background image

 

VDOT-ASD-100 Aspiration Detector                 

 

Velocity Detection

 

33 

VDOT-ASD-100 Aspirating Smoke Detector User’s Manual V1 

Commissioning 

Before commissioning the detector, the local standards of aspirating detection systems must 
be consulted. These standards differ widely throughout the world and specific advice for the 
market in one country may not be applicable to another. 
Commissioning strategy will initially depend upon the environment in which the detector is 
installed. For instance, the test for a computer room (which should be a relatively clean 
environment) would be very different from, say, a tobacco factory, which would probably 
have a high level of airborne particulate content. 
A widely accepted standard for computer rooms/IDC areas is British Standard BS6266 and 
also the NFPA 76, equipment overheating at a stage well before combustion. To perform the 
test electrically overload a 1-meter length of PVC insulated wire of 10/0.1mm gauge for one 
minute using an appropriate power supply. The detector has two minutes from the end of 
the wire burn to give an alarm indication. 
For areas with higher levels of background particulate matter testing methodology would be 
similar to that of standard point detectors. 
 

Commissioning Check List 

The following brief checklist allows quick setup of the detector. This procedure will be 
adequate for most standard installations. 

o

 

Before powering up the detector, visually check all cabling to ensure correct 
connection. If wire identification is not immediately clear (e.g. by use of different 
colored wires or wire identification sleeves) an electrical check should be made. Any 
damage caused by misconnection of the detector is not covered by warranty. 

o

 

Power up the unit and enter the engineering access code.   

o

 

Enter the Setup menu and verify that the time and date are correct.   

o

 

Set the appropriate alarm levels and time delays for the protected environment. 

o

 

Modify necessary settings in your application and exit program mode. 

o

 

Introduce smoke to every pipe end to make sure the maximum transport time is within 
specification. Typical maximum transport time per NFPA 72 is 120 seconds. Other 
transport time requirement should be specified considered in the design stage. 

o

 

Perform any necessary smoke tests, like Hot Wire performance test or Potassium 
Chlorate / Lactose performance test, ensuring that the detector reacts appropriately, 
and let the smoke fully dissipate. 

 

Содержание VDOT-ASD-100

Страница 1: ...VDOT ASD 100 Aspirating Smoke Detector User s Manual...

Страница 2: ...Introduction 3 Features 3 Specification 5 Sampling Pipework Design 8 Considerations 8 Design Guidelines 11 Installation 14 Mechanical Installation 14 Electrical Installation 16 Front Panel 21 Control...

Страница 3: ...must be set to very sensitive and is closed to environment background smoke level This makes the system very easy to have unwanted or false alarms The prefer detection zone size of VDOT ASD 100 is on...

Страница 4: ...ay Outputs l 3 in 1 Control Display Programmer Front Panel l RS485 Network l Support Modbus RTU Open Protocol Note Maximum pipe length and maximum number of sampling holes cannot be achieved at the sa...

Страница 5: ...0m 18 holes 60m 25 holes Two Branch Pipes 2x80m 2x15 holes Four Branch Pipes 4x 60m 4x10 Holes EN54 20 Class B Maximum 60 holes totally Two Branch Pipes 2x60m 2x25 holes Four Branch Pipes 4x 60m 4x15...

Страница 6: ...Fault Adjustable Flow Detection Sensitivity Adjustable Flow Fault Threshold Relay Output 7 Relays on Termination Board Configurable Rating 2A 30 VDC General Purpose Inputs 4xGPIs Configurable GPI Func...

Страница 7: ...ector Airflow System Auxiliary Isolated indicator Beeper Programmer Access Password Controlled Bargraph and 6 digits 7 Numerical LEDs display the function Func buttons to change settings Event Logs Nu...

Страница 8: ...int of supply or extract its system sensitivity may be directly related as equal to the sensitivity of the central detector due to the cumulative effect In the case of a system monitoring more than on...

Страница 9: ...from a protected area should not exceed 120 seconds 2 minutes Transport times in excess of this must be the subject of a variation Shorter maximum transport times may be desirable in certain applicat...

Страница 10: ...VDOT ASD 100 Aspiration Detector Velocity Detection 10 VDOT ASD 100 Aspirating Smoke Detector User s Manual V1 Two branch system Four branch system...

Страница 11: ...D 21mm Other sizes will often work but will provide different response times l Maximum pipework limitation The limitation of each pipe inlet of VDOT ASD 100 when the aspirator speed set to 10 is 100m...

Страница 12: ...ity are within desired limits l System Sensitivity The recommended maximum number of sampling holes on the pipework to achieve desired relative sampling hole sensitivity is as follows Class A 40 holes...

Страница 13: ...VDOT ASD 100 Aspiration Detector Velocity Detection 13 VDOT ASD 100 Aspirating Smoke Detector User s Manual V1 Typical VDOT ASD 100 Pipework Configurations Two Branch Pipe Four Branch Pipe...

Страница 14: ...rried out by suitably experienced and trained personnel Mechanical Installation Dimensions l The mounting holes in each corner are used to mount the device on the wall It is recommended the device is...

