83D4009
VLI31 Fireplace Insert
11
VeNtING INStALLAtION
VeNtING RequIReMeNtS
•
The exhaust vent must reline the entire length of chimney and terminate above chimney top.
•
Vent must meet all vent manufacturer's requirements when installed.
•
Make sure you have the following before installing unit:
•
3" and 3" UL 1777 Listed gas liner for air inlet and exhaust.
•
Vertical Terminations kits: HEDV3T11, HEDVRT, AI31TK33A
Figure 6 -
Venting Unit
FP1922
vent requirements
9/08
Maximum Height 40'
(1.9 m)
Minimum Height 10'
(3 m)
Exhaust
Inlet
FP19
•
Make sure the exhaust pipe on heater connects to exhaust
portion of cap. Attach flex liners.
Figure 6
•
Do not crimp or rupture liner when bending it into chimney
offsets.
W
ARNING