SPECIFICATIONS

Electrical Characteristics

External Supply Voltage 

18 – 30 VDC

Remote Reset Time 

External monitor must be pulled low 

 

for a minimum of 100 msec

Power Reset 

1 sec

Average Operating Current @24V* 

Fan High – 200mA, 4.8W at 24V

 

Fan Med – 151mA, 3.7W at 24V

 

Fan Low – 120mA, 2.9W at 24V

Alarm Current @24V* 

Fan High – 230mA, 5.6W at 24V

 

Fan Med – 172mA, 4.2W at 24V

 

Fan Low – 142mA, 3.5W at 24V

*Additional Current Requirements 

LCD on - 10mA, 0.24W at 24V

 

Ethernet enabled - 20mA, 0.48W at 24V

 

Serial Modbus enabled - 0.48V at 24V

 

Audible Indicator activated - 20mA, 0.48W at 24V

Relay Contact Ratings 

3.0A @ 30VDC, 0.5A @125VAC

Environmental Ratings

Operating Temperature 

32°F (0°C) to 100°F (38°C)

 

Factory tested to 131°F (55°C)

Sampled Air Temperature 

-4°F (-20°C) to 140°F (160°C)

Humidity 

10 to 95% non-condensing

IP Rating 

IP30

Coverage Area 

5,000 sq.ft. (464 sq.m.)

Ambient Air Movement 

0 – 4,000 ft/min (0 – 1,219.2 m/min)

FAAST XS 7100X
Fire Alarm Aspiration Sensing Technology

®

COMPREHENSIVE USER GUIDE

Exterior Dimensions

Height 

11.0 in (279mm)

Width 

9.0 in (229mm)

Depth 

6.25 in (15.9mm)

Cable Access 

3 1-inch (2.54 cm)

 

cable entry holes on top

 

and back of the unit.

Wire Gauge 

12 Ga.

Pipe Size 

½ or ¾ in Nom.

 

(20 or 25mm Nom.)

Max Single Pipe Length 

180 ft. (54.8 m)

 *

 

all designs must be 
verified within PipeIQ 
software

Shipping Weight 

8.8 lbs (3.99 kg)

Net Weight 

6.57 lbs (2.98 kg)

 

1 ASUG80001

TABLE OF CONTENTS 

Items Included With Unit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Connecting to FAAST XS (7100X)   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Connecting to FAAST XS via USB  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Connecting to FAAST XS via Ethernet  . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Pipe Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Physical Unit Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Wiring 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

User Interface   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Particulate Level Display   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Alarm Level Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Air Flow Display  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fault Display  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LCD User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Configuration Menu Screen   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
LCD Menu Screen   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Language Screen  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Backlight Screen   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Contrast Screen  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Message Log Screen  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Set Time Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Special mode screens  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Initialization Screen  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Baselining Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Firmware Upgrade Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Modes of Operation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Initialization  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Configuration Overview  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Fan Speed Configuration   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Alarm and Relay Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Audible Indicator Configuration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Failure of Configuration validation   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power glitch during configuration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Normal 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Test 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Sounder Test  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Reset 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Reset Airflow Baselines   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Isolation 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Disable Mode   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Acclimate Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Day, Night And Weekend Mode   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Logs 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Event Log    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Data Trend Log   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Message Log  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
EXSernal Monitor/Reset  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Ethernet Connection   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
USB Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Pipe Network   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Web Server    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Email Notification  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Canned Smoke Testing  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Laser Safety Information   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Warranty  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
FCC Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Содержание XS 7100X

Страница 1: ...Length 180 ft 54 8 m all designs must be verified within PipeIQ software Shipping Weight 8 8 lbs 3 99 kg Net Weight 6 57 lbs 2 98 kg 1 ASUG80001 TABLE OF CONTENTS Items Included With Unit 2 Connectin...

Страница 2: ...tructions USB interface cable PipeIQ software comprehensive manual and other helpful documents are available at systemsensor com faast CONNECTING TO FAAST XS FAAST XS requires a valid configuration fr...

Страница 3: ...orm the following procedure to mount the unit 1 Before installing the unit onto the bracket remove the appropriate con duit caps from the top or left side of the unit to match the orientation of the w...

Страница 4: ...XT MONITOR T8 MODBUS Rx G Rx T9 MODBUS Tx G Tx T10 UNUSED T1 POWER T2 FIRE 2 NC COM NO T3 FIRE 1 NC COM NO T4 ALERT NC COM NO FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS AS...

Страница 5: ...the following information Detector status Normal Alarm General Fault Isolate Fault Disable Fault Voltage Fault Alarm Level Alert Fire 1 Fire 2 Particulate Level 1 10 relative to Alert Flow level LCD...

Страница 6: ...Ds on the right side of the user interface and also on the LCD screen The four Fault LEDs are Fault Isolate Disable Low Voltage 6 ASUG80001 If the General Fault LED is ON the fault condition will be s...

Страница 7: ...ME SCREEN 23 JUN 14 10 04AM System Normal 0 0000 ft Menu The menu option is available from the home screen Pressing the select but ton will enter the main menu screen If the device s sounder is active...

Страница 8: ...fault or alarm 3 7 RESET The Reset function will reset the device When this function is selected from the functions menu the device will ask for confirmation Use the scroll keys to select cancel or ok...

Страница 9: ...ace located in the wiring cabinet of the device The device will validate the configuration before the configuration be comes active After validation of the data the device will perform an initializa t...

Страница 10: ...els 10 ASUG80001 for others Table 6 shows the various levels that are available Each Acclimate level is also able to be monitored in PipeIQ This allows the user to read the current Acclimated alarm le...

Страница 11: ...TING All FAAST XS systems must be tested after installation and periodically there after Testing methods must statisfy the authority having jurisdiction Systems offer maximum performance when tested a...

Страница 12: ...e limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing...