VDOT-ASD-100 Aspiration Detector                 

 

Velocity Detection

 

31 

VDOT-ASD-100 Aspirating Smoke Detector User’s Manual V1 

GPI-2 

I2. 

15 

2  0: NOT USED 

 

8:SENSITVITY MODE 1 

1: RESET   

 

9: SENSITIVITY MODE 2 

2: ISOLATE   

10: SCAN (VDOT-ASD-100-2000s Only) 

3: SILENCE   

11: UDI-1 

4: TEST 

 

 

12: UDI-2 

5: MAINS FAULT  13: UDI-3 

6: BATT. FAULT  14: UDI-4 

7: POWER FAULT  15: UDI-5 

GPI-3 

I3. 

15 

GPI-4 

I4. 

15 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 Device Relay 

Configuration 

Relay 1 

r1. 

1  This sets the termination board relays to below output: 

1: ISOLATE  2: FAULT   

3: ALERT 

4: ACTION   

5: FIRE 1   

6: FIRE 2 

7: AUXILIARY 

Note: Relay 2 is Normally Closed the others are Normally 

Open.   

DST 

Relay 2 

r2. 

Relay 3 

r3. 

Relay 4 

r4. 

Relay 5 

r5. 

Relay 6 

r6. 

Relay 7 

r7. 

11 Reserved 

 

 

 

 

  NA 

 

12 Device Relay 

Test 

Relay 1 

r1. 

N  When the selected relay is set to Y or N, the relay will be 

activated or de-activated to check if the relay connected 

device action is correct. For example, If relay 5 is fire 1 and 

connected to fire alarm system. Setting relay 5 to Y should 

have proper indications on the fire alarm panel.   

Setting All (All Relays) to Y, all relays will be activated. 

ADM

 

Relay 2 

r2. 

Relay 3 

r3. 

Relay 4 

r4. 

Relay 5 

r5. 

Relay 6 

r6. 

Relay 7 

r7. 

All 

AL.  N 

13 Reserved 

 

 

 

 

  NA 

 

14 Date & Time  YYYY/Year 

yy.  2000  2099  2010 It is important that the time and date be set up correctly on 

the controller’s internal calendar/clock because it uses this 

information to store events in the event log.

 

ADM 

MM/Month 

NN.  01 

12 

05 

DD/Day 

dd.  01 

31 

18 

HH/Hour 

HH.  01 

23 

19 

MM/Minute  nn.  00 

59 

36 

SS/Second 

SS.  00 

59 

15 System 

Address 

Ad.  1 

250  250  Setting the device RS485 address. A device must have a 

unique address on the network. 

ADM 

Factory 

Default 

dF.  N 

N  Setting the function to Y will restore the device to the factory 

default settings. However, the device address will not be 

affected to prevent from unwanted network error. 

DST 

 

Password 

PS.  N 

Y  When this function is set to Y it requires a password to enter 

the Program Mode and has the right to change settings. 

Setting this function to N it requires no password to enter the 

Program Mode and can only view the settings. 

Reference 

Detector 

Address 

rA. 

250 

0  Setting the reference detector address number between 1 and 

250 to enable referencing. When this function is set to 0 the 

referencing is disabled. 

Reference 

Zone 

rP. 

1  The zone (detector) number of above reference detector 

address. 

Reference 

Dilution 

rd. 

100  100  The value set with this function is the percentage reference 

signal subtracted from the detector’s signal, if a reference 

device has been allocated. 

Reference 

Delay 

rt. 

100 

0  This value is the delay time (in seconds) between a build up of 

pollution being seen by the reference (if used) and the 

pollution being seen by the detector. 

16 Log 

Smoke Log 

Enable 

SN.  N 

Y  Setting this function to Y enables the smoke/flow log. There 

are two selectable log modes, CHANGE and RATE. On VDOT-

ASD-100, 0 is CHAGNGE and 1 is RATE. When the log mode 

“CHANGE” is selected the following change function sets the 

ADM

 

Smoke Log 

Mode 

SL. 

