AC310 Series Frequency AC Drive Manual
13
4.3
Environment application
Parameter
(
Address
)
Name
Content
Factory default
(range)
Adjustable
properly
F00.00
(0x0000)
Parameter access
level
V/F SVC FVC PMVF PMSVC PMFVC
Set the parameter access level based on the case of restricted
parameter access.
0: standard parameter (Fxx.yy)
1: Common parameters (F00.00, Pxx.yy)
2: Monitoring parameters (F00.00, Cxx.yy)
3: Changed parameter(F00.00, Hxx.yy)
0
(0 ~ 3)
RUN
F00.03
(0x0003)
Initialization
V/F SVC FVC PMVF PMSVC PMFVC
Set the AC Drive initialization method.
0: not initialized
11: Select the set value according to the purpose to perform the
parameter (excluding the motor parameter)
22: All parameters are initialized
33: Clear the fault record
0
(
0 ~ 33
)
STOP
F00.04
(0x0004)
Keyboard parameter
copy
V/F SVC FVC PMVF PMSVC PMFVC
0: no function
1: Upload parameters to the keyboard
2: Download parameters to the AC Drive
0
(
0 ~ 9999
)
STOP
F00.05
(0x0005)
User password
V/F SVC FVC PMVF PMSVC PMFVC
Used to set the user password.
0
(
0 ~ 65355
)
STOP
F00.06
(0x0006)
LCD keyboard
language selection
V/F SVC FVC PMVF PMSVC PMFVC
Select the language displayed on the LCD operator.
0: Chinese 1: English
0
(
0 ~ 1
)
RUN
F00.07
(0x0007)
Free parameter 1
V/F SVC FVC PMVF PMSVC PMFVC
When using multiple machines, use the machine number or usage
mode number.
0
(
0 ~ 65535
)
RUN
F00.08
(0x0008)
Free parameter 2
V/F SVC FVC PMVF PMSVC PMFVC
When using multiple machines, use the machine number or usage
mode number.
0
(
0 ~ 65535
)
RUN
F00.10~F00.3
9
(0x0010 ~
0x0027)
Common parameter
address setting
V/F SVC FVC PMVF PMSVC PMFVC
“0~00” digits: yy setting in function parameter number Fxx.yy
00
~
99
“000~0000”digits: xx setting in function parameter number Fxx.yy
00~31
0102
(0000 ~ 3199)
RUN
4.4
F01
:
Basic Settings
F01.0x
:
Basic command
Parameter
(
Address
)
Name
Content
Factory default
(range)
Adjustable
properly
F01.00
(0x0100)
Motor control
V/F SVC FVC PMVF PMSVC PMFVC
The control mode of the motor.
Asynchronous motor control mode:
0: AM-VF; VF control
1:AM-SVC; open loop vector control, current closed loop control
2: AM-FVC; closed loop vector control
Synchronous motor control mode:
10: PM-VF; VF control
11: PM-SVC; open loop vector control
12: PM-FVC; closed loop vector control
0
(0 ~ 12)
STOP
F01.01
(0x0101)
Run command
channel
V/F SVC FVC PMVF PMSVC PMFVC
Used to select the channel that the drive accepts the run and stop
commands and the direction of travel.
0: keyboard control (external keyboard priority) 1: terminal control
2: RS485 communication control 3: Option card
0
(
0 ~ 3
)
RUN
F01.02
(0x0102)
Frequency given
channel A
V/F SVC FVC PMVF PMSVC PMFVC
The given source channel B of the frequency converter
0: keyboard digital reference frequency 1: keyboard analog
potentiometer given
2: Current/voltage analog AI1 given
3: Current/voltage analog AI2 given
0
(
0 ~ 11
)
RUN