VDOT-ASD-100 Aspiration Detector
Velocity Detection
31
VDOT-ASD-100 Aspirating Smoke Detector User’s Manual V1
GPI-2
I2.
0
15
2 0: NOT USED
8:SENSITVITY MODE 1
1: RESET
9: SENSITIVITY MODE 2
2: ISOLATE
10: SCAN (VDOT-ASD-100-2000s Only)
3: SILENCE
11: UDI-1
4: TEST
12: UDI-2
5: MAINS FAULT 13: UDI-3
6: BATT. FAULT 14: UDI-4
7: POWER FAULT 15: UDI-5
GPI-3
I3.
0
15
5
GPI-4
I4.
0
15
6
10 Device Relay
Configuration
Relay 1
r1.
1
7
1 This sets the termination board relays to below output:
1: ISOLATE 2: FAULT
3: ALERT
4: ACTION
5: FIRE 1
6: FIRE 2
7: AUXILIARY
Note: Relay 2 is Normally Closed the others are Normally
Open.
DST
Relay 2
r2.
2
2
2
Relay 3
r3.
1
7
3
Relay 4
r4.
1
7
4
Relay 5
r5.
1
7
5
Relay 6
r6.
1
7
6
Relay 7
r7.
1
7
7
11 Reserved
NA
12 Device Relay
Test
Relay 1
r1.
N
Y
N When the selected relay is set to Y or N, the relay will be
activated or de-activated to check if the relay connected
device action is correct. For example, If relay 5 is fire 1 and
connected to fire alarm system. Setting relay 5 to Y should
have proper indications on the fire alarm panel.
Setting All (All Relays) to Y, all relays will be activated.
ADM
Relay 2
r2.
N
Y
N
Relay 3
r3.
N
Y
N
Relay 4
r4.
N
Y
N
Relay 5
r5.
N
Y
N
Relay 6
r6.
N
Y
N
Relay 7
r7.
N
Y
N
All
AL. N
Y
N
13 Reserved
NA
14 Date & Time YYYY/Year
yy. 2000 2099 2010 It is important that the time and date be set up correctly on
the controller’s internal calendar/clock because it uses this
information to store events in the event log.
ADM
MM/Month
NN. 01
12
05
DD/Day
dd. 01
31
18
HH/Hour
HH. 01
23
19
MM/Minute nn. 00
59
36
SS/Second
SS. 00
59
0
15 System
Address
Ad. 1
250 250 Setting the device RS485 address. A device must have a
unique address on the network.
ADM
Factory
Default
dF. N
Y
N Setting the function to Y will restore the device to the factory
default settings. However, the device address will not be
affected to prevent from unwanted network error.
DST
Password
PS. N
Y
Y When this function is set to Y it requires a password to enter
the Program Mode and has the right to change settings.
Setting this function to N it requires no password to enter the
Program Mode and can only view the settings.
Reference
Detector
Address
rA.
0
250
0 Setting the reference detector address number between 1 and
250 to enable referencing. When this function is set to 0 the
referencing is disabled.
Reference
Zone
rP.
1
8
1 The zone (detector) number of above reference detector
address.
Reference
Dilution
rd.
1
100 100 The value set with this function is the percentage reference
signal subtracted from the detector’s signal, if a reference
device has been allocated.
Reference
Delay
rt.
0
100
0 This value is the delay time (in seconds) between a build up of
pollution being seen by the reference (if used) and the
pollution being seen by the detector.
16 Log
Smoke Log
Enable
SN. N
Y
Y Setting this function to Y enables the smoke/flow log. There
are two selectable log modes, CHANGE and RATE. On VDOT-
ASD-100, 0 is CHAGNGE and 1 is RATE. When the log mode
“CHANGE” is selected the following change function sets the
ADM
Smoke Log
Mode
SL.
0
1
0