VLI31 Fireplace Insert
cLeARANceS
INSeRt cLeARANceS
No combustibles (ie: drapes, doors) may be within, or swing within 36" of the front of the insert.
MANteL cLeARANceS
NOte: the combustible area above the facing must not protrude more than 3/4" from the
facing. If it does, it is considered a mantel and must meet the mantel requirements listed
in this manual.
heARth RequIReMeNtS
The insert must be installed on a noncombustible hearth extending a minimum of 1" from the
fireplace opening (local codes may require a larger hearth). The hearth must also extend to both
sides of the face (Refer to the table on Page 7).
12” (305 mm)
Maximum Depth
Side Wall
Combustible Mantel
Top Facing
Side Facing
3/4” (19 mm)
Maximum Depth
Combustible Facing
42” (1067 mm)
Minimum
10” (254 mm)
Minimum
12” (305 mm)
Minimum
FP1947
insert clearances
9/08
12”
(305 mm)
9”
(228 mm)
FP678
Figure 3 -
Mantel Clearances
NOte:
Side clearance to com-
bustibles is 10" (54 mm) from
opening whether it is side wall
or mantel legs.
cLeARANceS
MINIMuM FIRePLAce SIZe/cLeARANceS tO cOMBuStIBLeS
W
ARNING
The dimensions shown on
Pages 8 and 9, Figures 3 and 4
, are mini-
mum clearances to maintain when installing this heater. Follow these
instructions carefully to ensure safe installation. Failure to follow
instructions exactly can create a fire hazard.