Страница 15: ...ded to open the entry holes Sampling pipes Sampling pipes should be made from a non hazardous material and should be clearly identified Typical sampling pipes used in air sampling systems are ABS uPVC...

Страница 16: ...l the electrical connections should be made to the removable connectors on the termination board or the relay board if it equipped Cables Power cable should be 2 0mm2 2C of sufficient current carrying...

Страница 17: ...s Two 24Vdc power terminals on the termination board One must be connected to a 24 20 19 6 28 8 DC Power Supply The device may be powered by any EN54 4 compliant monitored 24DC power supply of suffici...

Страница 18: ...Isolate and Auxiliary The relay output function printed on the termination board is the factory default setting Users can change the relay function using front panel display or the Management compute...

Страница 19: ...evel is usually higher than the non working hours Sometimes outside pollutants go into the detection area can generate false alarm There are needs to decrease the sensitivity to prevent the false alar...

Страница 20: ...or another 1 2km l RS 485 Network can be configured in closed loop for better communication reliability The communication can switch direction to communicate with devices behind the failure point when...

Страница 21: ...Detector User s Manual V1 Front Panel The VDOT ASD 100 front panel is a Control Display Programmer 3 in 1 LED display Bargraph LED 20 segments Power Indicator Isolate Indicator 6 digits Numerical Dis...

Страница 22: ...f there s any malfunction LED The difference of SILENCE and ISOLATE is that SILENCE is used to silence beeper confirming the alarm or fault status When there is a new alarm or fault in occurrence the...

Страница 23: ...ult Latch function is enabled A manual reset will be needed to clear the alarm or fault o 6 digits Numerical LED In normal operation the 6 digit numerical LED displays real time smoke level airflow le...

Страница 24: ...nction is airflow related parameters ON In executing flow normalization Flashing ADDR Display the RS485 address of the device ON AUX Display code of current event and code ON Display Item Numerical LE...

Страница 25: ...Sensor 4 High Alarm A12 Sensor 4 Low Alarm High High Alarm A13 Sensor 5 High Alarm A14 Sensor 5 Low Alarm High High Alarm Smoke Detection Fault E1 Smoke Detector Failed E2 Smoke Detector Service Requ...

Страница 26: ...ecute REST ISOLATE SILENCE TEST function as well as to display the figure of Smoke Flow Addr Evt by numerical tube while in setting mode the setting of related operating parameters of detecting device...

Страница 27: ...ion u Bargraph grid represents parameter no ex Enter parameter 15 will lead 15th Bargraph grid starts to flash Enter parameter 21 will lead 20th and 01 Bargraph grid in flashing the rest may be deduce...

Страница 28: ...0 Aspiration Detector Velocity Detection 28 VDOT ASD 100 Aspirating Smoke Detector User s Manual V1 SILENCE Press and hold for 2 sec Save setting the numerical LED will flashes 3 times if successfully...

Страница 29: ...xpired The detector will generate Fire 2 Alarm 2 Time Delay Alert Delay t1 0 60 30 The alarm delay is the number of seconds that an alarm level has to be continuously sensed before the alarm is initia...

Страница 30: ...This is the factory default setting When this function is set to N the alarm will be reset automatically when the smoke level is decreased below alarm threshold Fault Latch FL N Y N When this functio...

Страница 31: ...store events in the event log ADM MM Month NN 01 12 05 DD Day dd 01 31 18 HH Hour HH 01 23 19 MM Minute nn 00 59 36 SS Second SS 00 59 0 15 System Address Ad 1 250 250 Setting the device RS485 address...

Страница 32: ...e this value to the original smoke alarm thresholds when relevant GPI is activated This setting must work with the GPI which is set to Sensitivity Mode 1 or 2 If this function value is set to be great...

Страница 33: ...s of background particulate matter testing methodology would be similar to that of standard point detectors Commissioning Check List The following brief checklist allows quick setup of the detector Th...

Страница 34: ...network can be synchronized by the Management System Software at the same time 2 Set the time delays temporarily to 0 second when testing the transport time is appropriate to eliminate the alarm dela...

Страница 35: ...f the detector as shown Untighten the screw in the middle of the filter to remove the filter Fit a new filter make sure to push the filter fully home and tighten the screw When the replacement filter...

Страница 36: ...nput voltage using a meter to make sure the power is within normal range o Check the Device Display a Press the Test button if it s enabled to check if all the LEDs on the display illuminates normally...

Страница 37: ...e g CIE BMS a Activate the fire relays in the relay test menu or introduce smoke to put the detector into alarms to check if there s associate alarm generated on the fire alarm panel if it s connected...

Страница 38: ...system a sampling pipe must be removed from the pipe inlet and introduce high airflow providing by a compressor into the sampling pipe to blow off the dust in the pipework and the sampling holes Alter...

Страница 39: ...ector Velocity Detection 39 VDOT ASD 100 Aspirating Smoke Detector User s Manual V1 Velocity Detection Address Detection House 72 78 Morfa Road Swansea SA1 2EN UK Email sales Velocitydetection com htt...

Отзывы: