Montpelier Medium Insert

30004403

Installing the Montpelier Medium Insert into an existing 
masonry fireplace is an effective way to add an efficient 
heater to your home. The existing fireplace and chim-
ney must meet certain requirements.

Requirements for Existing Fireplaces

The Montpelier Medium Insert is listed for installation 
within a properly built masonry or heat circulating, ma-
sonry-type fireplace that is constructed in accordance 
with the requirements of recognized building codes. A 
heat-circulating masonry-type fireplace must conform 
to building code standards for masonry fireplaces, and 
must consist of a factory-built metal firebox with air 
circulation pathways that are surrounded by masonry 
materials. Air circulation pathways must not be blocked 
by the insert or surround panels.
The fireplace and chimney must be clean and structur-
ally sound. Have them inspected by a qualified profes-
sional chimney sweep, a mason, or your Vermont Cast-
ings’ Authorized Dealer before the Montpelier Medium 
Insert is installed. Any deterioration (cracks, loose 
mortar or loose bricks) must be repaired.
Codes may permit removal of the damper in order to 
make a positive vent connection between the firebox 
and the chimney. However, the fireplace should not be 
modified in any way without first checking with your lo-
cal building inspector or fire marshal. Provision should 
be made to restore the fireplace to its original condition 
if the insert is removed. Do not remove bricks or mortar 
that may jeopardize the compliance of the fireplace with 
local building codes.

The Montpelier Medium Insert is not listed for in-
stallation in factory-built fireplaces.

  

Installation

Requirements for Existing Chimneys

Chimney requirements differ for the U.S. and Canada.  
Specifications for each are listed below. Connect the 
insert to the chimney in accordance with local codes 
and the requirements of the listing agency as specified 
in this manual.

Chimney Height / U.S. and Canada

Chimney height should be no less than 15’ (4.5 m) 
above the hearth and no more than 35’ (10.5 m).
The chimney should extend at least 3’ (914 mm) above 
the highest point where it passes through a roof, and at 
least 2’ (610 mm) higher than any portion of a building 
within 10’ (3 m). (Fig. 2)

Do not connect your Montpelier Medium insert  to a 
chimney flue serving another appliance.

U.S. 

In the U.S. (ANSI/NFPA 211, 1988), when  

 

installed in a masonry fireplace:

• 

A connector must extend from the flue collar  
to the flue liner.

  If a stainless steel liner is not used, the connec-

tor must extend at least four (4) feet from the flue 
collar of the insert.*

• 

The cross sectional area of the flue must be less  
than or equal to three times the area of the flue  
collar. If larger, the chimney must be re-lined.

• 

Means must be provided to prevent room air  
passing to the chimney cavity.

• 

Provision must be made for removal of the  
insert to clean the chimney flue.

General Considerations / U.S.

• 

While not required in most jurisdictions in the 
U.S., MHSC strongly recommends that a full 
stainless steel chimney liner be installed for the 
insert to the chimney top to increase overall per-
formance and to ease and reduce yearly mainte-
nance.

• 

A masonry chimney must be well-constructed 
and must meet minimum code requirements.  
The chimney flue should have a code-approved 
liner made of masonry or pre-cast refractory 
tiles, straight or flexible stainless steel pipe, or a 
poured-in-place liner. An unlined chimney must 
be relined professionally.

• 

The chimney must have a nominal flue size of 
6” (152 mm) diameter or 28 square inches (181 
cm

2

) but no greater than 3 times larger or 85 

square inches (548 cm

2

).  A chimney larger than 

this must be re-lined. 

2' Min.

2' Min.

3'

Min.

0 To 10'

3'

Min.

0 To 10'

AC617

RLTSKC8

2/11/98

AC617

Reference 

Point

Fig. 2

  The 2’-3’-10’ rule for chimneys.

* This requirement is in addition to those specified in ANSI/NFPA211.

Содержание Montpelier

Страница 1: ...LY INSTALLED OPERATED AND MAIN TAINED A HOUSE FIRE MAY RESULT TO REDUCE THE RISK OF FIRE FOLLOW THE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH CONTACT LOCAL BUILDING OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Homeowner s Installation and Operating Manual ...

Страница 2: ... a traditional masonry fireplace into a powerful heater You can count on years of comfortable heating and pleasurable fire viewing if you operate and maintain it according to the directions in this Owner s Guide This Insert has been tested and listed by OMNI Test Laboratories of Portland Oregon to ANSI UL 1482 for the United States and ULC S628 for Canada This Insert is listed to and in compliance w...

Страница 3: ...t is operated and the type and moisture content of the fuel used The figure shown is based on maximum fuel con sumption obtained under laboratory conditions and with average efficiencies These values are based on operation in building code conforming homes under typical winter climate conditions in New England If your home is of nonstan dard construction e g unusually well insulated not in sulated b...

Страница 4: ...he chimney in accordance with local codes and the requirements of the listing agency as specified in this manual Chimney Height U S and Canada Chimney height should be no less than 15 4 5 m above the hearth and no more than 35 10 5 m The chimney should extend at least 3 914 mm above the highest point where it passes through a roof and at least 2 610 mm higher than any portion of a building within 1...

Страница 5: ...o accommo date the liner The opening of the fireplace around the insert must be sealed to prevent room air passing to the fireplace cavity Existing air circulation chambers in a fireplace with a steel liner may not be blocked Provision must be made for removal of the insert to clean the chimney flue The existing fireplace damper if any should be locked in the open position A permanent metal warning lab...

