Output Configuration

1.   Communications Configuration
 

Communications parameters for the H663 series are field selectable for your  

 

convenience. Please see Figure 1 (page 2, #8) for selector location. The  

 

 

following parameters are configurable:

 

  

Parity: Odd, even or none

 

■ 

 Wiring: Two or four

 

   Baud Rate:  2400, 4800, 9600 or 19200

 

2.   Address Configuration
 

Each ModBus device on a single network must have a unique address. The    

 

switch block must be set to assign a unique address before the device is    

 

connected to the ModBus RS485 network. If an address is selected which    

 

conflicts with another device, neither device will be able to communicate. 

Chart 1

CONFIGURATION

The values of each dip switch are as follows:

 

 

 

1=1

 

 

 

2=2

 

 

 

3=4

 

 

 

4=8

 

 

 

5=16

 

 

 

6=32

 

 

 

7=64

 

 

 

8=128

To determine an address you simply add the values of any switch that is on. 

For example:

Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32.  (8+32 = 40)

See Chart 2 on the following page for a pictorial listing of the first 63 switch positions.

or

H663 series can be addressed as any whole number between and including 1-247. Each unit is equipped with a set of 8 dip switches for addressing. See below.

LSB

MSB

VALUE

Example: 2-wire 9600 Baud No Parity (Default Only)

=

=

1
X
X
X
X
X
X

2

On

Off

3

Off

On

Off

On

4

Off
Off

On
On

5

6

7
X
X
X
X
X
X

8
X
X
X
X
X
X

2400 Baud
4800 Baud

9600 Baud

19200 Baud

2 wire

4 wire

Wiring, Baud Rate, Parity

Wiring

None

Even
Odd

Off
Off
On

Off
On
Off

Parity

Baud Rate

DESIRED RESULT

Switch #

Baud Rate and Parity Switch Setttings

40

Shop for Power Metering products online at:

1.877.766.5412

www.

PowerMeterStore

.ca

Содержание H663 Series

Страница 1: ...workReadyRS485Output Retrieve amperage information from up to 42 circuits with one RS485 drop easy wiring Global alarm register for instant alarm and warning notification Integrates to available network display for local indication Easy to use configuration software simplifies setup and provides flexibility to customize the configuration to meet the application DANGER OF ELECTROCUTION BECERTAINTHATEVER...

Страница 2: ...Baud Rate Parity Selection Switches Field selectable RS 485 serial interface control See Chart 1 on page 5 INSTALLATION Figure1 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42 40 38 9 Modbus Address Dip Switches Each Modbus device must have a unique address These switches must be set to assign an individual address before the device is connected to the network See page 5 10 Lithium Battery CA...

Страница 3: ...0 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 LEFT RIGHT 4 1 3 9 3 7 3 5 3 3 3 1 2 9 2 7 2 5 2 3 2 1 1 9 1 7 1 5 1 3 1 1 9 7 5 3 1 4 2 4 0 3 8 3 6 3 4 3 2 3 0 2 8 2 6 2 4 2 2 2 0 1 8 1 6 1 4 1 2 1 0 8 6 4 2 Channel4 Channel2 Channel3 Channel41 Channel1 FT RIGHT Channel42 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42 40...

Страница 4: ...ket Kit Acquisition and interconnection boards are mounted to the bracket at the factory Data Acquisition Board 11 375 289 mm 1 12 28 mm 5 75 146 mm Data Acquisition Board Mounting Bracket Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore ca ...

Страница 5: ...alues of each dip switch are as follows 1 1 2 2 3 4 4 8 5 16 6 32 7 64 8 128 To determine an address you simply add the values of any switch that is on For example Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32 8 32 40 See Chart 2 on the following page for a pictorial listing of the first 63 switch positions or H663 series can be addressed as any whole number between...

Страница 6: ...NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore ca ...

Страница 7: ...use 4 Replace with new fuse see specifications for fuse type 5 Reconnect 120V power source to Data Acquisition Board 6 Reconnect power 7 Check Alive LED for proper function See Figure 1 3 on page 2 for location 240VACforH663SM xxE Iffuseblowsrepeatedly checkpowersourcetoensurethatitisastable120VACsource Master NetworkDisplay Slave H663series TX SHLD TX RX TX RX TX TX SHLD TX RX TX RX TX SHIELD SHIE...

Страница 8: ...1 stop bit Termination 5 position depluggable connector Defaults Warning Register 60 of current sensor max configurable Alarm Register 70 of current sensor max configurable Breaker Size Register 20A Dimensions Circuit Board L x W 7 25 x 5 75 Split Core CT s 6 leads 1 04 x 1 04 x 1 58 Lithium Battery Life 5 years Replace with type CRF 1220 or equiv CAUTION DANGER OF EXPLOSION IF BATTERY IS INCORRECTL...

Отзывы: