AC310 Series Frequency AC Drive Manual
51
Slave address
01H
Command code
83H
Fault code
04H
Low CRC CHK
40H
High CRC CHK
F3H
●Communication control parameter group address description
Function Description
Address
Definition
Data meaning
Characteristics
Communication given
frequency
0x3000 or 0x2000
0
~
32000 correspond to 0.00Hz
~
320.00Hz
W/R
Communication command
setting
0x3001 or 0x2001
0x0000:no command
0x0001:FWD run
0x0002:REV run
0x0003:FWD Jog
0x0004:REV Jog
0x0005:Dec stop
0x0006:free stop
0x0007:Fault reset
0x0008:Run prohibition
command
0x0009:Run permission
command
W/R
AC Drive status
0x3002 or 0x2002
Bit0
0:Stop status
1:Running status
R
Bit1
0:Non-Acc
status
1:Acc status
Bit2
0:Non-Dec
status
1:Dec status
Bit3
0:Foward
1:Reverse
Bit4
0:No fault
1:AC Drive fault
Bit5
0:GPRS unlock
1:GPRS locked
Bit6
0:No warning
1:AC
Drive
warning
AC Drive fault code
0x3003 or 0x2003
AC Drive current fault code (see fault code table)
R
Communication given upper
limit frequency
0x3004 or 0x2004
0
~
32000 correspond to 0.00Hz
~
320.00Hz
W/R
Communication torque setting
0x3005 or 0x2005
0
~
1000 correspond to 0.0
~
100.0%
W/R
Torque control positive
maximum frequency limit
0x3006 or 0x2006
0
~
1000 correspond to 0.0
~
100.0%
W/R
Torque control reverse
maximum frequency limit
0x3007 or 0x2007
0
~
1000 correspond to 0.0
~
100.0%
W/R
Communication given PID set
value
0x3008 or 0x2008
0
~
1000 correspond to 0.0
~
100.0%
W/R
Communication given PID
feedback value
0x3009 or 0x2009
0
~
1000 correspond to 0.0
~
100.0%
W/R
Fault and warning code
reading
0x3010 or 0x2010
Fault code:0
~
127 Warning code:128 and above
R
Output terminal status
0x3018 or 0x2018
External AC Drive output terminal,
Bit0 – Y
Bit1-- TA1-TB1-TC1;
Bit2 – extended Y1 (with IO expansion card)
BIT3 -- Extended relay (with IO expansion card)
R
AO output
0x3019 or 0x2019
0-10000 correspond to Output 0-10V/0-20mA
R
Note: For other function code addresses, see the “Address” column in the function code profile
When using the writing command (06H) to write the F00~F15 parameters, if the function code parameter address field high nibble is 0, only write in the
AC Drive RAM, won’t be stored when power down; if the function code parameter address field
high nibble is 1, written in the EEPROM, and will be stored
when power down.
For example parameter F00.xx: 0x00xx (write in RAM), 0x10xx (stored in EEPROM); parameter F01.xx: 0x01xx (write in RAM) 0x11xx (stored in EEPROM), and so
on, for other parameters. When reading the F00~F15 parameter group parameters, the address high nibble is 0, such as reading the parameter F03.xx: 0x03xx.
When using the write command (06H) to write F16~F29 parameters, if the function code parameter address field high nibble is 5, only write in to the AC