Страница 6: ... fire place opening on the hearth X Measure the top trim B and or mantel clearances A from the finished hearth surface Measure the front clearance to furnishings etc from the fireplace face Fig 4 Observe these clearances to combustible trim Hearth Requirements In some fireplaces the hearth in front of the fireplace opening is brick stone slate or some other non com bustible material that is in direct c...

Страница 7: ...o thermal protection is necessary 2 Determine the R value of the proposed alternate floor protector i Use the formula in Step 1 to convert values not expressed as R ii For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the system is greater than the R value of the specified floor protector the alter nate is acceptable EXAMPLE The specified floor prot...

Страница 8: ...depending on your application it may be easiest to install the con nector or stainless steel flue liner in the chimney first Refer to Figure 6 for the components of the venting system Carefully remove the fiber baffle by first remov ing the front air tube If necessary removing the remaining air tubes will allow easier access Remove the iron flue collar from the stove and fasten either the adapter pipe o...

Страница 9: ... will produce and how long it will burn The primary air control lever is located on the upper left side on the front of the insert The lever regulates air for starting maintaining and reviving the fire Generally more air entering the stove makes the fire burn hotter and faster while less air prolongs the burn The Montpelier Medium Insert s air supply is increased when the control lever is moved to t...

Страница 10: ...he length type and location of the chimney weather local geography nearby obstructions and other factors Too much draft may cause excessive temperatures in the Montpelier Medium Insert and could even damage internal components On the other hand too little draft can cause backpuffing into the room or a very sluggish fire How do you know if your draft is excessively high or low Symptoms of too much dr...

Страница 11: ...y adjust the air control and fan speed for your desired heat level Starting and Maintaining a Wood Fire Burn solid wood fuel only in the Montpelier Medium Insert and burn it directly on the grate Do not elevate the fuel Do not burn coal or other fuels Cast iron is a superior material for solid fuel stoves but it must be treated with respect It is extremely strong but can be broken with a sharp blo...

Страница 12: ...partially rotted or inadequately seasoned To compensate for these factors in cold climates it may be necessary to operate the Montpelier Medium Insert for longer periods of time with the air control set to a higher level more of the time Remove and Store Ash Safely Check the ash level before reloading the stove remove ashes if necessary Turn off the fan before shoveling the ash into your ash conta...

Страница 13: ...n the glass use the following procedure Be sure the glass is completely cool Cleaning with water will work in most cases Use a glass cleaner especially made for this purpose only if deposits are specially heavy If heavy deposits are a frequent occurrence however evaluate your operating techniques Do not use abrasive cleaners Rinse the glass thoroughly Dry the glass completely Adjust the Door Latch...

Страница 14: ...6 3 8 30002422 Firebox parts 3 16 1203556 Glass to the door 5 2 To change a gasket wait until the fire is out and the stove has cooled Wear protective eyewear and a dust mask The procedure is the same for all gaskets 1 Remove the existing fiberglass gasket by grasping an end and pulling firmly 2 Use a wire brush or the tip of a screwdriver to clean the channel of any remaining cement silicone or bits...

Страница 15: ... heating season as part of a regular maintenance schedule To inspect the chimney let the Montpelier Medium Insert cool completely Then using a strong light sight up through the flue collar into the chimney flue The fiber baffle will need to be removed gently to view inside the connector pipe If it is necessary to remove the firechamber to inspect or clean the chimney this is how to do it Let the Montpe...

Страница 16: ...or parts and information about your insert contact your Vermont Castings authorized dealer For the name of the dealer nearest you contact MHSC 149 Cleveland Drive Paris KY 40361 800 668 5323 Optional Accessories Georgian Cast Surround Model Color 30DVSGTKCB Classic Black 30DVSGTKB Ebony Mead Cast Surround Model Color MEAD3CB Classic Black MEAD3EB Ebony MEAD3BS Biscuit Caprice Cast Adjustable Profil...

Страница 17: ...m Slanted 30004328 5 Brick Back 30004326 6 Brick Bottom Up 30004329 7 Brick Right End 30004330 8 Brick Left End 30004331 9 Insulation End Int 30004334 10 End Right 30004308 11 End Left 30004309 12 Back 30004307 13 Andiron 30004321 14 Tube A Secondary Air Tube 30004377 1 3 4 5 6 7 8 9 9 10 11 12 13 15 14 16 17 18 19 20 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35 37 39 40 41 41 42 43 44 45 46...

Страница 18: ... Insulation Bottom Heat Shield 30004402 30 Bottom Heat Shield 30004393 31 Base 30004313 32 Fan Kit Assembly 30004416 33 Ashlip Refer to Enamel Parts Chart 34 Bottom Assembly 30004385 35 Cover Power Cord 30004379 36 Shroud Outer 30004392 37 Shroud Top 30004383 38 Flue Collar 30004317 39 Flange Right Side Surround 30004381 40 Flange Left Side Surround 30004380 41 Clip Glass 30001715 42 Glass Ceramic...

Страница 19: ...burning salt saturated wood chemically treated wood or any fuel not recommended in the Owners Guide 4 This warranty does not cover a stove repaired by someone other than a Vermont Castings Authorized Dealer 5 Damage to the unit while in transit is not covered by this warranty but is subject to a claim against the common carrier Contact Vermont Castings Autho rized Dealer from whom you purchased yo...

Страница 20: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com ...

Отзывы: