VDOT-ASD-100 Aspiration Detector
Velocity Detection
25
VDOT-ASD-100 Aspirating Smoke Detector User’s Manual V1
o
Beeper
There are the following beeper modes that the beep frequency is different when the device
is in alarm or fault status. Users can change the beeper mode according to their application.
o
Event code
Types
Code
Description
Smoke
Alarm
A1
Alert
A2
Action
A3
Fire 1
A4
Fire 2
Auxiliary
Sensor
Alarm
A5
Sensor 1 High Alarm
A6
Sensor 1 Low Alarm/High High Alarm
A7
Sensor 2 High Alarm
A8
Sensor 2 Low Alarm/High High Alarm
A9
Sensor 3 High Alarm
A10
Sensor 3 Low Alarm/High High Alarm
A11
Sensor 4 High Alarm
A12
Sensor 4 Low Alarm/High High Alarm
A13
Sensor 5 High Alarm
A14
Sensor 5 Low Alarm/High High Alarm
Smoke
Detection
Fault
E1
Smoke Detector Failed
E2
Smoke Detector Service Required
E3
Smoke Level High
E4
Smoke Level Low
Flow Fault
E5
Aspirator Failed
E6
Flow Sensor Failed
E7
Pipe Flow High Fault
E8
Pipe Flow Low Fault
E9
Normalization Failed
E17
Filter Blockage
E18
Filter Removed
E19
Filter Due
Comms.
Fault
E10
Programmer Not Found
E11
Fan Board Not Found
E12
Zone Relay Board Not Found
Mode
Beeper action
0
Disable the beeper.
1
In alarm, it beeps 1 second in every 10 seconds. In fault, no beep.
2
In alarm or fault, it beeps 1 second in every 10 seconds.
3
In alarm, it beeps continuously. In fault, it beeps 1 second in every 10 seconds.
4
In alarm or fault, it beeps continuously.