8
57D0215
380IDV/490IDV Fireplace Insert
cleARANceS
INSeRt cleARANceS
No combustibles (ie: drapes, doors) may be within, or swing
within 36" of the front of the insert.
MANtel cleARANceS
NOte: the combustible area above the facing must
not protrude more than 3/4" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
heARth RequIReMeNtS
The insert must be installed on a noncombustible hearth
extending a minimum of 12" from the fireplace opening
(local codes may require a larger hearth). The hearth must
also extend to both sides of the face.
Figure 4 -
Mantel Clearances
FP2623
Minimum clearances
Max.
13”
Max.
3/4”
Min.
9”
Min.
11”
13” (330 mm)
Maximum Depth
Minimum
8” (203 mm)
22”
(559 mm)
Minimum
10” (254 mm)
Hearth Should be
Width of Face Minimum
Minimum
8” (203 mm)
Minimum
8” (203 mm)
32”
(813 mm)
Minimum
12” (305 mm)
Minimum
11” (279 mm)
3/4" Maximum
Depth
Combustible
Facing
FP2623
Содержание 380IDVNV
Страница 37: ...57D0215 380IDV 490IDV Fireplace Insert 37...