Vermont Castings DVR28 Direct Vent Gas Fireplace

1
2
3
4

1
2
3
4

1 + 2 + 3 + 4 = 270°

FP1179

Fig. 26 

  Maximum elbow usage.

• 

The maximum angular variation allowed in the sys-
tem is 270°. (Fig. 26)

• 

The minimum height of the vent above the highest 
point of penetration through the roof is 2’ (610 mm). 
(Fig. 29)

Vertical Through-the-Roof Installation

1.  Locate your fireplace.
2.  Plumb to center of the (4”) flue collar from ceiling 

above and mark position.

3.  Cut opening equal to 9

³⁄₈

” x 9

³⁄₈

” (240 x 240 mm).

4.  Proceed to plumb for additional openings through 

the roof. In all cases, the opening must provide a 
minimum of 1 inch clearance to the vent pipe, i.e., 
the hole must be at least 9

³⁄₈

” x 9

³⁄₈

” (240 x 240 mm).

5.  Place fireplace into position.
6.  Place firestop(s) #7DVFS or Attic Insulation Shield 

#7DVAIS into position and secure. (Fig. 27)

7.  Install roof support (Fig. 44) and roof flashing making 

sure upper flange is below the shingles. (Fig. 28)

8.  Install appropriate pipe sections until the venting is 

above the flashing. (Fig. 30)

9.  Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height. (Fig. 

29)

11. Apply high temperature sealant to 4” and 7” collars 

of vertical vent termination and install.

If there is a room above ceiling level, fire stop spacer 
must be installed on both the bottom ad the top side 
of the ceiling joists. If an attic is above ceiling level a 
7DVAIS (Attic Insulation Shield) must be installed.
The enlarged ends of the vent section always face 
downward.

FP1029
attic insulation shield
firestop spacers
1/28/00   djt

Joist

Attic Insulation Shield

Ceiling Installation

Upper Floor

11”

(279mm)

Firestop 
Spacer

Nails (4)

Fig. 27  

Place firestop spacer(s) and secure.

FP1029

11”

(279mm)

FP1184
Typical roof/ceiling
support apps.

Typical Roof 

Support 

Application

Typical Ceiling Support 

Application

Fig. 28 

 Venting supports.

FP1184

TWL101a
Twist Lock Pipe
2/8/99   djt

3 #5 Sheet Metal 

Screws per Joint

Sealant

TWL101a

Fig. 30 

 Roof flashing.

Storm Collar

Min.
2' (610 mm)

FP1185

Fig. 29

  Minimum termination to roof clearance.

Содержание DVR28IN

Страница 1: ...he re department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE ALWAYS READ THIS MANUAL FIRST...

Страница 2: ...nd Installation 13 Vertical Side Wall Venting Applications and Installation 14 Below Grade Installation 15 Vertical Through the Roof Applications and Installation 16 Venting Components 18 Operating In...

Страница 3: ...y from the front of this replace when it is in use 5 Never operate the replace if it has malfunctioned and has not yet been serviced or if it has been exposed to water or damaged in any manner and has...

Страница 4: ...d oil from the manufacturing process Provide adequate ventilation during the breaking in process by opening all windows Proposition 65 Warning Fuels used in gas wood burning or oil red appliances and...

Страница 5: ...st vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF AL...

Страница 6: ...95 mm 14 377 mm 7 183 mm Wall Mount Bracket Typ 16 406 mm o c 10 264 mm 9 238 mm FP1783 Fig 3 Firestop framing 1 25 mm Min 10 254 mm Min 24 610 mm Min FP1782 DVR29 min clearances 3 07 27 686 mm 6 152...

Страница 7: ...s 1 The DVR28 comes with a wall mount bracket to secure the replace to the wall Standoffs on the back of the bracket allow for proper clearances to combustibles Fig 5 16 o c 406 mm Firestop Framing if...

Страница 8: ...lt provincial and or local authorities having jurisdiction for installations at elevations above 4 500 feet 1 370m Gas Line Installation Always remove the front window frame as sembly before purging t...

Страница 9: ...ow out 20 6 m 2 90 Elbow vertical 11 3 4 m 90 elbow out 13 4 m 3 90 Elbow vertical 20 6 m 90 elbow out 7 2 m 4 90 40 12 m vertical Flue restricted to 1 1 29 mm opening in ue pipe outlet 2 7 8 22 mm op...

Страница 10: ...al Venting There must not be any obstruction such as bushes garden sheds fences decks or utility buildings within 24 610 mm from the front of the termination hood Do not locate termination hood where...

