71
IX. System Piping
(continued)
Figure 9.4: Boiler Head Loss
Method 1: Primary/Secondary Piping (Strongly Recommended)
This method can be used in heat-only applications as shown in Figure 9.7a or 9.8a or with an indirect water heater as shown
in Figure 9.7b, 9.7c, 9.8b, 9.8c. In this system, the flow rate through the boiler (“secondary loop”) is completely independent
of the flow rate through the system (“primary loop”). Use the following guidelines to ensure that the boiler will have the
required flow shown in Table 9.3 regardless of the flow in the heating system.
1) System Loop Piping - Size the system circulator and piping to obtain the design flow rate through the heating system
as you would on any other heating system. All piping between the expansion tank and secondary connection tees must
be at least 1". In order to keep the flow rates in the system and boiler loops independent of each other, provide at least
8 diameters of straight pipe upstream of the first tee and 4 diameters downstream of the second tee. Keep the distance
between the expansion tank and the first secondary tee as short as practical.
Содержание Raptor RPTR155
Страница 1: ...1 ...
Страница 13: ...13 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 14: ...14 Figure 5 2 Boiler Mounting Bracket Installation Boiler Wall Mounting V Mounting The Boiler continued ...
Страница 87: ...87 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Страница 88: ...88 X Wiring continued ...
Страница 97: ...97 Operating Instructions XI Start Up and Checkout continued ...
Страница 142: ...142 XV Repair Parts continued 3A 3B 3C 3D 3F 3E 3G 3H 3O 3P 3Q 3R 3J 3K 3I 3M 3N 3L All Models ...
Страница 148: ...148 XV Repair Parts continued 6D 6B 6A 6E 6I 6G 6L 6N 6H 6C 6K 6M 6C 6C 6J 6J 6F All Models ...
Страница 172: ...172 ...