Vermont Castings  •  Intrepid DV-IFT Owner’s Manual_R20  •  11/21

Step 5

 - Using tin snips, cut the support box from the top 

corners  down  to  the  roofline,  and  fold  the  resulting  flaps 

over  the  roof  sheathing.  The  flaps  may  be  trimmed  as 

needed, Figure 3.40. Before nailing it to the roof, run a bead 

of non-hardening sealant around the support box to make 

a seal between the support box and the roof. Clean out any 

combustible material from inside the support box.

Step 6

 - Follow Steps 4 and 5 of the Vertical Installation 

instructions.

Step 7

 - Place the support clamp (provided with the support 

box)  inside  the  support  box  (at  the  bottom),  and  secure 

to  the  pipe  section. The  clamp  allows  the  support  box  to 

support  the  weight  of  the  pipe  sections.  Continue  to  add 

pipe sections until you are above the roofline.

Consult these 

installation instructions 

for the minimum 

allowable clearances 

between the outside of 

the vent pipe and the 

combustible surfaces 

of  the  enclosure.  Do 

not  fill  required  air 

spaces with insulation.
3.  If  venting  system 

passes  through  an 

attic space an attic 

insulation shield 

must be installed 

to prevent contact 

between pipe 

sections and the 

insulation.  Nail  the 

base to floor of attic 

and  adjust  shield 

for appropriate 

insulation level, 

then attach the 

collar at the top of 

assembly,  Figure 

3.38.  For  vaulted 

ceilings,  the  attic 

insulation shield cannot be installed. To prevent building 

insulation  and  other  debris  from  entering  the  support 

box  or  contacting  the  pipe,  a  chase  enclosure  can  be 

constructed  around  the  support  box.  Ensure  proper 

clearance to combustibles are maintained.

ST990
above roof
8/07

High Wind Vertical 

Termination

Roof Flashing

Storm Collar

Optional Low Profile 

Termination Cap

Secure Flashing with 

Non-hardening Sealant 

and Roofing Nails

Figure 3.37

Figure 3.38

ST991
attic insul shield
8/07

Nails

Attic Insulation Shield

Required Clearance

Minimum Clearance

Minimum Clearance

Minimum Clearance

Figure 3.39

ST992
clg support box
8/07

Level

2” Min. Below 

Finished Ceiling

Cut Hole 1/8” Larger 

than Support Box

Cathedral Ceiling 

Support Box

Cathedral Ceiling Installation
Step 1

 - Follow installation Step 1 and 2 under Vertical 

Termination.

Step 2

  -  Using  the  plumb  bob,  mark  the  centerline  of  the 

venting system on the ceiling and drill a small hole through 

the ceiling and roof at this point. From the roof, locate the drill 

hole and mark the outline of the Cathedral Ceiling Support 

Box.

Step 3

 - Remove shingles or other roof covering as necessary 

to cut the rectangular hole for the support box. Cut the hole 

1/8” (3 mm) larger than the support box outline.

Step 4

 - Lower the support box through the hole in the roof 

until each side of the bottom of the support box protrudes 

at  least  2”  (51  mm)  below  the  ceiling,  Figure  3.39.  Align 

the support box both vertically and horizontally with a level. 

Temporarily tack the support box in place through the inside 

walls and into the roof sheathing.

Содержание Intrepid INDVR-IFT-BD

Страница 1: ...not reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier NOTICE SAVE THESE INSTRUCTIONS Installation...

Страница 2: ...Policy 63 1 Important Safety Information 3 A Massachusetts Safety Information 4 B California Safety Information 4 2 Framing and Clearances 5 A Appliance Dimension Diagram 5 B Installation Requirement...

Страница 3: ...installations in the U S and Canada This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by state or local codes WARNING Operation of this heater when not co...

Страница 4: ...ns The following equipment is exempt from 248 CMR 5 08 2 a 1 through 4 The equipment listed in Chapter 10 entitled Equipment Not Required To Be Vented in the most current edition of NFPA 54 as adopted...

Страница 5: ...imension Diagram Figure 2 1 Intrepid DV dimensions Stove Dimensions 2 2 Framing and Clearances 24 1 4 616mm 13 11 16 347mm 21 3 16 538mm 13 7 8 352mm 21 3 4 553mm 16 7 16 418mm 21 3 8 543mm 18 457mm C...

