Advanced manual
24
RRG FC / ...
– the same settings for frequency converter of the rotary energy regenerator
Response timeout
– setting for max waiting for a slave to respond. If the time was exceeded, the
error will be detected. It is recommended to not modify that parameter.
Factory setting: 0,3s
Comm break time
– setting for idle time on the communication line between sending next packets. It
is recommended to not modify that parameter.
Factory setting: 2,0s
SERVICE MENU
INPUT STATES
Digital inputs
– readout of the actual states of hardware digital inputs
▪
D1 – Opened / Closed
▪
D2 – Opened / Closed
▪
D3 – Opened / Closed
▪
D4 – Opened / Closed
Sensor inputs
– readout of actual values read by temperature sensors Pt1000
▪
P1
▪
P2
▪
P3
SERVICE MENU
OUTPUT STATES
Relay outputs
– readout of the actual states of hardware digital outputs
▪
REL1 – Off / On
▪
REL2 – Off / On
▪
REL3 – Off / On
Analog outputs
– readout of actual values sena to hardware analog outputs
▪
A1 – 0..10V
▪
A2 – 0..10V
SERVICE MENU
INPUT EMULATION
Digital inputs
– overwriting the states of hardware digital inputs
▪
D1 – None / Set opened / Set closed
▪
D2 – None / Set opened / Set closed
▪
D3 – None / Set opened / Set closed
▪
D4 – None / Set opened / Set closed
Sensor inputs
– overwriting the actual values read by temperature sensors Pt1000
▪
P1 emulate – Disabled / Enabled – select to activate the overwriting
▪
P1 temp. - enter the value
▪
P2 emulate – Disabled / Enabled – select to activate the overwriting
▪
P2 temp. - enter the value
▪
P3 emulate – Disabled / Enabled – select to activate the overwriting
▪
P3 temp. - enter the value