5 Trouble shooting
VFD700 Solar pump inverter user manual 57
Issues
Reasons
Check And Treatments
Motor ramp
motion is not
stable
Acce. or dece. rate is
too short
Try suitable values for P00.09 and P00.10
Too big load
Adjust the load condition
After ramp
operating,
speed is not
stable
Load issue
Check if the mechanical load keeps changing
No auto-tune
Do the motor auto-tune
Motor data setup issue
Check if set the motor data according to the motor
nameplate
Cannot write
the parameter
Change is limited
Only can change at stop
The parameter property is "actual"
Keypad is locked
Press ESC switch for 5s to disable the keypad lock
Parameter is not
displayed
Set the value of P00.02 to be 1 to display all the
parameters
Enable the user code
Disable the user code
Conflicts on
parameter setup
Load default and set the parameters correctly
No display on
the k keypad
Link issue
Check the link between the keypad and drive, if the
keypad is fixed well?
DC bus bus bar link
issue
Check the link bDC and +DC1fitted well