Soft Lockout Codes Displayed
F. Troubleshooting problems where a Soft Lockout Code is displayed.
When a soft lockout occurs, the
boiler will shut down, the display will turn red and the “Help” button will “blink”. Select the “blinking” “Help” button to
determine the cause of the soft lockout. The boiler will automatically restart once the condition that caused the lockout is
corrected.
XIV. Troubleshooting
(continued)
Lockout
Number
Condition
Possible Cause
2
Boiler Safety Limit
Open
Boiler Safety Limit wired to terminals J6-1 or
3 OPEN:
•
External Limit.
• Optional LWCO
External Limit:
•
Water temperature is higher than External Limit setting. See “Hard
Lockout 4” for additional information.
• External device not used and jumper not installed.
• External Limit device is defective.
• Loose wiring to limit device
Optional Low Water Cut Off (LWCO)
• If yellow light on LWCO is on, system is low on water. Ensure air vent
is unobstructed and properly functioning as a blocked air vent can result
in low water indication.
• If neither yellow or green light on LWCO is on, check LWCO harness.
3
Boiler Safety Limit
Open
Blocked Flue/Inlet Switch wired to terminals
J5-1 OPEN
• Blocked Flue/Inlet Switch contact open - check for blocked flue/air intake.
NOTE
Blocked Flue/Inlet Switch Special Note
Before a call for heat the air pressure switch is closed. When there is a call
for heat with a blocked vent the air pressure switch will open (due to excessive
pressure of the blower against a blocked flue pipe) after the blower starts. The
control stops the start sequence and stops the blower. After the blower stops
the pressure switch re-closes and the cycle continues. The displays shows
the cause of trip for only the time the pressure switch is open.
7
Return sensor
(10 KOhms) fault
Shorted or open return temperature sensor.
• Shorted or mis-wired return sensor wiring.
• Defective return sensor.
8
Supply sensor
(10 KOhms) fault
Shorted or open supply temperature sensor.
• Shorted or mis-wired supply sensor wiring.
• Defective supply sensor.
10
Stack sensor
(10 KOhms) fault
Shorted or open flue gas (stack) temperature
sensor.
• Shorted or mis-wired flue temperature sensor wiring.
• Defective flue temperature sensor.
11
Ignition failure
Flame failure after 5 tries to restart. Flame
rod not detecting flame.
• Condensate trap plugged.
• No gas pressure.
• Gas pressure under minimum value shown on rating plate.
• Gas line not completely purged of air.
• Defective Electrode.
• Loose burner ground connection.
• Defective Ignition Cable.
• Defective gas valve (check for 24 Vac at harness during trial for ignition
before replacing valve).
• Air-fuel mixture out of adjustment - consult factory.
• Defective or fouled electrode.
• Plugged drain line in trap.
Содержание Raptor RPTR155
Страница 1: ...1 ...
Страница 13: ...13 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 14: ...14 Figure 5 2 Boiler Mounting Bracket Installation Boiler Wall Mounting V Mounting The Boiler continued ...
Страница 87: ...87 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Страница 88: ...88 X Wiring continued ...
Страница 97: ...97 Operating Instructions XI Start Up and Checkout continued ...
Страница 142: ...142 XV Repair Parts continued 3A 3B 3C 3D 3F 3E 3G 3H 3O 3P 3Q 3R 3J 3K 3I 3M 3N 3L All Models ...
Страница 148: ...148 XV Repair Parts continued 6D 6B 6A 6E 6I 6G 6L 6N 6H 6C 6K 6M 6C 6C 6J 6J 6F All Models ...
Страница 172: ...172 ...