background image

-7-

Z202833-0K 

©2006 Veris Industries 

10061

2.  Use Software Configuration Tool to set up breaker size, warning levels, and alarm levels.  

3.  Power Connection

 

  Disconnect and lock out power source before making any connections. Connect 2-wire 120 VAC power to 

 

  power terminals.  (see #5 on page 2 for location) Observe polarity.

Changing the Lithium Battery

 

1. Normal life expectancy is approximately 5 years.

 

2.  Disconnect and lock out power to panel.

 

3.  Disconnect and lock out 120 V* power source to Data Acquisition Board.

 

4.  Remove old lithium battery. Take care not to short battery terminals.

 

5.  Replace with new lithium battery. (See specifications for battery type)

 

6.  Reconnect 120V* power source to Data Acquisition Board.

 

7.  Reconnect power.

 

Note: Do not dispose of lithium battery in fire. Use local recycling facility to dispose of lithium batteries.

Changing the Fuse

 

1.  Disconnect and lock out power.

 

2.  Disconnect and lock out 120V* power source to Data Acquisition Board.

 

3.  Remove old fuse.

 

4.  Replace with new fuse (see specifications for fuse type).

 

5.  Reconnect 120V* power source to Data Acquisition Board.

 

6.   Reconnect power.

 

7.   Check “Alive” LED for proper function (See Figure 1, #3 on page 2 for location).

 

*240VAC for H663SM-

xxE

 

**If fuse blows repeatedly, check power source to ensure that it is a stable 120VAC source.

Master (Network Display)

Slave (H663 series)

TX+

SHLD  

TX+

RX+

TX–

RX–

TX–

TX+

SHLD  

TX+

RX+

TX–

RX–

TX–

SHIELD

SHIELD

Master or Slave

TX+

SHLD  

TX+

RX+

TX–

RX–

TX–

SHIELD

SHIELD

INSTALLATION

NOTES

 

A. The Modbus cable should be mechanically secured where it enters the    

 

electrical panel.

 

B.  All Modbus devices should be connected together in  a daisy-chain fashion,  

 

and properly terminated.

 

C. The Modbus cable should be shielded twisted pair wire such as Belden 1120A.  

 

The cable must  be voltage rated for the installation.

    

WARNING: After wiring the 

 

Modbus cable, remove all scraps 

 

of wire or foil shield from the    

 

electrical panel. This could be 

 

DANGEROUS if wire scraps 

 

come into contact with 

 

high voltage conductors!

2-Wire

4-Wire

Figure 4

1.  Connect 2-wire or 4-wire Modbus RS485 network (see Figure 4).

SERVICE

Shop for Power Metering products online at:

1.877.766.5412

www.

PowerMeterStore

.ca

Содержание H663 Series

Страница 1: ...workReadyRS485Output Retrieve amperage information from up to 42 circuits with one RS485 drop easy wiring Global alarm register for instant alarm and warning notification Integrates to available network display for local indication Easy to use configuration software simplifies setup and provides flexibility to customize the configuration to meet the application DANGER OF ELECTROCUTION BECERTAINTHATEVER...

Страница 2: ...Baud Rate Parity Selection Switches Field selectable RS 485 serial interface control See Chart 1 on page 5 INSTALLATION Figure1 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42 40 38 9 Modbus Address Dip Switches Each Modbus device must have a unique address These switches must be set to assign an individual address before the device is connected to the network See page 5 10 Lithium Battery CA...

Страница 3: ...0 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 LEFT RIGHT 4 1 3 9 3 7 3 5 3 3 3 1 2 9 2 7 2 5 2 3 2 1 1 9 1 7 1 5 1 3 1 1 9 7 5 3 1 4 2 4 0 3 8 3 6 3 4 3 2 3 0 2 8 2 6 2 4 2 2 2 0 1 8 1 6 1 4 1 2 1 0 8 6 4 2 Channel4 Channel2 Channel3 Channel41 Channel1 FT RIGHT Channel42 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42 40...

Страница 4: ...ket Kit Acquisition and interconnection boards are mounted to the bracket at the factory Data Acquisition Board 11 375 289 mm 1 12 28 mm 5 75 146 mm Data Acquisition Board Mounting Bracket Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore ca ...

Страница 5: ...alues of each dip switch are as follows 1 1 2 2 3 4 4 8 5 16 6 32 7 64 8 128 To determine an address you simply add the values of any switch that is on For example Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32 8 32 40 See Chart 2 on the following page for a pictorial listing of the first 63 switch positions or H663 series can be addressed as any whole number between...

Страница 6: ...NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore ca ...

Страница 7: ...use 4 Replace with new fuse see specifications for fuse type 5 Reconnect 120V power source to Data Acquisition Board 6 Reconnect power 7 Check Alive LED for proper function See Figure 1 3 on page 2 for location 240VACforH663SM xxE Iffuseblowsrepeatedly checkpowersourcetoensurethatitisastable120VACsource Master NetworkDisplay Slave H663series TX SHLD TX RX TX RX TX TX SHLD TX RX TX RX TX SHIELD SHIE...

Страница 8: ...1 stop bit Termination 5 position depluggable connector Defaults Warning Register 60 of current sensor max configurable Alarm Register 70 of current sensor max configurable Breaker Size Register 20A Dimensions Circuit Board L x W 7 25 x 5 75 Split Core CT s 6 leads 1 04 x 1 04 x 1 58 Lithium Battery Life 5 years Replace with type CRF 1220 or equiv CAUTION DANGER OF EXPLOSION IF BATTERY IS INCORRECTL...

Отзывы: