PARAMETERS
RECOVERY RATE
Readout of control signal for the rotary heat regenerator or plate
cross-
fl
ow recuperator, range 0..100%
Recovery rate
0%
PARAMETERS
ROTARY REGEN.
State of the rotary heat regenerator
Recovery rate
- readout of control signal for the recovery unit,
range 0..100%
Frequency
– readout of actual output from the frequency
converter
Fault code
– status word read from the frequency converter
Note!
For detailed information on fault codes, refer to the
manual of the frequency converter.
Rotary regen.
Recovery rate
0%
Frequency
0.0Hz
Motor RPM
0 rpm
Fault code
0x00
PARAMETERS
MIXING RATE
Readout of the control signal for the mixing dampers, range
0..100% (corresponding to 0..10V hardware output)
Mixing rate
100%
5. SETTINGS
Settings is the part of the menu, where setpoints, limits, PI
parameters and other con
fi
gurable values are accessed.
SETTINGS
DEF. WORK MODE
De
fi
nes the default working mode for the calendar if none of the
settings matches current date and time. This could happen if
the “Calendar” operation will be selected as the operation mode
while the whole calendar was left blank.
▪
Stop (factory setting)
▪
Stage I
▪
Stage II
▪
Standby
Note!
In such case, the temperature setpoint is taken from the
general setpoint from the main menu.
Def. work mode
Standby
SETTINGS
STANDBY MODE
De
fi
nes the conditions for the “standby” functionality to be
activated.
Active for
– enables the standby function for different types of
heat exchangers
▪
None – standby function disabled
Standby mode
Active for
Heating/Cooling