VEGADIS 82 • 4 … 20 mA/HART
45300-EN-170724
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the distance value.
4. Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the min. distance to the antenna edge.
5. Save settings with
[OK]
Proceed as follows:
1. Select the menu item "
Setup
" with
[->]
and confirm with
[OK]
.
Now select with
[->]
the menu item "
Min. adjustment
" and confirm
with
[OK]
.
2. Edit the percentage value with
[OK]
and set the cursor to the
requested position with
[->]
.
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the distance value.
4. Enter the suitable distance value in m for empty vessel (e.g. dis-
tance from the sensor to the vessel bottom) corresponding to the
percentage value.
5. Save settings with
[OK]
and move with
[ESC]
and
[->]
to the max.
adjustment.
In this menu item, the device status is displayed.
Setup - Min. adjustment
Diagnostics - Device
status