Страница 6: ...k or may adversely affect the binders in the wallpaper adhesive WARNING Due to high temperatures the heater should be located out of traffic and away from furniture and draperies The surface of the He...

Страница 7: ...610 mm The Intrepid DV Heater can be installed on any type of rigid flooring e g hardwood ceramic tile brick etc When the heater is installed on a carpeted surface a metal or wooden panel extending t...

Страница 8: ...pressure at 3 5 w c for Natural Gas and 10 w c for Propane High Elevations Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4 500 feet 1 370m above sea...

Страница 9: ...ent terminal and clearances Some of the most common clearances to keep in mind are shown in Figure 2 10 Important All vent clearances must be maintained Check your vent termination clearances against...

Страница 10: ...g Any horizontal run must have a 1 4 rise for every one 1 foot of run towards the vent termination Never run the vent level or down There must not be any obstruction such as bushes garden sheds fences...

Страница 11: ...0 000 BTU h 30kW 36 91cm for appliances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW...

Страница 12: ...n 12 305 mm for vinyl sidewalls O 8 2 4 m Min O P V V V Figure 2 11 Termination clearances DMin of Termination caps x 3 CMax 2 termination caps x DActual NOTE Termination in an alcove space spaces ope...

Страница 13: ...5 8 10 1 2 46DVA KCB Steel Chimney Conv Kit C 6 5 8 13 46DVA KCC Masonry Chimney Conversion Kit 46DVA KMC Vertical Termination Cap High Wind 46DVA VCH Vertical Termination Cap Low Profile 46DVA VC All...

Страница 14: ...ance with this instruction manual Read all instructions before starting installation then follow these instructions carefully to maximize stove performance and safety Report damaged parts to your deal...

Страница 15: ...Attach straps to framing members using nails or screws Tighten nut bolt to secure pipe The stove and venting system should be inspected before initial use and at least annually by a qualified field se...

Страница 16: ...losion DO NOT break seals on slip sections Use care when removing termination cap from slip pipe If slip section seals are broken during removal of the termination cap vent may leak Secure the Vent Se...

Страница 17: ...tal Termination Cap Attach slip section of cap to last vent section Maintain 1 1 2 overlap between slip and vent sections Note For installations using black pipe slide the decorative wall thimble over...

Страница 18: ...opening Figure 3 11 Vertical Side Wall Installation NOTE Refer to Figures 2 8 thru 2 10 for restrictor plate adjustments for vertical vent runs 1 Locate vent opening on the wall It may be necessary to...

Страница 19: ...n the pipes and fasten the snorkel termination to the wall with the screws provided 6 Level the soil to maintain a 4 clearance below the snorkel 7 If the foundation is recessed use extension brackets...

Страница 20: ...s 10 3 m 1 x 45 elbow 8 5 2 6 m 2 x 45 elbows 7 2 1 m A minimum of an 8 feet 2 5 m vertical rise is required Figure 3 15 Two sets of 45 elbow offsets may be used within the vertical sections From 0 to...

Страница 21: ...nd fittings may be used for concealed locations such as attics or spaces where corrosion is a factor such as above the roofline Decorative black painted sections are recommended for use on visible int...

Страница 22: ...s Figure 3 22 NOTE The zero clearance sleeve is required in combustible walls only Figure 3 20 Locate vent opening NOTE Zero clearance sleeve is required for combustible wall installations VO584 100a...

Страница 23: ...lockwise an eighth of a turn to lock sections together Figure 3 24 Screws are not required to secure the joint but are acceptable provided they do not penetrate the inner wall of the vent pipe 4 Slip...

Страница 24: ...e horizontal termination cap and the exterior wall Figure 3 29 The vinyl should be cut away to the outer edges of the assembled standoff HOT ST981 SIMP termination 8 07 Wood Screws Figure 3 28 Step 4...

Страница 25: ...l decorative brass trim to wall thimble cover if desired Vertical Installation Step 1 Check these installation instructions for required clearances air spaces to combustibles when passing through ceil...

Страница 26: ...the attic Step 7 Continue to add pipe sections until the height of the system before adding the cap meets the minimum building codes requirements as described in Table 2 Figure 3 36 Note that for stee...

