        Quick Setup 

           

VEM motors Thurm GmbH                                                    

Compact Drives Series M21 ... T

                  

10/2005

 

 

   

4

 

 

 
 
 

• 

Press START 

if there is a switch installed instead of the factory set bridge

 to start the 

drive in clockwise rotation or press START + REVERSING to start the drive in 
counterclockwise rotation. 

 

• 

Set reference to analog input: 

 

Use internal reference 10 V DC and a potentiometer (see fig. 2); 

or

 

Connect external reference 0 ... 10 V to terminal 2 . Use common (0 V) of terminal 
8; 

or

 

Set current 0 ... or 4 ... 20 mA of an external current source to terminal 1 against 
common (terminal 8) 

Enable terminal 1 by set-up parameter 331 and scaling via parameters 336 and 337 
by means of LCP2 or PC programming software 

 

 

What if the motor does not start? 

 

Make sure no parameters have been changed from initial delivery status (factory 
setting). Use the Local Control Panel or serial port to reset to factory setting.  

Make sure no [STOP]-command have been issued by the optional control panel 
keyboard (local stop). Control Panel [STOP] can only be restarted by the Control 
Panel [START]- button!  

Remove lid to check the Light Emitting Diodes visible through a hole in the 
inside isolation cover, follow Table below.  

 
  

Green 

 

Yellow

 

Red

 

Action

 

LED 302

 

LED 301

 

LED 300

   

OFF

 

OFF

 

OFF

 

Apply power 

 

ON 

OFF 

OFF

 

Apply start and reference signals 

 

ON

 

OFF

 

ON

 

Apply reset signal according to Fig. 2 

 

ON 

ON 

ON 

Switch off power until all LED's have turned 
off. After power on reset signal is required. 

 

 

   

 

• 

Press RESET pushbutton after power on 

(if necessary)

 

 

Drive starts in run mode

!

 

• 

Close lid and fasten screws 

 

 
 
 
 

 

The  manual  “Installation,  operating  and  maintenance  instructions  Three  phase 
asynchronous motors with squirrel cage rotor and slip ring rotor, standard design”, ID-No. 
VEM 68 238 01, is generally valid for Compact Drives, too. Please note that the indicated 
number of service hours is only valid for operation at the rated speed. If during operation 
of the motor the nominal speed is exeeded then the regreasing period reduces     
approximately in the opposite ratio to the increase in the motor speed. 
No. of switches of the mains: max. 1 every 2 minutes 
Environmental temperature: -10°C (at reduced load) … +40°C 
Environmental conditions: no direct exposure to sunlight because of overheating 

 