"Duzy" Gas Log Sets – The Look and Feel of a Real Wood Fire

22

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 

detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State  of 

Massachusetts requires the damper to be permanently removed 

or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 

bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 

bedroom or bathroom regardless of size or type in the State of 

Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

(2) Revise  10.8.3  by  adding  the  following  additional 

requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment installed in every dwelling, building or structure used 

in  whole  or  in  part  for  residential  purposes,  including  those 

owned or operated by the Commonwealth and where the side 

wall exhaust vent termination is less than seven (7) feet above 

finished  grade  in  the  area  of  the  venting,  including  but  not 

limited to decks and porches, the following requirements shall 

be satisfied:
1. 

Installation  of  carbon  monoxide  detectors. 

At  the  time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 

equipment,  the  installing  plumber  or  gas  fitter  shall  observe 

that a hard wired carbon monoxide detector with an alarm and 

battery  back-up  is  installed  on  the  floor  level  where  the  gas 

equipment is to be installed. In addition, the installing plumber 

or gas fitter shall observe that a battery operated or hard wired 

carbon  monoxide  detector  with  an  alarm  is  installed  on  each 

additional level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services of 

qualified licensed professionals for the installation of hard wired 

carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 

hard  wired  carbon  monoxide  detector  with  alarm  and  battery 

back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of  installation,  the 

owner shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said thirty 

(30) day period, a battery operated carbon monoxide detector 

with an alarm shall be installed.

Massachusetts Residents Only — Please read and follow these special requirements

2. 

Approved  Carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.
3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 

minimum height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment. The sign shall read, in print size 

no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. 

Inspection.

 The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve the 

installation  unless,  upon  inspection,  the  inspector  observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) 

Exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not 

Required To Be Vented" in the most current edition of NFPA 54 

as adopted by the Board; and
2.  Product Approved  side  wall  horizontally  vented  gas  fueled 

equipment  installed  in  a  room  or  structure  separate  from  the 

dwelling,  building  or  structure  used  in  whole  or  in  part  for 

residential purposes.
(c)  

Manufacturer requirements — Gas Equipment Venting 

System  Provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 

a  venting  system  design  or  venting  system  components  with 

the equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system shall 

include:
1. Detailed instructions for the installation of the venting system 

design or the venting system components; and
2. A complete parts list for the venting system design or venting 

system.
(d) 

Manufacturer requirements — Gas Equipment Venting 

System Not Provided. 

When the manufacturer of a Product 

Approved  side  wall  horizontally  vented  gas  fueled  equipment 

does  not  provide  the  parts  for  venting  the  flue  gases,  but 

identifies “special venting systems,” the following requirements 

shall be satisfied by the manufacturer:
1.  The  referenced  "special  venting  system"  instructions  shall 

be  included  with  the  appliance  or  equipment  installation 

instructions; and
2. The “special venting systems” shall be Product Approved by 

the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions.
(e)  

A  copy  of  all  installation  instructions  for  all  Product 

Approved side wall horizontally vented gas fueled equipment, 

all  venting  instructions,  all  parts  lists  for  venting  instructions, 

and/or all venting design

Содержание DUZY VDY24/18

Страница 1: ...e Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your ga...

Страница 2: ...r Placement 12 Decorative Volcanic Rock Placement 12 Fireplace Draft Test 12 contents Flame Appearance 13 Initial Startup 13 Operating Instructions 14 For Your Safety Read Before Lighting 14 Millivolt...

Страница 3: ...zard of high surface temperature and should stay away to avoid burns or clothing ignition 11 Young children should be carefully supervised when they are in the same room with the gas log set in opera...

Страница 4: ...hutoff valve Piping which complies with local codes Pipe wrench Tee joint Pipe sealant approved for use with propane L P G Resistant to sulfur compounds Drill with masonry bit for mounting to the floo...

Страница 5: ...re of the fireplace damper blade and provide a minimum flue opening per table below Should the clamp not fit or provide the required permanent opening from the table have the damper blade cut to pro v...

Страница 6: ...in the homeowner s manual must not be exceeded NOTE If the log set is equipped with a remote receiver a restrictive barrier may reduce the battery life by increasing the ambient temperature inside th...

Страница 7: ...pe Internally tinned copper or copper tubing can be used per National Fuel Code section 2 6 3 providing gas meets hydrogen sulfide limits and where permitted by local codes Gas piping system must be s...

Страница 8: ...cause improper and dan gerous operation Verify proper operation after servicing WARNING The Millivolt thermopile is a self powered combination gas control that does not require 110VAC to operate See F...

Страница 9: ...k covering The remote receiver is attached but does not physi cally fit inside the fireplace with 2 clearance to the side wall install remote receiver Connect wires according to remote receiver instru...

Страница 10: ...e 8 LG1000 VDY2418D5 BACK LOG Back Log 1 LG1000 Figure 9 LG1001 VDY2418D5 bottom logs Bottom Left Log 3 Bottom Right Log 2 LG1001 Figure 10 2 Placed bottom right log 2 on right side of grate Figure 10...

Страница 11: ...d middle right log Figure 11 5 Place middle right log 5 on top of bottom right log Figure 11 6 Rest top right log 6 on back log and bottom right log Figure 12 7 Place top left log 7 on bottom left log...

Страница 12: ...is important to periodically clean and inspect the logs per the cleaning and ser vicing section of the manual FIREPLACE DRAFT TEST FIREPLACE DRAFT TEST METHOD To determine if your fireplace is draftin...

Страница 13: ...pilot flame must always be present when appliance is in operation It should touch the thermocouple or ther mopile body Initial Startup During manufacturing fabricating and shipping various components...

Страница 14: ...pplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never...

Страница 15: ...ntrol knob in for a further 60 seconds to prevent the flame detector from shut ting off the gas while the probe is warming up Release the control knob 9 Turn gas control knob counterclockwise to the O...

Страница 16: ...lure to keep air intake holes clean will result in sooting and poor combustion If embers rock wool have turned a rust color and become brittle remove old embers rock wool from log set Replace with new...

Страница 17: ...2 Pilot is partially clogged 3 Defective thermopile 1 Gas leak 2 Control valve defective 1 Gas supply turned off or manual shutoff valve closed 2 Control knob not in PILOT position 3 Control knob not...

Страница 18: ...s clogged or dam aged 2 Burner is damaged 3 Gas regulator is defective 1 Vapors from paint or curing process of logs 1 Turning control knob to HIGH posi tion when burner is cold 2 Air in gas line 3 Di...

Страница 19: ...07 2 Control Knob 18D0603 18D0603 3 Millivolt Control Valve w Pilot 27D8006 27D8005 4 Pilot 27D8974 27D8973 5 Thermocouple Thermopile 28D0566 28D0566 ACCESSORIES Flex Connector Flexcon30 Wall Kit Swit...

Страница 20: ...2418D5 logs REPLACEMENT PARTS DUZY V LOG SERIES Ref Description Qty VDY24 18D5 1 Back Log 1 32D3121 2 Bottom Right Log 1 32D3122 3 Bottom Left Log 1 32D3123 4 Middle Left Log 1 32D3124 5 Middle Right...

Страница 21: ...21 Duzy Gas Log Sets The Look and Feel of a Real Wood Fire 20304949...

Страница 22: ...days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents...

Страница 23: ...s The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox b...

Страница 24: ...Technical Service Costco Bilingual 1 800 463 3783 Vermont Castings Group 1 866 500 5670 Vermont Castings Group 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup com...

Отзывы: