I
f the adjustment ranges are exceeded
,
the message
"
O
utside
parameter limits
"
appears
.
T
he editing procedure can be aborted with
[
ESC
]
or the displayed limit value can be accepted with
[
OK
]
.
P
roceed as follows
:
1
E
dit the
%
value in the menu item
"
M
ax
.
adjustment
"
with
[
OK
]
.
M
ax
.
adjustment
+
100
.
0
%
=
+
1000
.
0
mbar
0000
.
0
mbar
I
nformation
:
T
he displayed pressure for
100
%
corresponds to the nominal
measuring range of the sensor
(
in the above example
1
bar
=
1000
mbar
).
2
S
et the requested percentage value with
[-
>
]
and
[
OK
]
.
3
E
dit the requested mbar value with
[
OK
]
.
4
S
et the requested mbar value with
[
+
]
and
[-
>
]
.
5
C
on
fi
rm with
[
OK
]
and move to the menu overview with
[
ESC
]
.
T
he max
.
adjustment is
fi
nished
.
I
nformation
:
F
or an adjustment with
fi
lling
,
simply enter the actual measured value
indicated at the bottom of the display
.
I
f the adjustment ranges are exceeded
,
the message
"
O
utside
parameter limits
"
appears
.
T
he editing procedure can be aborted with
[
ESC
]
or the displayed limit value can be accepted with
[
OK
]
.
P
rocess pressure measurement
S
et up
VEGABAR
51
in the following sequence
:
1
S
elect application
"
P
rocess pressure measurement
"
2
S
elect the unit of measurement
3
C
arry out a position correction
4
C
arrying out zero adjustment
5
C
arrying out span adjustment
I
n the menu item
"
A
djustment unit
"
you select the physical unit in which
the adjustment should be carried out
,
e
.
g
.
mbar
,
bar
,
psi
…
T
he position correction compensates the in
fl
uence of the mounting
position or static pressure on the measurement
.
I
t does not in
fl
uence
the adjustment values
.
I
n the menu items
"
zero
"
and
"
span
"
you determine the span of the
sensor
,
the span corresponds to the end value
.
C
arry out max
.
adjust
-
ment
P
arameter ad
-
justment
"
P
ro
-
cess pressure
measurement
"
36
VEGABAR
51
•
F
oundation
F
ieldbus
6
S
et up with the indicating and adjustment module
PLICSCOM
36715
-
EN
-
110629