8 Diagnostics and servicing
VEGADIS 82 • 4 … 20 mA/HART
45300-EN-170724
Code
Text message
Reason
Rectification
F036
No executable software
version
•
Instrument software
not executable (during
software update or after
failed update)
•
Wait until software update is finished
•
Carry out another software update
F037
RAM defective
•
Error of the RAM in the
internal data memory
•
Switch the instrument off and on
•
Carry out reset to default setting
•
Send instrument for repair
F040
General hardware error
•
Hardware error
•
Switch the instrument off and on
•
Carry out reset to default setting
•
Send instrument for repair
S053
Sensor measuring range
too small
•
Sensor measuring range
not read correctly
•
HART communication error: Check sensor cable and
screening
•
Switch the instrument off and on
8.3 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
Connect a multimeter in the suitable measuring range according to
the wiring plan. The following table describes possible errors in the
current signal and helps to eliminate them:
Error
Reason
Rectification
4 … 20 mA signal not sta-
ble
•
Fluctuations of the
measured variable
•
Set damping appropriate to the instrument via the
display and adjustment module or PACTware/DTM
4 … 20 mA signal missing
•
Electrical connection
faulty
•
Check connection according to chapter "
Connection
steps
" and if necessary, correct according to chapter
"
Wiring plan
"
•
Voltage supply missing
•
Check cables for breaks; repair if necessary
•
Operating voltage too
low or load resistance
too high
•
Check, adapt if necessary
Current signal greater than
22 mA or less than 3.6 mA
•
Electronics module in the
sensor defective
•
Exchange the instrument or send it in for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "
Setup
" must be carried out again or must
be checked for plausibility and completeness.
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no.
+49 1805 858550
.
The hotline is also available outside normal working hours, seven
days a week around the clock.
Since we offer this service worldwide, the support is provided in
English. The service itself is free of charge, the only costs involved are
the normal call charges.
Reaction when malfunc-
tion occurs
Check the 4 … 20 mA
signal
Reaction after fault recti-
fication
24 hour service hotline