WPLLD Site Prep and Installation Guide
Red Jacket Quantum Pump (w/ and w/o SpikeCheck Valve Assy.)
4-7
Figure 4-8. WPLLD Transducer Installation--Red Jacket Pump w/o SwiftCheck
Red Jacket Quantum Pump (w/ and w/o SpikeCheck Valve Assy.)
1. Turn Off, tag, and lockout power to pump.
2. After referring to Figure 4-9 remove the Line Test Port plug, the Pressurstat (if installing a SpikeCheck), and the
cover from the pump’s capacitor housing (do not discard cover).
Figure 4-9. Red Jacket Quantum Pump
wplld\rjnosck.eps
Wireless Line Leak Sensor
Sensing Line
Capacitor
Cover
Bracket
PERFORM THE FOLLOWING BEFORE BEGINNING SERVICE:
Capacitor Cover
Snapped in Bracket
6-32 x .375 Thread-Forming
Screws (2)
Tank Test Port
Warning Tag
Line Test Port
WARNING
THE SUBMERGED PUMP SYSTEM SUPPLYING THE
DISPENSERS MAY TURN ON UNEXPECTEDLY TO
PERFORM A LINE LEAK TEST. THIS MAY RESULT
IN FUEL SPRAYING DURING DISPENSER, PRODUCT
LINE, LEAK DETECTOR OR STP SERVICE.
1. CLOSE AFFECTED DISPENSER SHEAR VALVE AND TEST
FOR PROPER SHUTOFF OF THE VALVE IF PERFORMING
DISPENSER HYDRAULIC SERVICE.
2. REMOVE POWER TO THE SUBMERGED PUMP (STP) AND
TO LLD-300 AND LINE LEAK DETECTOR SYSTEM.
3. WEAR EYE PROTECTION.
4. COLLECT FUEL IN APPROVED CONTAINERS.
DO NOT CONTAMINATE ENVIRONMENT.
PERFORM THE FOLLOWING BEFORE BEGINNING SERVICE:
Pressurstat
Assembly
OFF
Cover - remove for
WPLLD Transducer &
Adaptor
Line Test Port -
remove plug for
Sensing Line
fitting
If installing SpikeCheck assy.
(Red Jacket P/N 388-080-5)
remove Pressurstat valve assy.
and replace with SpikeCheck
following Red Jacket's instructions.
wplld/quantumw1.eps