Cabinet Instal lation
I-Ga te 4000 P R O Ins tall ation
5-8
Veraz Networks Inc. Proprietary
02041802-05
5.1.4. Connecting the ETSI Cabinet to an Overhead
Cable Run
The procedure below describes connecting an ETSI cabinet to an overhead cable
run.
To connect the ETSI cabinet to an overhead cable run:
1. Locate the cable run or runs under which you want to place the cabinets, and
verify that their location is appropriate for your needs.
2. Attach the upper bracket to the two support rods (see Figure 5-6). Use M8x30
screws, washers and lock washers. Do not tighten the screws completely.
3. Adjust the upper bracket until it comes in contact with the cable run.
4. Tighten the side screw.
5. Place the tightening bar on the inner side of the cable run as shown in Figure 5-6,
and tighten the top screws.
TOP SCREW M8X30
FLAT WASHER
LOCK WASHER
NUT M8
TIGHTENING BAR
CABLE RUN
UPPER BRACKET
Cabinet
SIDE
SCREW M8X30
SUPPORT ROD
Figure
5-6: Connecting the ETSI cabinet to an overhead cable run