CLEANING AND MAINTENANCE 

BURNER, PILOT AND CONTROL  

COMPARTMENT

Keep the control compartment, stones and burner areas 

surrounding the stones clean by vacuuming or brushing 

at least twice a year.  Make sure the burner porting, pilot 

air opening and burner air opening are free of obstructions 

at all times.

PILOT FLAME

The flames from the pilot should be visually checked as 

soon as the heater is installed and periodically during 

normal operation. 

The  pilot  flame  must  always  be 

present when the fireplace is in operation. 

Figure 57

The pilot flame has three distinct flames, one engulfing 

the sensor, one engulfing the thermopile, and the other 

reaching to the main burner.

 

             

BURNER

Inspect area around the injector. Remove any lint or foreign 

material with a brush or vacuum. 

BURNER FLAME

The flames from the burner should be visually checked 

as soon as the heater is installed and periodically during 

normal operation. In normal operation, at full rate, and after 

operating for about 15 to 30 minutes, the flame should be 

yellow.

 Figure 58

If the flame is blue and candle-like in appearance, adjust 

glass or add more glass over ports. 

NOTE:

 

The type of installation, vent system configuration, 

and wind effects may cause the flame patterns to vary.

W

ARNING

Turn  off  gas  before  servicing  fireplace.  It  is 

recommended that a qualified service technician 

perform  these  check-ups  at  the  beginning  of 

each heating season

FP2568
pilot flame

Figure 57 - 

Pilot Flame 

Thermopile 

Sensor

FP2568

FP2436
WDV flame appearance

Figure 58 - 

Burner Flame Appearance

Содержание WDVST500NTSCSB

Страница 1: ...maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier Thisappliancemaybeinstall...

Страница 2: ...13 Vertical Sidewall Installation 14 Vertical Horizontal Termination Configurations 15 Below Grade Installation 16 Vertical Through the Roof Applications Installation 17 Installation for Vertical Ter...

Страница 3: ...properly seated and sealed If this unit is not properly installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early...

Страница 4: ...tested by CSA and found to comply with the established standards for VENTED GAS FIREPLACES in the USA and Canada as follows LISTED VENTED GAS FIREPLACES WDVST500 TESTED TO ANSI Z21 50 2014 CSA 2 22 2...

Страница 5: ...ny damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have been received You should have the following Fireplac...

Страница 6: ...to do so will cause fire and damage to property 1 2 or 5 8 25 654 mm Min Rough Opening Width 51 1314 mm 40 1016 mm 361 8 918 mm 177 8 454 mm 299 16 751 mm 375 8 956 mm 711 16 195 mm 1 38 mm 13 349 mm...

Страница 7: ...this manual for allowable venting configurations These units can be installed in a bedroom Refer to the National Fuel Gas Code ANSI Z233 1 NFPA 54 cur rent edition the Uniform Mechanical Code current...

Страница 8: ...a fire hazard The appliance cannot be installed on a carpet tile or other combustible material other than wood flooring If installed on carpet or vinyl flooring the appliance shall be installed on a m...

Страница 9: ...als i e brick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black painted face of the appliance It is permissible to bring combustible wall board to the to...

Страница 10: ...m 1 25 mm 1 25 mm Figure 7 Combustible Clearances for Vent Pipe 12 305 mm Vertical Rise Required Before Horizontal Run FP2748 VENT INSTALLATION Read all instructions completely and thoroughly before a...

Страница 11: ...Treatment of firestops and construction of the chase may vary from building type to building type These instructions are not substitutes for the requirements of local building codes You must follow al...

Страница 12: ...r appliances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clearance to permanently...

Страница 13: ...place Vertical Dimension From the Floor of Unit to the Center of the Horizontal Vent Pipe Dimensions in Feet 50 1270 mm From Floor to Center Outside Corner Inside Corner Termination Clearances Termina...

Страница 14: ...re the vertical height X required from the base of the flue collars to the center of the wall opening Figure 12 Step 4 Using appropriate length of pipe section s attach to fire place with three 3 scre...

Страница 15: ...ree 3 Figure 14 A minimum of 12 305 mm is required before a 90 elbow If a 90 elbow is fitted directly after 12 305 mm vertical section mounted to the top of the fireplace the maximum horizontal vent r...

Страница 16: ...ee the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 12 1 Establish vent hole through the wall 2 Remove soil to a depth of approximately 16 below base of snorkel Install d...

Страница 17: ...Screws Wall Screws Snorkel WARNING Do not back fill around snorkel A clearance of at least 4 must be maintained between the snorkel and the soil Up to two 45 elbows may be used within the horizontal r...

Страница 18: ...of the flue exit Mark the center point where the vent will penetrate the ceiling Drill a small locating hole a this point Drop a plumb line from the inside of the roof to the ceiling locating hole in...

Страница 19: ...ials 6 Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements NOTE You must increase vent height for steep roof pitches Nearby trees adjoining roof...

Страница 20: ...extend the inner flexible vent 4 Slide the inner vent onto the adapter collar for a minimum 13 4 overlap 5 Locate the clamp at approximately 3 4 from the flex end and tighten 6 Secure the clamped inn...

Страница 21: ...o be installed at inter vals prescribed by the flexible vent manufacturer and in such a way as to maintain concentric inner and outer vent spacing D Attaching flexible venting to vertical termination...

Страница 22: ...fittings approved for gas connections The gas control inlet is 3 8 NPT The gas control is equipped with a captured screw type pressure test point therefore it is not necessary to provide a 1 8 test po...

Страница 23: ...xcess sealant from going into pipe Excess seal ant in pipe could result in clogged burner system valves We recommend that you install a sediment trap drip leg in supply line as shown in Figure 32 Loca...

Страница 24: ...e extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from junction box to lower control area at bottom of fireplace Unplug the 12 cable from the com mand center...

Страница 25: ...HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Connector Control Board to Solenoid Gas In Gas Out Pilot Gas Tubing...

Страница 26: ...connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the main electrical power supply or performing service BLOTB...

Страница 27: ...3 Tilt glass away from unit Lift glass frame up and away from unit FP2432 open cam levers Cam Levers FP2433 lift glass FP2431 remove glass 1 Front Access Door Spring Hinge Pin Figure 37 Remove Glass...

Страница 28: ...Figure 58 4 Replace glass frame and access door in reverse order of removal Figure 39 Stone Placement FP2434 stone placement Firebox Perimeter Burner Surface Rear Vent Example of Stone Placement FP24...

Страница 29: ...NSTALLATION INSTRUCTIONS 1 Remove screen from packaging 2 Align the four tabs on the sides of the screen frame two top two bottom Figure 40 with the correspond ing slots on the firebox Figure 41 3 Sli...

Страница 30: ...phone Follow the gas supplier s instruc tions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not...

Страница 31: ...gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will...

Страница 32: ...out X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blower Modulation X Three Brightness Settings for Lights X Three...

Страница 33: ...ds when the master switch Shutoff on the main burner is off RF Remote Receiver Push the RF receiver On Off button on the control board RF OFF On Off Beep once for ON and beep twice for OFF Learn Remot...

Страница 34: ...al reset Self Diagnostics Chart The Command Center has a self diagnostic LED en abling you to troubleshoot problems and potentially avoid a service call Please refer to the charts below for indicator...

Страница 35: ...r an extended period of time Never leave anything on top of the surface of the transmitter FP2646 TSFSC display Information Bar Touch Area Logo Bar Menus Adjustment Controls Function Areas of the LCD...

Страница 36: ...econds 4 During the 10 sec onds press the OFF button on the transmitter to learn Another two beeps will be given to confirm a suc cessful learning Figure 47 TOUCH SCREEN REMOTE CONTROL OPERATION WARNI...

Страница 37: ...unts down to zero 6 To exit Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to zero Or c Slide down on the arrow buttons to exit TIMER...

Страница 38: ...wer speed will take effect right away if the fireplace is off the receiver will remember this setting and the blower is still off see blower On Delay and Off Delay in the next section 4 After the sign...

Страница 39: ...but tons become flame height controller again 5 When the light button is flashing slide up and down on the arrow buttons will turn the light brightness to HIGH or Off directly without pressing the lig...

Страница 40: ...splay is blank Check battery installation or replace batteries LCD display shows funny display Reset the transmitter see Resetting the Transmitter section Appliance does not come on The transmitter di...

Страница 41: ...ing to the main burner BURNER Inspect area around the injector Remove any lint or foreign material with a brush or vacuum BURNER FLAME The flames from the burner should be visually checked as soon as...

Страница 42: ...cement glass door assemblies MUST be supplied by the fireplace manufacturer No substitute materi als may be used Handle glass door with care to avoid striking or scratch ing it on hard objects To clea...

Страница 43: ...h Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check v...

Страница 44: ...0 2 Bulb Socket 12 73D4521K 3 Safety Screen Barrier 1 20306602K 4 Glass Frame Assembly 2 78D0027K 5 Panel Access Door 2 78D0040K Junction Box Assembly not shown 1 26D2128 Accessories Field Installed O...

Страница 45: ...20306746 45 WDV See thru Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 780012 DVW SG parts 6 09 1 2 3 4 15 5 6 7 8a 9 14 8b...

Страница 46: ...e w Shutoff Valve 1 69D0030 69D0030 7 Injector 2 59D0062 69D0226 8a Burner Assembly 1 78D2100 78D2100 8b Burner Assembly 1 78D2101 78D2101 9 Venturi 2 69D1026 69D1026 10 Air Shutter not shown 2 69D102...

Страница 47: ...s Fireplace STONES REPLACEMENT PARTS ITEM DESCRIPTION QTY PART NO 1 White Stone 1 5 78D0122 2 Light Gray Stone 2 5 78D0123 3 Dark Gray Stone 3 5 78D0124 4 Brown Stone 4 5 78D0125 5 Sand Stone 5 5 78D0...

Страница 48: ...48 20306746 WDV See thru Gas Fireplace HOT 1 2 3 4 5 6 9 7 8 10 730024 KHLDV vent parts VENT COMPONENTS REPLACEMENT PARTS...

Страница 49: ...ipe 20 to 48 Adapter BHSF58TK 1 8 Horizontal Termination w 1 Firestop BHR58T 8 1 1 Horizontal High Wind Termination Cap 58DVA HC 1285 5DT HC 1 1 Horizontal Termination Cap 5DHT 2 1 Vertical Terminatio...

Страница 50: ...o comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed MASSACHUSETTS RESIDENTS ONLY 2...

Страница 51: ...Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage...

Страница 52: ...Based on CSA P 4 1 09 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup com EFFICIENCY RATINGS MODEL ENERGUIDE RATINGS FIREPLACE EFFICIENCY PERCENTAGE WDV500NTSC 61 0 WDV500PTSC 59 7...

Отзывы: