FIGURE 8. AIR FLOW INDICATION

FIGURE 9. FAULT DISPLAY 

ASP122-00

ASP120-00

lay from 0 to 60 seconds. 

AIR FLOW DISPLAY

The FAAST XS system uses ultrasonic airflow sensing and displays the status in 
real time on the user interface. The air flow display consists of 10 green LEDs at 
the bottom of the device to display current flow balance as shown in Figure 8. 

The green segments on the air flow pendulum indicate how close the current 
air flow is to a high or low fault threshold. The default threshold for a fault 
condition is + or – 20% from airflow baseline. This fault threshold is configu-
rable using the PipeIQ software. During normal operation two adjacent indica-
tors are green and correspond to the current air flow entering the detector for 
the inlet being displayed. When air flow is balanced, these two indicators will 
be centered in the pendulum. As air flow increases or decreases, the indicators 
will move to the left in the case of a low flow condition, or right in the case of 
a high flow condition. A flow fault occurs when the flow boundary threshold 
has been exceeded longer than the flow fault delay period. The fault relay will 
be set when this occurs.

Detailed air flow information can also be read by accessing the ‘Air Flow’ 

menu in the device’s LCD display.

FAULT DISPLAY

The FAAST XS user interface displays faults in two ways, through amber LEDs 
on the right side of the user interface, and also on the LCD screen. The four 
Fault LEDs are:

Fault

Isolate

Disable

Low Voltage

 

6 ASUG80001

If the General Fault LED is ON, the fault condition will be shown on the LCD 
display under the Active Faults menu. The possible fault conditions are:

TYPE

DESCRIPTION

ACTIVATED RELAY

Low Flow Fault

Device air flow below the 
boundary and delay programed 
by the user.

Fault

Configuration

Configuration of device with 
configuration software has 
failed.

Fault

Device was interrupted with a 
power loss during configura-
tion. A Reset will clear this 
fault and device will revert 
back to it’s last good configu-
ration.

Fault

Device is new and has not 
been configured.

Fault

Device has corrupt configura-
tion and is unable to operate.

Fault

Drift Blue Fault

Device blue signal has reached 
the long term drift limit.

Fault

IR Laser Drift Fault Device IR Laser signal has 

reached the long term drift 
limit.

Fault

Sensor Fault

Device sensor is not work-
ing and requires immediate 
replacement

Fault

External Monitor 
Fault

External monitor detects open. Fault

Time Fault

Internal Time needs updating. Fault

Aspirator Fault

Indicates the fan has stopped 
working and requires immedi-
ate attention.

Fault

Filter Fault

Device filter is clogged and 
requires replacement

Fault

Disable Fault

Device has been put in disable 
mode.

Isolate

Isolation Fault

Device has been put in isolate 
mode.

Isolate

High Flow Fault

Device air flow above the 
boundary and delay pro-
gramed by the user.

Fault

Low Voltage Fault

Device Input voltage is low 

Fault

Содержание XS 7100X

Страница 1: ...Length 180 ft 54 8 m all designs must be verified within PipeIQ software Shipping Weight 8 8 lbs 3 99 kg Net Weight 6 57 lbs 2 98 kg 1 ASUG80001 TABLE OF CONTENTS Items Included With Unit 2 Connectin...

Страница 2: ...tructions USB interface cable PipeIQ software comprehensive manual and other helpful documents are available at systemsensor com faast CONNECTING TO FAAST XS FAAST XS requires a valid configuration fr...

Страница 3: ...orm the following procedure to mount the unit 1 Before installing the unit onto the bracket remove the appropriate con duit caps from the top or left side of the unit to match the orientation of the w...

Страница 4: ...XT MONITOR T8 MODBUS Rx G Rx T9 MODBUS Tx G Tx T10 UNUSED T1 POWER T2 FIRE 2 NC COM NO T3 FIRE 1 NC COM NO T4 ALERT NC COM NO FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS AS...

Страница 5: ...the following information Detector status Normal Alarm General Fault Isolate Fault Disable Fault Voltage Fault Alarm Level Alert Fire 1 Fire 2 Particulate Level 1 10 relative to Alert Flow level LCD...

Страница 6: ...Ds on the right side of the user interface and also on the LCD screen The four Fault LEDs are Fault Isolate Disable Low Voltage 6 ASUG80001 If the General Fault LED is ON the fault condition will be s...

Страница 7: ...ME SCREEN 23 JUN 14 10 04AM System Normal 0 0000 ft Menu The menu option is available from the home screen Pressing the select but ton will enter the main menu screen If the device s sounder is active...

Страница 8: ...fault or alarm 3 7 RESET The Reset function will reset the device When this function is selected from the functions menu the device will ask for confirmation Use the scroll keys to select cancel or ok...

Страница 9: ...ace located in the wiring cabinet of the device The device will validate the configuration before the configuration be comes active After validation of the data the device will perform an initializa t...

Страница 10: ...els 10 ASUG80001 for others Table 6 shows the various levels that are available Each Acclimate level is also able to be monitored in PipeIQ This allows the user to read the current Acclimated alarm le...

Страница 11: ...TING All FAAST XS systems must be tested after installation and periodically there after Testing methods must statisfy the authority having jurisdiction Systems offer maximum performance when tested a...

Страница 12: ...e limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing...

Отзывы: