RS 485 2 or 4-Wire Connection

 

 

Daisy chain multiple H663's using a 2-wire or 4-wire modbus network. Refer  

 

to Figure 4 on page 7.  

 

 

   2

 

Optical Communications Isolation

 

Optical isolators are used to separate 120 VAC portions of the circuit from the  

 

RS485 network.

  3

 

Alive LED

    

Flashes once per second to indicate correct  operation. If steadily lit or out,  

 

indicates internal failure.

  4

 

Current Transformer (CT) Connectors (Interconnection Boards)

 

Numbered terminals correspond to the input channels of the acquisition    

 

board. Fasten the  current transformer connectors into the terminals  as    

 

shown in figure 3 on page 3.

  5

  

120 VAC Power Connection*

 

Easy 2-wire 120 VAC line to neutral 50/60 Hz.

  6

  

250 VAC 100mA Fuse

 

Fused power connection for circuit protection.

  7

 

Power Transformer

 

Linear power supply for reliability and low noise

  8

 

Baud Rate & Parity Selection Switches

 

Field selectable RS-485 serial interface control.

 

(See Chart 1 on page 5)

INSTALLATION

Figure 1

6

4

2

12

10

8

18

16

14

24

22

20

30

28

26

36

34

32

42

40

38

 

 

9

 

Modbus Address Dip Switches

 

Each Modbus device must have a unique address. These switches must be set  

 

to assign an individual address before the device is connected to the  

 

 

network. (See page 5)             

 10

   Lithium Battery

 

CAUTION! DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY  

 

 

REPLACED. REPLACE ONLY WITH THE SAME OR EQUIVALENT    

 

 

TYPE RECOMMENDED BY THE MANUFACTURER. DISPOSE OF    

 

USED BATTERIES ACCORDING TO THE MANUFACTURER'S  

 

 

 

INSTRUCTIONS.

  11 

  TX LED

 

Indicates transmission of information over the Modbus network.

 12 

RX LED

 

Indicates data received on the Modbus network

 13

 

Current Sensors

 

Each current sensor is capable of monitoring conductors carrying up to a    

 

maximum of 50 amps.*

* The H663SM-42H is capable of monitoring conductors up to a maximum of 100 amps. 
 

*For 240VAC Power Connection version, order catalog number H663SM-

xxE.

Shop for Power Metering products online at:

1.877.766.5412

www.

PowerMeterStore

.ca

Содержание H663 Series

Страница 1: ...workReadyRS485Output Retrieve amperage information from up to 42 circuits with one RS485 drop easy wiring Global alarm register for instant alarm and warning notification Integrates to available network display for local indication Easy to use configuration software simplifies setup and provides flexibility to customize the configuration to meet the application DANGER OF ELECTROCUTION BECERTAINTHATEVER...

Страница 2: ...Baud Rate Parity Selection Switches Field selectable RS 485 serial interface control See Chart 1 on page 5 INSTALLATION Figure1 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42 40 38 9 Modbus Address Dip Switches Each Modbus device must have a unique address These switches must be set to assign an individual address before the device is connected to the network See page 5 10 Lithium Battery CA...

Страница 3: ...0 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 LEFT RIGHT 4 1 3 9 3 7 3 5 3 3 3 1 2 9 2 7 2 5 2 3 2 1 1 9 1 7 1 5 1 3 1 1 9 7 5 3 1 4 2 4 0 3 8 3 6 3 4 3 2 3 0 2 8 2 6 2 4 2 2 2 0 1 8 1 6 1 4 1 2 1 0 8 6 4 2 Channel4 Channel2 Channel3 Channel41 Channel1 FT RIGHT Channel42 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42 40...

Страница 4: ...ket Kit Acquisition and interconnection boards are mounted to the bracket at the factory Data Acquisition Board 11 375 289 mm 1 12 28 mm 5 75 146 mm Data Acquisition Board Mounting Bracket Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore ca ...

Страница 5: ...alues of each dip switch are as follows 1 1 2 2 3 4 4 8 5 16 6 32 7 64 8 128 To determine an address you simply add the values of any switch that is on For example Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32 8 32 40 See Chart 2 on the following page for a pictorial listing of the first 63 switch positions or H663 series can be addressed as any whole number between...

Страница 6: ...NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore ca ...

Страница 7: ...use 4 Replace with new fuse see specifications for fuse type 5 Reconnect 120V power source to Data Acquisition Board 6 Reconnect power 7 Check Alive LED for proper function See Figure 1 3 on page 2 for location 240VACforH663SM xxE Iffuseblowsrepeatedly checkpowersourcetoensurethatitisastable120VACsource Master NetworkDisplay Slave H663series TX SHLD TX RX TX RX TX TX SHLD TX RX TX RX TX SHIELD SHIE...

Страница 8: ...1 stop bit Termination 5 position depluggable connector Defaults Warning Register 60 of current sensor max configurable Alarm Register 70 of current sensor max configurable Breaker Size Register 20A Dimensions Circuit Board L x W 7 25 x 5 75 Split Core CT s 6 leads 1 04 x 1 04 x 1 58 Lithium Battery Life 5 years Replace with type CRF 1220 or equiv CAUTION DANGER OF EXPLOSION IF BATTERY IS INCORRECTL...

Отзывы: