface of the transmitter FP2646 TSFSC display Information Bar Touch Area Logo Bar Menus Adjustment Controls Function Areas of the LCD...

Страница 36: ...econds 4 During the 10 sec onds press the OFF button on the transmitter to learn Another two beeps will be given to confirm a suc cessful learning Figure 47 TOUCH SCREEN REMOTE CONTROL OPERATION WARNI...

Страница 37: ...unts down to zero 6 To exit Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to zero Or c Slide down on the arrow buttons to exit TIMER...

Страница 38: ...wer speed will take effect right away if the fireplace is off the receiver will remember this setting and the blower is still off see blower On Delay and Off Delay in the next section 4 After the sign...

Страница 39: ...but tons become flame height controller again 5 When the light button is flashing slide up and down on the arrow buttons will turn the light brightness to HIGH or Off directly without pressing the lig...

Страница 40: ...splay is blank Check battery installation or replace batteries LCD display shows funny display Reset the transmitter see Resetting the Transmitter section Appliance does not come on The transmitter di...

Страница 41: ...ing to the main burner BURNER Inspect area around the injector Remove any lint or foreign material with a brush or vacuum BURNER FLAME The flames from the burner should be visually checked as soon as...

Страница 42: ...cement glass door assemblies MUST be supplied by the fireplace manufacturer No substitute materi als may be used Handle glass door with care to avoid striking or scratch ing it on hard objects To clea...

Страница 43: ...h Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check v...

Страница 44: ...0 2 Bulb Socket 12 73D4521K 3 Safety Screen Barrier 1 20306602K 4 Glass Frame Assembly 2 78D0027K 5 Panel Access Door 2 78D0040K Junction Box Assembly not shown 1 26D2128 Accessories Field Installed O...

Страница 45: ...20306746 45 WDV See thru Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 780012 DVW SG parts 6 09 1 2 3 4 15 5 6 7 8a 9 14 8b...

Страница 46: ...e w Shutoff Valve 1 69D0030 69D0030 7 Injector 2 59D0062 69D0226 8a Burner Assembly 1 78D2100 78D2100 8b Burner Assembly 1 78D2101 78D2101 9 Venturi 2 69D1026 69D1026 10 Air Shutter not shown 2 69D102...

Страница 47: ...s Fireplace STONES REPLACEMENT PARTS ITEM DESCRIPTION QTY PART NO 1 White Stone 1 5 78D0122 2 Light Gray Stone 2 5 78D0123 3 Dark Gray Stone 3 5 78D0124 4 Brown Stone 4 5 78D0125 5 Sand Stone 5 5 78D0...

Страница 48: ...48 20306746 WDV See thru Gas Fireplace HOT 1 2 3 4 5 6 9 7 8 10 730024 KHLDV vent parts VENT COMPONENTS REPLACEMENT PARTS...

Страница 49: ...ipe 20 to 48 Adapter BHSF58TK 1 8 Horizontal Termination w 1 Firestop BHR58T 8 1 1 Horizontal High Wind Termination Cap 58DVA HC 1285 5DT HC 1 1 Horizontal Termination Cap 5DHT 2 1 Vertical Terminatio...

Страница 50: ...o comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed MASSACHUSETTS RESIDENTS ONLY 2...

Страница 51: ...Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage...

Страница 52: ...Based on CSA P 4 1 09 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup com EFFICIENCY RATINGS MODEL ENERGUIDE RATINGS FIREPLACE EFFICIENCY PERCENTAGE WDV500NTSC 61 0 WDV500PTSC 59 7...

Отзывы: