        Quick Setup 

           

VEM motors Thurm GmbH                                                    

Compact Drives Series M21 ... T

                  

10/2005

 

 

   

3

 

 

 
 
RS 485 switch  

 

For terminating an RS 485 interface serial communication,

 

the bus must be terminated by a 

resistor network at both ends. This is provided by setting both switches to ON. 
 

LEDs  

 

The Compact Drive has five LEDs which indicate the status of the Compact Drive: 
 
LED 300

 

red

 

Fault trip

 

LED 301

 

yellow

 

Warning

 

LED 302

 

green

 

Power on

 

LED 303-304

 

green

 

Communication

 

 

EMC-correct installation 

  

The control cables must be screened cables to ensure EMC-correct electrical installation. 
Connect the screen to earth at both ends. 
Avoid installation with twisted screen ends (pigtails), since this ruins the screening effect at high 
frequencies. Use cable clamps instead. 
 
 

2. 

Start the Compact Drive

 

 
Figure 2 shows the factory settings of terminal block X101 for starting the VEM Compact Drives 
without any additionally accessories for local or remote control. 
The steps of starting have to be kept! 
 

Fig. 2 

 

 

also usable as digital input (see Table B)

     

** 

also usable as digital output (see Table B) 

 

• 

Open the lid of the FC by releasing the screws

 

• 

Install RESET pushbutton 

between terminals 3 and 6

 

to clear any trip

 

• 

Connect

 

switch 

START 

 between terminals 4 and 6 to start the drive clockwise 

or

 switch  

START + REVERSING

 between terminals 5 and 6 to start the drive counterclockwise 

 

(in factory setting terminals 4 and 6 are bridged by a cable to start the drive clockwise at 
power-up with a speed refering to the reference at terminal 2) 

• 

Connect terminal 2, 7 and 8 to the potentiometer

 (see fig. 2).

 

• 

Connect mains terminals L1, L2, L3 and earth terminal. Switch on mains supply.

 

 

NB

 

!

     

The voltage on the Compact Drive is dangerous when the motor is connected 

to mains. Incorrect installation of the Compact Drive may lead to material damage or 
serious injury or it may be fatal. 

 

  

                     

 
RESET (pushbutton) 
START 
START + REVERSING 

 
 

Speed reference 

Terminals: 
 

1: Analog input 

2: Analog input * 

3: Digital input 

4: Digital input 

5: Digital input 

6: 24 V DC-supply 

7: 10 V DC-supply 

8: 0 V 

9: Analog output **

 

 