49
6 Set up the sensor with the display and adjustment module
VEGAPULS 69 • Modbus and Levelmaster protocol
47252-EN-210205
In this menu item, the internal clock of the sensor is set to the request-
ed time and time format. At the time of shipment from factory, the
instrument is set to CET (Central European Time).
During a reset, the parameter settings carried out by the user are
reset to the default values (see below table).
Proceed as follows:
1. Select with
[->]
under "
Additional adjustments
" the menu item "
Reset
" and confirm with
[OK]
.
2. Confirm with
[OK]
and select the requested reset function with
[->]
3. Confirm with
[OK]
, for approx. 5 s the message "
Resetting
" is
displayed, then the selection window appears.
Caution:
For the duration of the reset, the set trouble signal is output via the
current output. Within the context of the asset management function,
the message "
Maintenance
" is output.
The following reset functions are available:
Delivery status:
Restores the parameter settings at the time of ship-
ment from the factory, incl. the order-specific settings. Any created
false signal suppression, user-programmable linearization curve as
well as measured value and echo curve memory is deleted. The event
and parameter modification memories remain unaffected.
Basic settings:
Resets the parameter settings, incl. special param-
eters, to the default values of the respective instrument. Any stored
false signal suppression or user programmable linearisation curve, as
Additional settings - Date/
Time
Additional settings -
Reset