5 Connecting to power supply
VEGADIS 82 • 4 … 20 mA/HART
45300-EN-170724
5.3 Wiring plan
Sensor
1
2
+
( )
(-)
power supply
3
4
+
( )
(-)
R
off on
HART
1
4
2
3
Fig. 10: Wiring plan VEGADIS 82 4 … 20 mA/HART
1 To the sensor
2 Switch for communication resistor (on = activated, off = deactivated)
3 Terminal for connection of the cable screen
4 For power supply
1
3
2
4
3
1
2
Fig. 11: Wiring plan VEGADIS 82 for 4 … 20 mA sensors - panel mounting
1 To the sensor
2 Ground terminal in the switching cabinet for connection of the cable screen
3 For power supply
5.4 Connection HART standard
The following illustration shows in a simplified way the use of
VEGADIS 82 in conjunction with a HART sensor.
Note:
If the instrument is powered via a VEGAMET signal conditioning
instrument, the communication resistance is already included in the
signal conditioning instrument. The communication resistance in
VEGADIS 82 may not be activated.
Wiring plan
Wiring plan - Panel
mounting