PLLD Site Prep and Installation Guide
Warning Tags
4-15
Figure 4-17. Example WPLLD Installation in pump w/Healy Mini-Jet
System (req’d. dielectric union & shutoff valve not
shown)
Warning Tags
WARNING tags [Figure 4-18] are provided with the WPLLD System. For your safety and the safety of others who may
service dispensers, submersible pumps, or WPLLD Systems, you must attach a tag to the console, submersible pump,
and dispenser filter where they can be seen clearly by a serviceman performing work on the system.
Figure 4-18. WARNING Tag
wplld\healy.eps
Sump sensor
Red Jacket Standard pump or,
Red Jacket Quantum pump
w/o SpikeCheck
WPLLD sensor
Containment
sump
SwiftCheck valve
Flexible fuel line
Note: Remove in-line check
valve, if present
Healy Mini-Jet
TM
Product line
to dispensers
Red Jacket
leak detector
fitting (Red
Jacket Part
No. 038-072)
WARNING
THE SUBMERGED PUMP SYSTEM SUPPLYING THE
DISPENSERS MAY TURN ON UNEXPECTEDLY TO
PERFORM A LINE LEAK TEST. THIS MAY RESULT
IN FUEL SPRAYING DURING DISPENSER, PRODUCT
LINE, LEAK DETECTOR OR STP SERVICE.
PERFORM THE FOLLOWING BEFORE BEGINNING SERVICE:
1. CLOSE AFFECTED DISPENSER SHEAR VALVE AND TEST
FOR PROPER SHUTOFF OF THE VALVE IF PERFORMING
DISPENSER HYDRAULIC SERVICE.
2. REMOVE POWER TO THE SUBMERGED PUMP (STP) AND
TO THE CONSOLE AND THE LINE LEAK DETECTOR SYSTEM.
3. WEAR EYE PROTECTION.
4. COLLECT FUEL IN APPROVED CONTAINERS.
DO NOT CONTAMINATE ENVIRONMENT.
TO ORDER TAGS - USE PART NO. 329801-001