Страница 27: ...hield cannot be installed To prevent building insulation and other debris from entering the support box or contacting the pipe a chase enclosure can be constructed around the support box Ensure proper...

Страница 28: ...emental Canadian Instructions When installing DirectVent Pro on appliances in Canada a 2 piece decorative wall thimble is required in order to comply with IR 39 Figure 3 2 and 3 3 Install galvanized e...

Страница 29: ...mney system Three sizes of termination caps are available which should fit most sizes and makes of metal chimney systems The Retro Connector is then attached to the bottom of the flex pipe Both the ca...

Страница 30: ...does not need to be framed This allows the retro connector to mount directly on the masonry and provide clearance to the combustibles Figure 3 35 3 Secure the flashing 705C to the top of the masonry...

Страница 31: ...ro connector and the 10 254 mm square framed opening as shown in Figure 3 53 If needed add a section of direct vent pipe to the retro connector in order to extend through the opening in the wall thimb...

Страница 32: ...mination Kit 4 ft 1m of 3 in 76mm Flex Liner Air Intake Section Included in Chimney Liner Termination Kit The chimney must be sealed from the 4 ft 1m section to termination using a smoke shelf or a fl...

Страница 33: ...m inlet pressure of 5 5 w c In order to connect Propane use a fitting with 3 8 NPT nipple on the valve side and 1 2 propane gas supply line with a minimum input of 21 000 BTUs at a minimum inlet press...

Страница 34: ...raised notch on back left side of the ember bed Cutout on bottom right side is clearance for pilot assembly Figure 3 60 Gently push right side of log back until it contacts the firebox back slightly...

Страница 35: ...latest edition and Canadian Electrical Code CSA C22 1 CAUTION Label all wires before disconnecting when servicing controls Wiring errors can cause improper and dangerous operation Connect the Gas Supp...

Страница 36: ...2 psig 3 5 kPa The Intrepid DV Heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at...

Страница 37: ...uch control valve which operates on a 6 volt 1 5 AMP system Plug the 6 volt transformer plug into the appliance junction box to supply power to the unit OR install 4 AA cell batteries not included int...

Страница 38: ...doors open or closed 1 Remove screen from packaging 2 Place the two bottom hooks over the bottom edge of the stove opening Figure 3 61 3 Press the screen against the stove snapping the two spring fin...

Страница 39: ...Figure 4 2 If flame patterns are incorrect turn the heater off Contact your dealer or a qualified gas technician for assistance Do not operate the heater until the pilot flame is correct Follow regul...

Страница 40: ...rol knob slightly and turn clockwise to OFF Do not force 5 Close control access panel If knob does not pop up when released stop and immediatelycallyourservicetechnicianorgassupplier If after several...

Страница 41: ...es defective 1 Check wall switch and wires for proper connections Jumper wire across terminals at wall switch if burner comes on replace defective wall switch If okay jumper wires across wall switch w...

Страница 42: ...upplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tool...

Страница 43: ...e re department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand DO NOT try to repair it call a quali ed service technician For...

Страница 44: ...cal section of the appliance Installation Manual 3 Turn the appliance on according to the instructions below for the appropriate type of control Standard Wall Switch Toggle the switch as you would und...

Страница 45: ...T RC400 all installed accessories can be controlled by the IFT RC400 see IFT RC400 user manual The IFT ECM has a safety feature that will automatically shut down the fireplace after 9 hours of continu...

Страница 46: ...e IFT ECM 3 position selector switch to ON or REMOTE position Module will beep once and flash a three GREEN LED code on successful startup If placed in ON position the appliance will ignite normally i...

Страница 47: ...etween the desired room temperature and actual temperature In thermostat mode the hearth appliance will start in HI flame but as the actual temperature approaches the desired set temperature on the re...

Страница 48: ...ose connections or electrical shorts in wiring from module to pilot assembly Verify wire insulation is not damaged Verify wires are not grounding out to chassis pilot burner or any other metal object...

Страница 49: ...n main valve solenoid Check main valve solenoid resistance nominal is 60 ohms If open or shorted replace valve Verify valve inlet pressure is correct for gas type Pilot and main do not light ECM goes...