Содержание VDOT-ASD-100

Страница 1: ...VDOT ASD 100 Aspirating Smoke Detector User s Manual...

Страница 2: ...Introduction 3 Features 3 Specification 5 Sampling Pipework Design 8 Considerations 8 Design Guidelines 11 Installation 14 Mechanical Installation 14 Electrical Installation 16 Front Panel 21 Control...

Страница 3: ...must be set to very sensitive and is closed to environment background smoke level This makes the system very easy to have unwanted or false alarms The prefer detection zone size of VDOT ASD 100 is on...

Страница 4: ...ay Outputs l 3 in 1 Control Display Programmer Front Panel l RS485 Network l Support Modbus RTU Open Protocol Note Maximum pipe length and maximum number of sampling holes cannot be achieved at the sa...

Страница 5: ...0m 18 holes 60m 25 holes Two Branch Pipes 2x80m 2x15 holes Four Branch Pipes 4x 60m 4x10 Holes EN54 20 Class B Maximum 60 holes totally Two Branch Pipes 2x60m 2x25 holes Four Branch Pipes 4x 60m 4x15...

Страница 6: ...Fault Adjustable Flow Detection Sensitivity Adjustable Flow Fault Threshold Relay Output 7 Relays on Termination Board Configurable Rating 2A 30 VDC General Purpose Inputs 4xGPIs Configurable GPI Func...

Страница 7: ...ector Airflow System Auxiliary Isolated indicator Beeper Programmer Access Password Controlled Bargraph and 6 digits 7 Numerical LEDs display the function Func buttons to change settings Event Logs Nu...

Страница 8: ...int of supply or extract its system sensitivity may be directly related as equal to the sensitivity of the central detector due to the cumulative effect In the case of a system monitoring more than on...

Страница 9: ...from a protected area should not exceed 120 seconds 2 minutes Transport times in excess of this must be the subject of a variation Shorter maximum transport times may be desirable in certain applicat...

Страница 10: ...VDOT ASD 100 Aspiration Detector Velocity Detection 10 VDOT ASD 100 Aspirating Smoke Detector User s Manual V1 Two branch system Four branch system...

Страница 11: ...D 21mm Other sizes will often work but will provide different response times l Maximum pipework limitation The limitation of each pipe inlet of VDOT ASD 100 when the aspirator speed set to 10 is 100m...

Страница 12: ...ity are within desired limits l System Sensitivity The recommended maximum number of sampling holes on the pipework to achieve desired relative sampling hole sensitivity is as follows Class A 40 holes...

Страница 13: ...VDOT ASD 100 Aspiration Detector Velocity Detection 13 VDOT ASD 100 Aspirating Smoke Detector User s Manual V1 Typical VDOT ASD 100 Pipework Configurations Two Branch Pipe Four Branch Pipe...

Страница 14: ...rried out by suitably experienced and trained personnel Mechanical Installation Dimensions l The mounting holes in each corner are used to mount the device on the wall It is recommended the device is...

Страница 15: ...ded to open the entry holes Sampling pipes Sampling pipes should be made from a non hazardous material and should be clearly identified Typical sampling pipes used in air sampling systems are ABS uPVC...

Страница 16: ...l the electrical connections should be made to the removable connectors on the termination board or the relay board if it equipped Cables Power cable should be 2 0mm2 2C of sufficient current carrying...

Страница 17: ...s Two 24Vdc power terminals on the termination board One must be connected to a 24 20 19 6 28 8 DC Power Supply The device may be powered by any EN54 4 compliant monitored 24DC power supply of suffici...

Страница 18: ...Isolate and Auxiliary The relay output function printed on the termination board is the factory default setting Users can change the relay function using front panel display or the Management compute...

Страница 19: ...evel is usually higher than the non working hours Sometimes outside pollutants go into the detection area can generate false alarm There are needs to decrease the sensitivity to prevent the false alar...

Страница 20: ...or another 1 2km l RS 485 Network can be configured in closed loop for better communication reliability The communication can switch direction to communicate with devices behind the failure point when...

Страница 21: ...Detector User s Manual V1 Front Panel The VDOT ASD 100 front panel is a Control Display Programmer 3 in 1 LED display Bargraph LED 20 segments Power Indicator Isolate Indicator 6 digits Numerical Dis...

Страница 22: ...f there s any malfunction LED The difference of SILENCE and ISOLATE is that SILENCE is used to silence beeper confirming the alarm or fault status When there is a new alarm or fault in occurrence the...

Страница 23: ...ult Latch function is enabled A manual reset will be needed to clear the alarm or fault o 6 digits Numerical LED In normal operation the 6 digit numerical LED displays real time smoke level airflow le...

Страница 24: ...nction is airflow related parameters ON In executing flow normalization Flashing ADDR Display the RS485 address of the device ON AUX Display code of current event and code ON Display Item Numerical LE...

Страница 25: ...Sensor 4 High Alarm A12 Sensor 4 Low Alarm High High Alarm A13 Sensor 5 High Alarm A14 Sensor 5 Low Alarm High High Alarm Smoke Detection Fault E1 Smoke Detector Failed E2 Smoke Detector Service Requ...

Страница 26: ...ecute REST ISOLATE SILENCE TEST function as well as to display the figure of Smoke Flow Addr Evt by numerical tube while in setting mode the setting of related operating parameters of detecting device...

Страница 27: ...ion u Bargraph grid represents parameter no ex Enter parameter 15 will lead 15th Bargraph grid starts to flash Enter parameter 21 will lead 20th and 01 Bargraph grid in flashing the rest may be deduce...

Страница 28: ...0 Aspiration Detector Velocity Detection 28 VDOT ASD 100 Aspirating Smoke Detector User s Manual V1 SILENCE Press and hold for 2 sec Save setting the numerical LED will flashes 3 times if successfully...

Страница 29: ...xpired The detector will generate Fire 2 Alarm 2 Time Delay Alert Delay t1 0 60 30 The alarm delay is the number of seconds that an alarm level has to be continuously sensed before the alarm is initia...

Страница 30: ...This is the factory default setting When this function is set to N the alarm will be reset automatically when the smoke level is decreased below alarm threshold Fault Latch FL N Y N When this functio...

Страница 31: ...store events in the event log ADM MM Month NN 01 12 05 DD Day dd 01 31 18 HH Hour HH 01 23 19 MM Minute nn 00 59 36 SS Second SS 00 59 0 15 System Address Ad 1 250 250 Setting the device RS485 address...

Страница 32: ...e this value to the original smoke alarm thresholds when relevant GPI is activated This setting must work with the GPI which is set to Sensitivity Mode 1 or 2 If this function value is set to be great...

Страница 33: ...s of background particulate matter testing methodology would be similar to that of standard point detectors Commissioning Check List The following brief checklist allows quick setup of the detector Th...

Страница 34: ...network can be synchronized by the Management System Software at the same time 2 Set the time delays temporarily to 0 second when testing the transport time is appropriate to eliminate the alarm dela...

Страница 35: ...f the detector as shown Untighten the screw in the middle of the filter to remove the filter Fit a new filter make sure to push the filter fully home and tighten the screw When the replacement filter...

Страница 36: ...nput voltage using a meter to make sure the power is within normal range o Check the Device Display a Press the Test button if it s enabled to check if all the LEDs on the display illuminates normally...

Страница 37: ...e g CIE BMS a Activate the fire relays in the relay test menu or introduce smoke to put the detector into alarms to check if there s associate alarm generated on the fire alarm panel if it s connected...

Страница 38: ...system a sampling pipe must be removed from the pipe inlet and introduce high airflow providing by a compressor into the sampling pipe to blow off the dust in the pipework and the sampling holes Alter...

Страница 39: ...ector Velocity Detection 39 VDOT ASD 100 Aspirating Smoke Detector User s Manual V1 Velocity Detection Address Detection House 72 78 Morfa Road Swansea SA1 2EN UK Email sales Velocitydetection com htt...

Отзывы: