AC310 Series Frequency AC Drive Manual
37
F11.2x
:
Monitoring Parameter
Parameter
(
Address
)
Name
Content
Factory default
(range)
Adjustable
properly
F11.20
(0x0B14)
Keyboard display item
settings
V/F SVC FVC PMVF PMSVC PMFVC
Unit digit: Output frequency display selection
0: Target frequency 1: Operating frequency >=2: Target frequency,
the filtering depth increases with this value
Ten: reserved
Hundreds: Power Display Dimensions
0: Power display percentage (%) 1: Power display kilowatt (KW)
Thousands: reserved
0002
(0000 ~ 111F)
RUN
F11.21
(0x0B15)
Speed display factor
V/F SVC FVC PMVF PMSVC PMFVC
Adjust the speed display of C00.06.
100.0%
(0.0
~
500.0%)
RUN
F11.22
(0x0B16)
Power display factor
V/F SVC FVC PMVF PMSVC PMFVC
Adjust the output power display of C00.10.
100.0%
(0.0
~
500.0%)
RUN
F11.23
(0x0B17)
Monitoring parameter
group display selection
V/F SVC FVC PMVF PMSVC PMFVC
Unit: Reserved
Ten: C05 display selection
0: Automatically switch according to the control mode
1:VF mode related parameters
2: VC mode related parameters
Hundreds place: C00.40~C00.63 display selection
0: Do not display 1: display
Thousands: Communication fault code switching enable
0: not enabled
1: Enable, the fault code is switched to the same as AC300 when
485 communication
2: Enable, the fault code is switched to the AC70 when 485
communication
0000
(0000 ~ FFFF)
RUN
F11.24
(0x0B18)
Monitoring parameter
filtering selection
V/F SVC FVC PMVF PMSVC PMFVC
Unit: Output current display filter
0~F: the larger the value, the deeper the filter
0002
(0000 ~000F)
RUN
F11.25
(0x0B19)
Display selection when
the motor is
self-learning
V/F SVC FVC PMVF PMSVC PMFVC
Set the display selection when the motor is self-learning
0: Display self-learning process status 1: Do not display self-learning
process status
0
(0 ~ 1)
STOP
F11.27
(0x0B1B)
Fault display selection
V/F SVC FVC PMVF PMSVC PMFVC
Unit: The fault is displayed when the fault recovers.
0: Do not display 1: Display
0001
(0000 ~ 0001)
RUN
4.15
F12
:
Communication Parameter
F12.0x
:
MODBUS Slave Parameter
Parameter
(
Address
)
Name
Content
Factory default
(range)
Adjustable
properly
F12.00
(0x0C00)
Host-slave choice
V/F SVC FVC PMVF PMSVC PMFVC
0
:
Slave
,
1
:
Host
0
(0 ~ 1)
STOP
F12.01
(0x0C01)
Modbus
communication
address
V/F SVC FVC PMVF PMSVC PMFVC
Set different values for different slaves.
1
(1 ~ 247)
STOP
F12.02
(0x0C02)
Communication baud
rate selection
V/F SVC FVC PMVF PMSVC PMFVC
0
:
1200 bps 1
:
2400 bps 2
:
4800 bps
3
:
9600 bps 4
:
19200 bps 5
:
38400 bps
6
:
57600 bps
3
(0 ~ 6)
STOP
F12.03
(0x0C03)
Modbus data format
V/F SVC FVC PMVF PMSVC PMFVC
0: (N, 8, 1) no parity, data bits: 8, stop bits: 1
1: (E, 8, 1) even parity, data bits: 8, stop bits: 1
2: (O, 8, 1) odd parity, data bits: 8, stop bits: 1
3: (N, 8, 2) no parity, data bits: 8, stop bits: 2
4: (E, 8, 2) even parity, data bits: 8, stop bits: 2
5: (O, 8, 2) odd parity, data bits: 8, stop bits: 2
0
(0 ~ 5)
STOP