4 Parameter
VFD700 Solar pump inverter user manual 31
Code
Name
Range
Min unit
Default
Change
P00.05 (P08.02)
AI1 mode selector
0
~
6
1
6
Stop Only
AI1 signal can be voltage or current mode.
0: 0mA
~
20mA
1: 20mA
~
0mA
2: 4mA
~
20mA (current loosing with trip)
3: 20mA
~
4mA (current loosing with trip)
4: 4mA
~
20mA (current loosing without trip)
5: 20mA
~
4mA (current loosing without trip)
6: 0V
~
10V
When the AI mode selection is“0
~
5”, if the input current is over 26mA, the drive will trip at
F012, the drive will stop as the mode decided by P03.10, then turn off the IGBTs.
When this parameter is set to 2 or 3, if the input current is less than 3mA, then the drive will
trip at F013, the drive will stop as the mode decided by P03.10, then turn off the IGBTs.
NOTE: If the selection is "2
~
5", once the current is less than 3mA, P08.16 (current loosing
indicator) is 1.
Code
Name
Range
Min unit
Default
Change
P00.06 (P04.01)
Preset1
±Max. reference
0.01Hz
50.00Hz
Run&Stop
Code
Name
Range
Min unit
Default
Change
P00.07 (P01.02)
Max. reference
0.00
~
300.0Hz
0.00 Hz
50.00 Hz
Stop Only
P00.08 (P01.03)
Min. reference
0.00Hz
~
max.
reference
0.00 Hz
0.00 Hz
Stop Only
If P03.01=0 (reverse is enabled), then the P00.08 is fixed at 0.00Hz.
Code
Name
Range
Min unit
Default
Change
P00.09 (P02.04)
Acceleration
rate1
0.0s
~
3600.0
0.1
10.0
Run&Stop
P00.10 (P02.05)
Deceleration
rate 1
0.0s
~
3600.0
0.1
20.0
Run&Stop