120 seconds by the PipeIQ software. Refer to local agency requirements and 
PipeIQ software for proper configuration.

WEB SERVER

The FAAST system contains an integrated Web server which is used to ob-
serve detector configuration and may be used to remotely monitor the unit.

The Web server features include:

•  Intuitive interface for remote monitoring of faults, relays, particulate 

level, air flow, and power supply

•  Facility location and contact information

•  Configuration settings display

•  Multi-Lingual support

•  Event log viewer

EMAIL NOTIFICATION

The FAAST system has the ability to send e-mail notifications to an individual 
or organization. Up to 6 different email addresses may be stored for notifica-
tion. Each email address can be configured to be notified of a specific alarm 
level, fault level or isolate condition through the PipeIQ software. E-mails from 
the device indicate a device’s ID, location and alarm or fault type. A com-
prehensive networking guide may be downloaded at systemsensor.com/faast.

CANNED SMOKE TESTING

All FAAST XS systems must be tested after installation and periodically there-
after. Testing methods must statisfy the authority having jurisdiction. Systems 
offer maximum performance when tested and maintained in compliance with 
NFPA 72. UL Tested and approved aerosol smoke products are listed in Table 7.

TABLE 7. CANNED SMOKE TESTING

UL 

LISTED

COMPANY

AEROSOL 

Home Safeguard

25S

SDI LLC

CHEK02, CHEK06

SOLOA3

SMOKE SABRE-01

MAINTENANCE

The only periodic maintenance required is to replace the filter assembly when 
the filter light is illuminated. Perform the following procedure to replace the 
filter assembly.

 

1. Remove power from the device or system.

 

2. Open the door that covers the User Interface LED indicators.

 

3. Remove the plastic name card over the LEDs.

 

4. Remove the two screws holding the filter assembly into the device.

 

5. Remove the filter assembly and replace it with a new assembly.

 

6.  Torque the two philips head screws to 6in-lb (0.7 N-M) or ¼ turn past 

“lightly snug.” DO NOT OVERTIGHTEN

 

7. Replace the plastic name card over the LEDs.

 

8. Close the door and apply power to the device or system.

Other system checks may need to be performed in accordance with local or 
national codes and regulations.

 11 ASUG80001

Содержание XS 7100X

Страница 1: ...Length 180 ft 54 8 m all designs must be verified within PipeIQ software Shipping Weight 8 8 lbs 3 99 kg Net Weight 6 57 lbs 2 98 kg 1 ASUG80001 TABLE OF CONTENTS Items Included With Unit 2 Connectin...

Страница 2: ...tructions USB interface cable PipeIQ software comprehensive manual and other helpful documents are available at systemsensor com faast CONNECTING TO FAAST XS FAAST XS requires a valid configuration fr...

Страница 3: ...orm the following procedure to mount the unit 1 Before installing the unit onto the bracket remove the appropriate con duit caps from the top or left side of the unit to match the orientation of the w...

Страница 4: ...XT MONITOR T8 MODBUS Rx G Rx T9 MODBUS Tx G Tx T10 UNUSED T1 POWER T2 FIRE 2 NC COM NO T3 FIRE 1 NC COM NO T4 ALERT NC COM NO FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS AS...

Страница 5: ...the following information Detector status Normal Alarm General Fault Isolate Fault Disable Fault Voltage Fault Alarm Level Alert Fire 1 Fire 2 Particulate Level 1 10 relative to Alert Flow level LCD...

Страница 6: ...Ds on the right side of the user interface and also on the LCD screen The four Fault LEDs are Fault Isolate Disable Low Voltage 6 ASUG80001 If the General Fault LED is ON the fault condition will be s...

Страница 7: ...ME SCREEN 23 JUN 14 10 04AM System Normal 0 0000 ft Menu The menu option is available from the home screen Pressing the select but ton will enter the main menu screen If the device s sounder is active...

Страница 8: ...fault or alarm 3 7 RESET The Reset function will reset the device When this function is selected from the functions menu the device will ask for confirmation Use the scroll keys to select cancel or ok...

Страница 9: ...ace located in the wiring cabinet of the device The device will validate the configuration before the configuration be comes active After validation of the data the device will perform an initializa t...

Страница 10: ...els 10 ASUG80001 for others Table 6 shows the various levels that are available Each Acclimate level is also able to be monitored in PipeIQ This allows the user to read the current Acclimated alarm le...

Страница 11: ...TING All FAAST XS systems must be tested after installation and periodically there after Testing methods must statisfy the authority having jurisdiction Systems offer maximum performance when tested a...

Страница 12: ...e limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing...

Отзывы: