RFSDV22/32/42 Freestanding Direct Vent Fireplace
Firestop
7" Pipe
24"
(608mm)
Minimum
Snorkel
4" Clearance
Window Well
Ground
Gravel
Drain
Foundation Wall
* A minimum of 24" (608mm)
vertical pipe must be installed
when using the snorkel kit.
* The 22" vertical rise (center to
center) of the snorkel may be
included for calculation of max.
horizontal run.
FP1341
Fig. 21 Below grade installation.
Screws
Snorkel
Wall Screws
Foundation
Recess
Watertight Seal
Around Pipe
Sheet Metal
Screws
BG401
Fig. 22 Snorkel installation, recessed foundation.
Vertical Through-the-Roof Applications
This Gas Fireplace has been approved for,
•
Vertical installations up to 40 feet (12m) in height.
Up to a 10 ft. horizontal vent run can be installed
within the vent system using a maximum of two 90
o
elbows. (Fig. 23)
•
Up to two 45
o
elbows may be used within the hori-
zontal run. For each 45
o
elbow used on the horizon-
tal level the maximum horizontal length must be
reduced by 18".
Do Not Back Fill Around Snorkel. Soil
Should Not Be Less Than 4" Below
Snorkel.
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel.
Fasten brackets to wall first and then secure to snorkel
with self drilling #8 x 1/2 sheet metal screws. It will be
necessary to extend the vent pipes out as far as the
protruding wall face. (Fig. 22)
Example: Maximum horizontal length
0
-
45
o
elbows 10 ft. (3m)
1
-
45
o
elbows 8.5 ft. (2.6m)
2
-
45
o
elbows 7 ft. (2m)
Maximum
10' (305cm)
Minimum 8'
(2.4m)
Maximum
40' (12.2m)
FP1342
Support Straps
Every 3' (914mm)
Fig. 23 Vertical through the roof requirements.
•
A minimum of an 8 ft. vertical rise.
•
Two sets of 45 degree elbow offsets within these
vertical installations. From 0 to a maximum of 8 ft. of
vent pipe can be used between elbows. (Fig. 24)
•
7DVCS must be used to support offsets. (Fig. 25)
This application will require that you first determine
the roof pitch and use the appropriate starter kit.
(See Venting Components List)
•
The minimum height of the vent above the
highest point of penetration through the roof is 2
feet. (Fig. 26)
40' (12m)
Max. 8'
(2.44m)
Max. 8'
(2.44m)
45
°
45
°
FP1343
Fig. 24 Typical offset installation.