AC310 Series Frequency AC Drive Manual 

13 

4.3

 

Environment application

 

Parameter 

Address

 

Name 

Content 

Factory default 

(range) 

Adjustable 

properly 

F00.00 

(0x0000) 

Parameter access 

level 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

Set  the  parameter  access  level  based  on  the  case  of  restricted 
parameter access. 
0: standard parameter (Fxx.yy) 
1: Common parameters (F00.00, Pxx.yy) 
2: Monitoring parameters (F00.00, Cxx.yy) 
3: Changed parameter(F00.00, Hxx.yy) 

(0 ~ 3) 

RUN 

F00.03 

(0x0003) 

Initialization   

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

Set the AC Drive initialization method. 
0: not initialized 
11: Select the set value according to the purpose to perform the 
parameter (excluding the motor parameter) 
22: All parameters are initialized 
33: Clear the fault record 

0 ~ 33

 

STOP 

F00.04 

(0x0004) 

Keyboard parameter 

copy 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

0: no function 
1: Upload parameters to the keyboard 
2: Download parameters to the AC Drive 

0 ~ 9999

 

STOP 

F00.05 

(0x0005) 

User password 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

Used to set the user password. 

0 ~ 65355

 

STOP 

F00.06 

(0x0006) 

LCD keyboard 

language selection 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

Select the language displayed on the LCD operator. 
0: Chinese 1: English 

0 ~ 1

 

RUN 

F00.07 

(0x0007) 

Free parameter 1 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

When using multiple machines, use the machine number or usage 
mode number. 

0 ~ 65535

 

RUN 

F00.08 

(0x0008) 

Free parameter 2 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

When using multiple machines, use the machine number or usage 
mode number. 

0 ~ 65535

 

RUN 

F00.10~F00.3

(0x0010 ~ 

0x0027) 

Common parameter 

address setting 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

“0~00” digits: yy setting in function parameter number Fxx.yy 
00

99 

“000~0000”digits: xx setting in function parameter number Fxx.yy 
00~31 

0102 

(0000 ~ 3199) 

RUN

 

4.4

 

F01

Basic Settings 

F01.0x

Basic command 

Parameter 

Address

 

Name 

Content 

Factory default 

(range) 

Adjustable 

properly 

F01.00 

(0x0100) 

Motor control 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

The control mode of the motor. 
Asynchronous motor control mode: 
0: AM-VF; VF control 
1:AM-SVC; open loop vector control, current closed loop control 
2: AM-FVC; closed loop vector control 
Synchronous motor control mode: 
10: PM-VF; VF control 
11: PM-SVC; open loop vector control 
12: PM-FVC; closed loop vector control 

(0 ~ 12) 

STOP

 

F01.01 

(0x0101) 

Run command 

channel 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

Used to select the channel that the drive accepts the run and stop 
commands and the direction of travel. 
0: keyboard control (external keyboard priority) 1: terminal control 
2: RS485 communication control 3: Option card 

0 ~ 3

 

RUN 

F01.02 

(0x0102) 

Frequency given 

channel A 

V/F    SVC    FVC    PMVF    PMSVC    PMFVC 

The given source channel B of the frequency converter 
0:  keyboard  digital  reference  frequency  1:  keyboard  analog 
potentiometer given 
2: Current/voltage analog AI1 given 
3: Current/voltage analog AI2 given 

0 ~ 11

 

RUN 

Содержание AC310

Страница 1: ...5 F02 MOTORPARAMETER 16 4 6 F03 VECTOR CONTROLLING 18 4 7 F04 V FCONTROLLING 21 4 8 F05 INPUTTERMINAL 22 4 9 F06 OUTPUTTERMINAL 25 4 10 F07 OPERATIONALCONTROL 29 4 11 F08 AUXILIARY CONTROL 31 4 12 F0...

Страница 2: ...nd confirm that the DCvoltage of the main circuit has dropped to Safety level wait 5 minutesbefore performing related work Thepowercable motor cable andcontrolcable must be tightly connected Theground...

Страница 3: ...atic torque boost 0 0 100 0 Manual torqueboost 0 0 30 0 V F curve Four modes linear torque characteristic curve self set V Fcurve torque reduction characteristic curve 1 1 to 2 0 power square V Fcurve...

Страница 4: ...192 155 149 65 65 193 5 5 4 3 M4 AC310 T3 1R5G 2R2P B AC310 T3 2R2G B AC310 T3 004G 5R5P B 100 242 231 155 149 84 86 5 231 5 8 5 5 3 M4 AC310 T3 5R5G 7R5P B AC310 T3 7R5G 011P B 116 320 307 5 175 169...

Страница 5: ...uirements 150mm 150mm Externalkeyboard shape and opening size Note LCDkeyboard is fully compatible with LED keyboard size and opening size AC310 Series Externalkeyboard pocket shape and opening size L...

Страница 6: ...electrical components instructions Name Installation andselection Function Definition DCreactor Installed between the EMC filter and thebraking resistor 132kWand above standard Increase thepowerfactor...

Страница 7: ...ard shiftkeyfunction to quicklyselect Runmonitoringstatus view Note When using the external keyboard use the left shift button to cycle through the first line of monitoring parameters and use the righ...

Страница 8: ...or usage modenumber 0 0 65535 RUN F00 08 0x0008 Free parameter 2 V F SVC FVC PMVF PMSVC PMFVC Whenusing multiple machines use the machine numberor usage modenumber 0 0 65535 RUN F00 10 F00 3 9 0x0010...