Страница 11: ...nt outlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for appliances 10 000 Btuh 6 15 cm for appliances to building or the combustion air inlet to any 3kW 12 30 cm for applia...

Страница 12: ...NOTE Termination in an alcove space spaces open only on one side and with an overhang is permitted with the dimensions speci ed for vinyl or non vinyl siding and sof ts 1 There must be a 3 914 mm min...

Страница 13: ...nting components are approved to be used in these applications Refer to Venting Components listed for different installation requirements The maximum horizontal distance between the rear of the applia...

Страница 14: ...Fig 19 Attach the termination to the wall as outlined in the instruction sheet supplied with the termination FP1005 Side View Vent Termination 1 25 00 djt Finished Wall Vent Termination FP1753 Fig 19...

Страница 15: ...the 90 elbows are used to increase or redirect a vertical rise Fig 21 Example According to the vent graph Page 11 the maximum horizontal vent length in a system with a 7 5 2 3 m vertical rise is 20 6...

Страница 16: ...ews Sheet Metal Screws Foundation Recess Watertight Seal Around Pipe BG401 Fig 24 Snorkel installation recessed foundation Vertical Through the Roof Application This gas replace has been approved for...

Страница 17: ...Install appropriate pipe sections until the venting is above the ashing Fig 30 9 Install storm collar and seal around the pipe 10 Add additional vent lengths for proper height Fig 29 11 Apply high te...

Страница 18: ...VRT90 for Rear Vent to Vertical Vent 90 Elbow 7TDV90 Vertical Horizontal Offset Telescopic vent sections 7TDVP1218 11 to 17 adjustable length 7TDVTP3564 35 to 67 adjustable length Pipe sections for ve...

Страница 19: ...ame Assembly Fireplace Front Glass Panel Fig 31 Window frame assembly removal FP1758 Glass Cleaning It is necessary to clean the glass periodically During start up condensation which is normal forms o...

Страница 20: ...Temperature Adjustment To adjust Hi Lo setting push either the high or low con trol button on remote control transmitter FP1796 Wireless remote 3 07 ON OFF HI LO FP1759 Fig 34 Flame adjustment for Am...

Страница 21: ...as line to the OFF position FP297A Warning If you do not follow these instructions exactly a re or explosion may result causing property damage personal injury and loss of life Lighting Instructions T...

Страница 22: ...recom mended that ALKALINE batteries always be used for longer battery life and maximum operational performance Before using the transmitter install the 2 AAA transmitter bat teries into the battery c...

Страница 23: ...mode ON LO Flame Operation Press and release the ON H L key The appliance ame will stay ON and ame on LO During this time the LCD screen will show LO After 3 seconds the LCD screen will default to di...

Страница 24: ...Press and hold the OFF CONTINUOUS PILOT key for approximately 5 seconds until the word PILOT appears on the LCD screen NOTE The word PILOT will appear on the LCD screen in ON mode CP Childproof Featu...

Страница 25: ...ON or OFF depending on which button is being pressed The LED indicator should illuminate on wall transmitters and on off hand held transmitters Fig 43 Buttons should be pressed and held for 1 to 2 sec...

Страница 26: ...e leads from the module are securely connected to the terminals labeled PILOT on the valve body Fig 42 Ensure the black GROUND wire is securely connected to an appropriate metal portion of the valve o...

Страница 27: ...body red to red and black to black Verify the selector switch on the battery pack is set to DC MOTOR DRIVE or LATCHING SOLENOID depending upon which device is installed Fig 41 Check functionality wit...

Страница 28: ...or OFF command was not last sent from another transmitter These commands will over ride the thermal commands from the handheld trans mitter To return the system to THERMO mode press either ON or OFF...

Страница 29: ...ation 6 Ignite pilot Refer to Lighting Instructions 7 Reinstall window frame assembly Maintenance FP1778 Fig 45 Correct pilot ame appearance WARNING Always use a quali ed technician or service agency...

Страница 30: ...28 1 Burner Tube 20012266 2 Rear Refractory 20011551 3 Ceramic Retainer 20012350 4 Bracket Upper Trim 20011581 5 Lower Bracket Assembly 20011579 6 Valve Assy VF4000 20012290 7 Main Module 20011895 8 S...

Страница 31: ...ninspection thedamageisfoundtobethefaultofthemanufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this war...

Страница 32: ...ings Model EnerGuide Ratings Steady State D O E Fireplace Ef ciency Fan OFF Fan ON AFUE DVR28IN 67 6 85 n a 64 3 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CF...

Отзывы: