VDOT-ASD-100 Aspiration Detector
Velocity Detection
23
VDOT-ASD-100 Aspirating Smoke Detector User’s Manual V1
ACTION (red)
When the Action Threshold has been reached and the appropriate
time delays have expired. The detector will generate Action Alarm.
FIRE 1 (red)
When the Fire 1 Threshold has been reached and the appropriate
time delays have expired. The detector will generate Fire 1 Alarm.
FIRE 2 (red)
When the Fire 2 Threshold has been reached and the appropriate
time delays have expired. The detector will generate Fire 2 Alarm.
DET’N (yellow)
Smoke detection fault
FLOW (yellow)
Airflow Hi/Lo fault, air flow sensor fail, aspirator fail
SYSTEM (yellow) Except DET’N/FLOW error, all other error is SYSTEM error
AUX (yellow)
Any one of the GPI points on terminal board is in action
Bargraph
(yellow)
Display the real-time smoke level, with full scale of Fire 1 Level
In program mode, individual bargraph LED flashing indicates current
parameter no.
Note: The status of the alarm and fault LEDs might not represent current device status. This
is because the alarm/fault output will be maintained even when the alarm/fault condition no
longer exist if the Alarm Latch or Fault Latch function is enabled. A manual reset will be
needed to clear the alarm or fault.
o
6-digits Numerical LED
In normal operation, the 6-digit numerical LED displays real-time smoke level, airflow level,
device address and current event in occurrence. Press
v
w
buttons on panel could switch
the display item in sequence as follows:
Smoke(S)
D
Flow(F)
D
Address (Addr)
D
Auxiliary (Aux)
The 4 indication LEDs above the numerical display indicates which item is displayed. Press
w
key to switch rightward; press
v
key to switch leftward.
When switching to Aux, the total number of active events will be displayed first. Press
<+>
、
<-> key will show the detail event message, including date, time and event code. For
example, if there are two events: code A0 and E11 exist, it displays 2 when switching to Aux;
press <+> will display A0 event message, press <+> again will display E11 event message, and
then press <+> to return to the beginning 2. Where, 2 represented total events, A0 is the
most updated event, and E11 is the previous event. If <-> is pressed, it will show the event
Fire 2
Smoke
Flow
Addr
Evt
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
OK
Isol.
FUNC.
MODE
SCAN
ISOL. SILENCE
TEST
+
-
Fire 1
ACTION
ALERT
DET'N
FLOW
SYSTEM
AUX
RESET
Mode for selection
6-digit numerical tube
Numerical display of status
Smoke concentration
indicator
In 20-level
Fault indicator
Normal indicators
Isolated indicators
Warning Indicator
Function keys in control