2 Installation and cabling
18 VFD700 Solar pump inverter user manual
Type
Terminal
Name
Function
Technical Specifications
Rail supply and
Relay
RL1,RL2
Programmable relay1
output contactors
Type: normal open
Updating rate: 5ms
Contactor rating:
250VAC/2A(cosφ=1)
250VAC/1A(cosφ=0.4)
30VDC/1A
Default:
Relay1: closed when powered and
healthy.
Relay2: closed when drive is active.
RL3,RL4
Programmable relay2
output contactors
Digital input terminal basic function
There are 7 units programmable digital input terminals.
P09.01=0 (default), only basic function for digital input
P09.01=1, advanced functions are available for digital input.
This manual only introduces the basic function of digital input.
For advanced functions. please refer to “HD700 Advanced User Manual”
The basic function list is as the following table