Страница 9: ...ation time 3 V F SVC FVC PMVF PMSVC PMFVC Time required for the output frequency to decelerate from the reference frequencyto 0 00 Hz Modelrelated 0 01 650 00s RUN F01 28 0x011C Acceleration time 4 V...

Страница 10: ...stator resistance standard value V F SVC FVC PMVF PMSVC PMFVC Setthe stator resistance valueofthe PM Modelrelated READ F02 26 0x021A Synchronousmachine D axis inductance standard value V F SVC FVC PMV...

Страница 11: ...esponds to F01 10 maximum frequency 10 0 0 0 100 0 RUN F03 23 0x0317 Asynchronousmotor slip compensation V F SVC FVC PMVF PMSVC PMFVC Setthe asynchronousmotorspeed slip compensation 100 0 0 0 250 0 RU...

Страница 12: ...l torque boost 0 0 0 0 30 0 RUN F04 02 0x0402 Torque boostcutoff frequency V F SVC FVC PMVF PMSVC PMFVC Set the effective range of the torque boost function When the output frequency exceeds this valu...

Страница 13: ...l X4 transit from the active state to the inactive state 0 010 0 000 6 000s RUN F05 18 0x0512 X5 effective detection delay V F SVC FVC PMVF PMSVC PMFVC The delay time corresponding to the input termin...

Страница 14: ...tthe lower limitofcurve 2 0 0 0 0 100 0 RUN F05 71 0x0547 Curve 2 lower limit corresponding setting V F SVC FVC PMVF PMSVC PMFVC Setthe corresponding percentage 0 00 0 00 100 00 RUN F05 72 0x0548 Curv...

Страница 15: ...y default range Adjustable properly F06 50 0x0632 Comparator 1 monitor selection V F SVC FVC PMVF PMSVC PMFVC UnitsandTensdigits Set yyvalue ofthe Cxx yy 00 63 Hundredsand thousands Setxxvalue ofthe C...

Страница 16: ...0 command isinvalid 1 command isvalid 0000 0000 1121 STOP F07 06 0x0706 Powerfailurerestart action selection V F SVC FVC PMVF PMSVC PMFVC 0 Invalid 1 Valid 0 0 1 STOP F07 07 0x0707 Powerfailurerestar...

Страница 17: ...0 Second 1 Minute 2 Hour 0 0 2 STOP F08 08 0x0808 Timersetting V F SVC FVC PMVF PMSVC PMFVC Setthe timersetting 0 0 65000 STOP F08 3x Swing Frequency Control Parameter Address Name Content Factory def...

Страница 18: ...and outputphase loss protection options V F SVC FVC PMVF PMSVC PMFVC Setwhether the inputand outputphase lossprotection functionsare enabled Unit Outputphase lossprotection 0 off1 on Tens inputphase l...

Страница 19: ...MFVC Setthe waiting time fromfaultto reset 1 0s 0 100 0 STOP F10 52 0x0A34 Number offault recovered V F SVC FVC PMVF PMSVC PMFVC This value indicates the number of self recovery that have been perform...

Страница 20: ...cation 0000 0000 FFFF RUN F11 24 0x0B18 Monitoring parameter filtering selection V F SVC FVC PMVF PMSVC PMFVC Unit Outputcurrentdisplayfilter 0 F the largerthe value the deeper the filter 0002 0000 00...

Страница 21: ...X A monitoring frame addressgroup 3 V F SVC FVC PMVF PMSVC PMFVC Ditto 0007 0000 0763 RUN F12 56 0x0C38 Expansion portEX A monitoring frame addressgroup 4 V F SVC FVC PMVF PMSVC PMFVC Ditto 0011 0000...

Страница 22: ...x0D1E Sleep frequency V F SVC FVC PMVF PMSVC PMFVC Setsleep frequency 10 00Hz 0 00 Max frequency RUN F13 31 0x0D1F Sleep delay V F SVC FVC PMVF PMSVC PMFVC Setthe timeofsleep delay 60 0S 0 0 3600 0S R...

Страница 23: ...nning direction ofthissegment compared with the running command 0 same direction 1 reverse Ten digits acceleration anddeceleration time ofthissection 0 Acceleration deceleration time 11 Acceleration d...

Страница 24: ...and Revcommandgiven C02 01 0x2301 PIDgiven C02 09 0x2309 Jog commandgiven C02 02 0x2302 PIDoutput C02 60 0x233C Expansion cardAversion C02 03 0x2303 PIDcontrolstatus C02 61 0x233D Expansion card B ve...

Страница 25: ...tion Fault A SPD 134 Speed warning Warning E COP 43 Parameter copyfailure Fault A GPS1 135 GPS locked Warning E PG1 44 PGparameter settingerror Fault A GPS2 136 GPS disconnection Warning E PG2 44 Enco...

Страница 26: ...o need to replace it please contact the agent where you purchased the product or the salesdepartmentofthe company 5 3 Product Warranty 1 The productduring the warrantyperiod isfaulty Fordetails please...

Страница 27: ...erse maximum frequency limit 0x3007 or0x2007 0 1000 correspond to 0 0 100 0 W R Communication given PID set value 0x3008 or0x2008 0 1000 correspond to 0 0 100 0 W R Communication given PID feedback va...

Страница 28: ...In thismode the three wireoperation controlterminal Xi isthe stop operation terminal and therunning command isgenerated bythe forward rotation operation terminal X1 forward rotationoperation and the d...

Отзывы: