VFD700 Solar pump inverter user manual 45
sleeping time (P15.26), the drive will set the alarm “SLEEP” and coast stop immediately,:
(1) If the DC voltage is increasing to wake up level (P15.29) ,the alarm “SLEEP” will
disappear immediately, and delay about 15seconds ,the drive run.
(2) If the DC voltage is still lower than sleep level, the drive will keep alarming 5
times(default value, could be settable by P10.31) the drive will go to sleep. If the DC voltage
is increasing to wake up level, and it delay for 60 seconds (P15.30, settable),the drive will
wake up.
Code
Name
Range
Min unit
Default
Change
P15.26
Delay for sleeping
0.0s~3000.0s
0.1s
0.2s
Stop Only
P15.27
Wakeup mode
selector
0~1
1
1
Stop Only
P15.28
Wakeup back feed
channel
P00.00~P18.08
0.01
P05.13
Stop Only
P15.29
Threshold of
wakeup
0.0%~100.0%
0.1%
220V:74.0%
380V:64.0%
Stop Only
P15.30
Delay for wakeup
0.0s~3000.0s
0.1s
600.0s
Stop Only
When P15.27 = 0,the absolute value of the setup parameter of P15.28 (wakeup channel) is less
than P15.29 (wakeup threshold) and it keeps over wakeup delay time (P15.30), then the drive
will access wakeup mode from sleep mode and according to the previous setup parameters to
run.
When P15.27 = 1,the absolute value of the setup parameter of P15.28 (wakeup channel) is
more than P15.29 (wakeup threshold) and it keeps over wakeup delay time (P15.30), then the
drive will access wakeup mode from sleep mode and according to the previous setup
parameters to run.