Страница 50: ...ensor one engulfing the thermopile and the other reaching to the main burner Burner Inspect area around the injector Remove any lint or foreign material with a brush or vacuum Burner Flame The flames...

Страница 51: ...as to be painted with a wire brush and be sure to cover the logs burner and valve assembly glass and frame assembly Apply the paint sparingly two light coats of paint will give better results than a s...

Страница 52: ...alant along the inside corner of the glass frame all around the perimeter Place the flat gasketed side of the glass panel back into the steel frame Pinch the rounded inside facing gasket material to b...

Страница 53: ...opile Black Black Millivolt Gas Valve St124b on off switch wiring 1 11 00 djt TP TH TP TH Thermostat Optional Thermopile Black Black St124c Thermostat wiring 1 11 00 djt TP TH TP TH FAN Strain Relief...

Страница 54: ...nual_R20 11 21 Figure 6 3 INDV IFT Wiring Diagram FLAME SENSE IGNITER RF MODULE 6 PIN BRN ORANGE PILOT GREEN MAIN IFT RC400 REMOTE CONTROL BLK RED ROCKER SWITCH SPLITTER BLK RED BLK TO JUNCTION BOX 11...

Страница 55: ...BSB Classic Black INDVRBMSB Majolica Brown End Manufacturing Date Mar 2019 INDVRBDSB Bordeaux INDVRBSSB Biscuit End Manufacturing Date Mar 2019 Intrepid Direct Vent Rear Vent Gas Heater With Standing...

Страница 56: ...ly 20012906 Y 3 Top Classic Black 30003930A Biscuit SRV30004239 Bordeaux 30006762A Brown Majolica SRV30004921 4 Front Operable Door Classic Black 30003931A Biscuit SRV30004240 Bordeaux 30006763A Brown...

Страница 57: ...Assembly 3 Way N DV RN 0 199 706 SRV10002264 Y N DV RP 0 199 703 SRV10002265 Y 23 2 Pilot PSE NA175 20001115A Y LP175 20001116A Y 24 Thermocouple SRV24D0808 Y 25 Electrode Ignitor w Cable SIT24 100012...

Страница 58: ...MENTS PART NUMBER 43 Safety Barrier 30007255 44 Zero Clearance Sleeve Qty 2 req 54623 Touch Up Paint Classic Black 3 42 19905 Bordeaux 0001341 Biscuit 0001277 Majolica 0001270 Fan Kit FK20 VC Y Fan On...

Страница 59: ...2019 Ending Manufacturing Date Active Gas Stove INDVR IFT CB Classic Black INDVR IFT BD Bordeaux Intrepid Direct Vent Rear Vent Gas Heater w IFT Controls Part number list on following page 10 19 14 15...

Страница 60: ...4 Front Operable Door Classic Black 30003931A Bordeaux 30006763A 5 Door Right Classic Black 30003933A Bordeaux 30006765A 6 Door Left Classic Black 30003932A Bordeaux 30006764A 7 End Left Classic Black...

Страница 61: ...Switch 30000874 Y 36 Air Shutter Assembly 20012517 37 Gasket Control Plate 30004200 38 Gasket HE Door 1203687A Y 39 Gasket Flue Collar 30004021 Y 40 Gasket Cement 1206122 Y Magnet Door Use common supe...

Страница 62: ...re in the room Refer to Page 54 for wiring diagrams These remote controls are for use with standard millivolt models ON OFF Remotes ON OFF Thermostat Remote RCB RCMT TSST RCST Warming Shelf Warming sh...

Страница 63: ...distributor whichever occurs earlier However the Warranty coverage shall commence no later than 24 months following the date of Product shipment from HHT regardless of the installation or occupancy da...

Страница 64: ...evices such as exhaust fans or forced air furnaces or other such causes 6 use of fuels other than those specified in the operation instructions 7 installation or use of components not supplied with th...

Страница 65: ...6565 3 90 30007474 Vermont Castings Intrepid DV IFT Owner s Manual_R20 11 21...

Страница 66: ...ure les caract ristique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 Based on CSA P 4 1 2015 EFFICIENCY RATINGS MODEL ENERGUIDE RATINGS STOVE EFFICIENCY PERCENTAGE D O E AFUE PE...

Отзывы: