WPLLD Site Prep and Installation Guide

Red Jacket Pumps (Except Quantum and The Red Jacket)

4-6

Figure 4-6.   Placing Shield Into Capacitor Housing

7. Rotate the transducer about three turns counterclockwise, then screw it into the pump compartment and tighten it 

securely.

8. For 3.0 Gph-Only Testing (w/o SwiftCheck valve) -

Connect one end of the Sensing Line to the fitting in the Line Test port and the other end to the WPLLD transducer 
(Figure 4-8). Tighten connections and attach one of the “WARNING” tags to the Sensing Line. With the two 6-32 x 
0.375” screws provided, attach the capacitor cover bracket to the top of the transducer. Snap the capacitor cover into 
the storage bracket.

For 0.2 Gph And 0.1 Gph Testing (w/ SwiftCheck valve) -

Install one end of the Sensing Line from the installation kit to the WPLLD transducer and the other end to the Swift-
Check valve (Figure 4-7). Tighten connections and attach one of the “WARNING” tags to the Sensing Line. With the 
two 6-32 x 0.375” screws provided, attach the capacitor cover bracket to the top of the transducer. Snap the capacitor 
cover into the storage bracket. 

 

Figure 4-7.   WPLLD Transducer Installation--Red Jacket Pump w/SwiftCheck

slld/wplldshl.eps

Insert 2 wires from the 
transducer into the notch 
when installing the shield

Shield

WPLLD sensor

Capacitor well

slld\wlrdjk5.eps

WPLLD Sensor

Sensing Line

SwiftCheck Valve 
in Mechanical 
LLD Pump Port

Capacitor Cover
Snapped in Bracket

6-32 x .375 Thread-Forming 
Screws (2)

Warning Tag

WARNING

THE SUBMERGED PUMP SYSTEM SUPPLYING THE

DISPENSERS MAY TURN ON UNEXPECTEDLY TO

PERFORM A LINE LEAK TEST.  THIS MAY RESULT

IN FUEL SPRAYING DURING DISPENSER, PRODUCT

LINE, LEAK DETECTOR OR STP SERVICE.

PERFORM THE FOLLOWING BEFORE BEGINNING SERVICE:

1. CLOSE AFFECTED DISPENSER SHEAR VALVE AND TEST

    FOR PROPER SHUTOFF OF THE VALVE IF PERFORMING

    DISPENSER HYDRAULIC SERVICE.

2. REMOVE POWER TO THE SUBMERGED PUMP (STP) AND

    TO LLD-300  AND LINE LEAK DETECTOR SYSTEM.

3. WEAR EYE PROTECTION.

4. COLLECT FUEL IN APPROVED CONTAINERS.

    DO NOT CONTAMINATE ENVIRONMENT.

TO ORDER TAGS - USE PART NO. 329801-00X

Содержание WPLLD

Страница 1: ...WPLLD Manual No 576013 923 Revision V Site Prep and Installation Guide...

Страница 2: ...all components and units as soon as they are received If damaged write a complete and detailed description of the damage on the face of the freight bill The carrier s agent must verify the inspection...

Страница 3: ...antum and The Red Jacket 4 1 SwiftCheck Valve Installation 4 1 Adjusting the Pressurstat Relief Pressure for 3 0 gph testing only 4 3 Disabling the Functional Element required for 0 2 0 1 gph testing...

Страница 4: ...Pump 4 10 Figure 4 13 Wiring the WPLLD Transducer to the FE Petro Pump 4 11 Figure 4 14 WPLLD Transducer Installation FE Petro Pump 4 12 Figure 4 15 Manifolded Product Lines WPLLD Installation Dual Pu...

Страница 5: ...may only be submitted by selected Distributors Related Manuals 576013 879 TLS 3XX Series Site Prep and Installation Manual 577013 465 Line Leak Application Guide 577013 481 WPLLD Modules Installation...

Страница 6: ...l not detect leaks less than 3 0 gph In this situation the system will always pass 0 2 and 0 1 gph tests but the results will not be valid 4 Ensure that the submersible pump is properly grounded per t...

Страница 7: ...0020 416 And Interlock Relay Non Vented Swift Check Valve for Secondary pump V R Kit P N 330020 416 Red Jacket Pressurstat TM Assy P Ns 323 006 5 323 001 5 323 007 5 AG or 323 002 5 AG 849490 003 Not...

Страница 8: ...ion Guide 576013 923 1 O ring Line Leak Sensor 512700 225 1 Label 331058 001 1The 849490 004 systems require that a SwiftCheck Valve be purchased separately Contained in Red Jacket Install Kit 330020...

Страница 9: ...crews 510500 457 1 Label 331058 001 Contained in Install Kit 330020 412 Table 1 6 WPLLD System 849490 006 Quantity Description Part Number 1 Wireless Line Leak Sensor 331474 015 1 Sensing Line 410138...

Страница 10: ...system isolate the inactive lines from the active lines using a shutoff valve Failure to do so may cause inaccurate leak test results Existing Check Valves You must ensure that there are no existing c...

Страница 11: ...ing for multiple pump controls may be entering the console through the same conduit open ing be sure to color code or mark each wire to identify its source WPLLD AC Interface Module 1 Turn Off tag and...

Страница 12: ...ation Excessive noise will cause WPLLD Comm alarms resulting in line shutdowns Verification is done as follows 1 Turn On all electrical equipment at the site and leave it on during this entire procedu...

Страница 13: ...e extension jacks If unplugging one of these devices causes the LED to go off that device is not compatible with WPLLD and should not be used IMPORTANT Do not unplug equipment required for site operat...

Страница 14: ...ector LLD remove the mechanical unit and any related tubing and fittings Plug any tubing openings using appropriate fittings and seal using a UL classified thread sealant suitable for the fuel involve...

Страница 15: ...stall the WPLLD valve Figure 4 2 in the Mechanical LLD pump port IMPORTANT Do not overtighten the valve when installing into the pump Overtightening the valve can cause it to stick resulting in a flow...

Страница 16: ...Replace the brass cap you only have to hand tighten it because the O ring completes the seal Figure 4 3 Pressurstat Adjustable Check Valve DISABLING THE FUNCTIONAL ELEMENT REQUIRED FOR 0 2 0 1 GPH TE...

Страница 17: ...ith a UL classified nontoxic thread sealant suitable for the fuel involved Do not apply sealant to the threads adjacent to the flare fitting 3 Remove the O ring from the installation kit and lightly l...

Страница 18: ...D transducer Figure 4 5 Wiring the WPLLD Transducer to the Pump 6 Place the shield from the installation kit into the capacitor housing with open side up Hold the shield at an angle and place notched...

Страница 19: ...he two 6 32 x 0 375 screws provided attach the capacitor cover bracket to the top of the transducer Snap the capacitor cover into the storage bracket Figure 4 7 WPLLD Transducer Installation Red Jacke...

Страница 20: ...rning Tag Line Test Port W ARNING THE SUBM ERGED PUM P SYSTEM SUPPLYIN G THE DIS PENSERS M AY TURN ON UNEXPECTEDLY TO PERFORM A LIN E LEAK TEST THIS M AY RESULT IN FUEL SPRAYIN G DURIN G DIS PENSER PR...

Страница 21: ...tion in Red Jacket Quantum Pump WARNING DO NOT APPLY ANY THREAD SEALANT OR PIPE DOPE TO THE THREADS OF THE WPLLD TRANSDUCER OR TO THE THREADS OF THE STP S MOTOR CAPACITOR WELL INTO WHICH IT IS SCREWED...

Страница 22: ...THREADS OF THE WPLLD TRANSDUCER OR TO THE THREADS OF THE STP S MOTOR CAPACITOR WELL INTO WHICH IT IS SCREWED The metal to metal joint created by threads of the WPLLD transducer in the STP s capacitor...

Страница 23: ...ALLATION 1 Turn Off tag and lockout power to pump 2 Remove the plug from the top of the Pressure Test Port and adjust Valve Clamp if necessary Figure 4 14 3 For precision testing install the FE Petro...

Страница 24: ...13 Using the electrical connector provided connect the 2 cut black leads to either one of the wires from the WPLLD transducer Figure 4 13 Wiring the WPLLD Transducer to the FE Petro Pump 8 Cut the or...

Страница 25: ...pump is energized only when dispensing but is turned Off when performing line tests Refer to page 5 1 for specific installation instructions A non vented SwiftCheck valve must be installed in the sec...

Страница 26: ...stalled in the secondary pump s Dielectric unions and flexible piping elements should be used as required by federal state and local requirements for the specific piping application Location of unions...

Страница 27: ...nitored containment sump or mechanical leak detector is required The WPLLD will not detect leaks upstream from the valve i e between the valve and the Submersible Pump Also there must not be a check v...

Страница 28: ...sor Containment sump SwiftCheck valve Flexible fuel line Note Remove in line check valve if present Healy Mini Jet TM Product line to dispensers Red Jacket leak detector fitting Red Jacket Part No 038...

Страница 29: ...able to start the submersible pump to perform a line leak test and shut the pump off if a leak is detected To enable this feature interrupt the AC Line between the Dispenser ON Switch and the pump con...

Страница 30: ...Connect a wire from the C terminal on the 4 Relay output or I O Combination module into the wire connecting the L1 terminal on the WPLLD Controller Module to 120 volt AC line 7 If installing a system...

Страница 31: ...Control Box PI 1 PR LI PO PI 2 PR LI PO PI 3 PR LI PO RELAY RATINGS FORM A CONTACTS 120 or 240 VAC 2A MAX WIRELESS PRESSURE LINE LEAK CONTROLLER MODULE Pump Contactor 120 or 240 Vac Line 15 Amp Max A...

Страница 32: ...TROLLER MODULE PI PR L1 PO PI PR L1 PO PI PR L1 PO 1 2 3 PUMP INPUT PUMP RETURN NEUTRAL PUMP OUTPUT L1 120 or 240 VAC LINE 15 AMP MAX AC NEUTRAL Circuit Breaker Panel TO SUBMERSIBLE PUMP FROM BREAKER...

Страница 33: ...DULE 4 RELAY OUTPUT MODULE S2 W2 W1 N L1 L2 Product Relay TO SUBMERSIBLE PUMP RED JACKET REMOTE CONTROL BOX FROM BREAKER PANEL PUMP POWER Secondary Pump S2 W2 W1 N L1 L2 Product Relay PUMP CONTROL FRO...

Страница 34: ...noise on the line One dimly flashing red LED is acceptable however if more than 1 of the red LEDs are flashing you have excessive noise on the ac line and it should be removed before continuing Start...

Страница 35: ...WPLLD set up information into the console before beginning this procedure PRESSURE OFFSET New transducers are now factory sealed and their internal chamber cannot be equalized to atmospheric pressure...

Страница 36: ...for transducer W1 If necessary press the left arrow key to change the sign or Note enter the Offset value exactly as displayed in the Offset test result message including or sign Press TANK SENSOR to...

Страница 37: ...mation Check for STP leaks as follows a Turn On the STP and carefully check all fittings and the functional element for leaks b Verify that the functional element strainer and check valve threads into...

Страница 38: ...ng veeder com England Hydrex House Garden Road Richmond Surrey TW9 4NR Tel 44 0 20 8392 1355 Fax 44 0 20 8878 6642 Email sales veeder co uk France 94 106 Rue Blaise Pascal 93600 Aulnay Sous Bois Tel 3...

Отзывы: