background image

14

20012301

Vermont Castings DVR28 Direct Vent Gas Fireplace

STEP 1

Locate vent opening on the wall. To locate hole center 
consult with appropriate fireplace dimensions, Page 4. 
Frame as shown below.

Combustible Walls 

(Fig. 17)

Cut a 10

³⁄₈

”H x 9

³⁄₈

” W 

(264 x 240 mm) hole through the exterior wall and 
frame as shown. 

Noncombustible Walls

 (Fig. 17)

:

 Hole opening must 

be 7

¹⁄₂

” (190 mm) in diameter. 

Always use a zero clearance sleeve when 
the wal is combustible.

STEP 2

Measure wall thickness and cut zero clearance sleeve 
parts to proper length (MAXIMUM 12”/305 mm). Assem-
ble sleeve and attach to firestop with #8 sheet metal 
screws (supplied). (Fig. 18)

STEP 3

Measure the horizontal length requirement for the vent-
ing including a 2” (51 mm) overlap, i.e. from the elbow 
to the outside wall face plus 2” (51 mm). (Fig. 15 or 16)

attach the elbow to the appliance in the same manner 
then attach the venting to the elbow.

Never permit a downward slope (away from 
the fireplace) to occur anywhere in the sys-
tem when installing the vent or an elbow in 
the vent.

STEP 5

Guide the venting through the vent hole a you place the 
appliance in its installed position. Guide the 4” (102 mm) 
and 7” (178 mm) collar of the vent termination into the 
outer ends of the venting. Do not force the termination. If 
the vent pipes do not align with the termination, remove 
and realign the venting at the appliance flue collars. 
(Fig. 19) Attach the termination to the wall as outlined in 
the instruction sheet supplied with the termination.

FP1005
Side View Vent Termination
1/25/00   djt

Finished Wall

Vent 

Termination

FP1753

Fig. 19

  Side view of final unit location.

Firestop

Zero Clearance 

Sleeve

Rear Wall Installation

Twist Lock Pipe

FP1751
vent opening
2/07

Vent Opening for Combustible Wall

9

³⁄₈

(240mm)

10

³⁄₈

(264mm)

Fireplace Hearth

Framing 

Detail

Opening for 

Noncombustible Wall

7

¹⁄₂

(190 mm)

FP1751

Fig. 17

  Locate vent opening on wall.

Firestop

Top Tabs

Bottom Tabs

Install provided firestop with zero 

clearance sleeve into framing 

opening after drywall or finish 

material is installed. Use the tabs 

for clearance locators top and 

bottom.

Maintain 1” (25 mm) Air 

Space from Zero Clear-

ance Sleeve to Framing

FP1752 
Zero Clearance Sleeve
2/07

Max. Length 

12” (305mm)

#8 Screws (2)

#8 Screws 

(2)

Adjustable 
Zero Clear-
ance Sleeve

#8 Screws 

(2)

Adjust-

able Zero 

Clearance 

Sleeve

FP1752

Fig. 18

  Adjustable zero clearance sleeve.

Firestop

1” (25 mm) Clear-

ance between Zero 

Clearance Sleeve 

and Framing

STEP 4

Install the 4” (102 mm) vent to the appliance collar and 
secure with three (3) sheet metal screws. Install the 7” 
(178 mm) vent pipe to the appliance collar and secure 
with three (3) sheet metal screws. It is not necessary 
to seal this connection. If a 45° elbow is being used, 

Vertical Sidewall Applications

Since it is very important for the venting system 
to maintain balance between the combustion air 
intake and the flue gas exhaust, certain limitations 
as to vent configurations apply and must be strictly 
adhered to.

Содержание DVR28IN

Страница 1: ...he re department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE ALWAYS READ THIS MANUAL FIRST...

Страница 2: ...nd Installation 13 Vertical Side Wall Venting Applications and Installation 14 Below Grade Installation 15 Vertical Through the Roof Applications and Installation 16 Venting Components 18 Operating In...

Страница 3: ...y from the front of this replace when it is in use 5 Never operate the replace if it has malfunctioned and has not yet been serviced or if it has been exposed to water or damaged in any manner and has...

Страница 4: ...d oil from the manufacturing process Provide adequate ventilation during the breaking in process by opening all windows Proposition 65 Warning Fuels used in gas wood burning or oil red appliances and...

Страница 5: ...st vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF AL...

Страница 6: ...95 mm 14 377 mm 7 183 mm Wall Mount Bracket Typ 16 406 mm o c 10 264 mm 9 238 mm FP1783 Fig 3 Firestop framing 1 25 mm Min 10 254 mm Min 24 610 mm Min FP1782 DVR29 min clearances 3 07 27 686 mm 6 152...

Страница 7: ...s 1 The DVR28 comes with a wall mount bracket to secure the replace to the wall Standoffs on the back of the bracket allow for proper clearances to combustibles Fig 5 16 o c 406 mm Firestop Framing if...

Страница 8: ...lt provincial and or local authorities having jurisdiction for installations at elevations above 4 500 feet 1 370m Gas Line Installation Always remove the front window frame as sembly before purging t...

Страница 9: ...ow out 20 6 m 2 90 Elbow vertical 11 3 4 m 90 elbow out 13 4 m 3 90 Elbow vertical 20 6 m 90 elbow out 7 2 m 4 90 40 12 m vertical Flue restricted to 1 1 29 mm opening in ue pipe outlet 2 7 8 22 mm op...

Страница 10: ...al Venting There must not be any obstruction such as bushes garden sheds fences decks or utility buildings within 24 610 mm from the front of the termination hood Do not locate termination hood where...

Страница 11: ...nt outlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for appliances 10 000 Btuh 6 15 cm for appliances to building or the combustion air inlet to any 3kW 12 30 cm for applia...

Страница 12: ...NOTE Termination in an alcove space spaces open only on one side and with an overhang is permitted with the dimensions speci ed for vinyl or non vinyl siding and sof ts 1 There must be a 3 914 mm min...

Страница 13: ...nting components are approved to be used in these applications Refer to Venting Components listed for different installation requirements The maximum horizontal distance between the rear of the applia...

Страница 14: ...Fig 19 Attach the termination to the wall as outlined in the instruction sheet supplied with the termination FP1005 Side View Vent Termination 1 25 00 djt Finished Wall Vent Termination FP1753 Fig 19...

Страница 15: ...the 90 elbows are used to increase or redirect a vertical rise Fig 21 Example According to the vent graph Page 11 the maximum horizontal vent length in a system with a 7 5 2 3 m vertical rise is 20 6...

Страница 16: ...ews Sheet Metal Screws Foundation Recess Watertight Seal Around Pipe BG401 Fig 24 Snorkel installation recessed foundation Vertical Through the Roof Application This gas replace has been approved for...

Страница 17: ...Install appropriate pipe sections until the venting is above the ashing Fig 30 9 Install storm collar and seal around the pipe 10 Add additional vent lengths for proper height Fig 29 11 Apply high te...

Страница 18: ...VRT90 for Rear Vent to Vertical Vent 90 Elbow 7TDV90 Vertical Horizontal Offset Telescopic vent sections 7TDVP1218 11 to 17 adjustable length 7TDVTP3564 35 to 67 adjustable length Pipe sections for ve...

Страница 19: ...ame Assembly Fireplace Front Glass Panel Fig 31 Window frame assembly removal FP1758 Glass Cleaning It is necessary to clean the glass periodically During start up condensation which is normal forms o...

Страница 20: ...Temperature Adjustment To adjust Hi Lo setting push either the high or low con trol button on remote control transmitter FP1796 Wireless remote 3 07 ON OFF HI LO FP1759 Fig 34 Flame adjustment for Am...

Страница 21: ...as line to the OFF position FP297A Warning If you do not follow these instructions exactly a re or explosion may result causing property damage personal injury and loss of life Lighting Instructions T...

Страница 22: ...recom mended that ALKALINE batteries always be used for longer battery life and maximum operational performance Before using the transmitter install the 2 AAA transmitter bat teries into the battery c...

Страница 23: ...mode ON LO Flame Operation Press and release the ON H L key The appliance ame will stay ON and ame on LO During this time the LCD screen will show LO After 3 seconds the LCD screen will default to di...

Страница 24: ...Press and hold the OFF CONTINUOUS PILOT key for approximately 5 seconds until the word PILOT appears on the LCD screen NOTE The word PILOT will appear on the LCD screen in ON mode CP Childproof Featu...

Страница 25: ...ON or OFF depending on which button is being pressed The LED indicator should illuminate on wall transmitters and on off hand held transmitters Fig 43 Buttons should be pressed and held for 1 to 2 sec...

Страница 26: ...e leads from the module are securely connected to the terminals labeled PILOT on the valve body Fig 42 Ensure the black GROUND wire is securely connected to an appropriate metal portion of the valve o...

Страница 27: ...body red to red and black to black Verify the selector switch on the battery pack is set to DC MOTOR DRIVE or LATCHING SOLENOID depending upon which device is installed Fig 41 Check functionality wit...

Страница 28: ...or OFF command was not last sent from another transmitter These commands will over ride the thermal commands from the handheld trans mitter To return the system to THERMO mode press either ON or OFF...

Страница 29: ...ation 6 Ignite pilot Refer to Lighting Instructions 7 Reinstall window frame assembly Maintenance FP1778 Fig 45 Correct pilot ame appearance WARNING Always use a quali ed technician or service agency...

Страница 30: ...28 1 Burner Tube 20012266 2 Rear Refractory 20011551 3 Ceramic Retainer 20012350 4 Bracket Upper Trim 20011581 5 Lower Bracket Assembly 20011579 6 Valve Assy VF4000 20012290 7 Main Module 20011895 8 S...

Страница 31: ...ninspection thedamageisfoundtobethefaultofthemanufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this war...

Страница 32: ...ings Model EnerGuide Ratings Steady State D O E Fireplace Ef ciency Fan OFF Fan ON AFUE DVR28IN 67 6 85 n a 64 3 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CF...

Отзывы: