FIGURE 5. USER INTERFACE DISPLAY
FIGURE 6. PARTICULATE LEVEL DISPLAY
ASP118-00
ASP130-00
SYSTEM POWERING
The following procedure describes how to initially power up the FAAST XS system.
1. Unplug the unit’s power connector to the unit before turning on the
power.
2. Turn on the power.
3. Check the voltage at the connector. Make sure it is within the required
voltage range.
4. If the voltage is within the proper range, reconnect the power connec-
tor to the unit.
5. Connect a computer, with PipeIQ installed, to the unit using either the
USB or the Ethernet port located in the left side wiring door. (See the
‘Connecting to FAAST XS’ for detailed connection instructions.)
6. Use the PipeIQ software to set up the unit configuration required for
the particular application.
7. The PC may now be disconnected unless a permanent networked con-
nection is desired.
8. Verify the system fan starts up and air begins to flow out of the ex-
haust port. The user interface will provide the device status.
9. The device will establish an airflow baseline during the first five min-
utes of operation. After five minutes, the airflow level display will
provide the true measured airflow status. The device will give visual
indication of the baselining period on the LCD screen.
USER INTERFACE
The user interface, shown in Figure 5, provides the following information:
• Detector status: Normal, Alarm, General Fault, Isolate Fault, Disable
Fault, Voltage Fault
• Alarm Level: Alert, Fire 1, Fire 2
• Particulate Level: 1 – 10 relative to Alert
• Flow level
• LCD for device test, service, and monitoring.
5 ASUG80001
PARTICULATE LEVEL DISPLAY
The particulate level display, shown in Figure 6, consists of ten amber LEDs
that correspond to the current level of the particulate level detected. The LEDs
illuminate in order from Level 1 to Level 10, starting from the bottom of the
display and moving up as the particulate level increases. Each LED represents
a 10 percent increment in the particulate level relative to the Alert level.
ALARM LEVEL DISPLAY
The alarm level display consists of three red LEDs whose illumination corre-
sponds to the current alarm level, shown in Figure 7. These LEDs are located
directly above the particulate level LEDs. They illuminate sequentially upward
as the severity of the alarm increases. These alarm levels are configured at
default levels when shipped. They may be modified using the PipeIQ software.
Each of these alarm levels controls a set of form C relay contacts. When an
alarm level threshold has been crossed, the corresponding Alarm LED illumi-
nates and the relay activates after the Alarm Delay period has elapsed. These
alarm thresholds and associated relay outputs can be configured for either
latching or non-latching operation. Each Alarm output has a configurable de-
FIGURE 7. ALARM LEVEL DISPLAY
ASP119-01
FIRE 2
FIRE 1
ALERT